WM40 96EnergyManagementSmart Modular Power AnalyzerType WM40 96 Front protection degree: IP65, NEMA4x, NEMA12Optical front communication port (ANSI type 2)Up to one RS232 and RS485 port (on request)Communication protocol: MODBUS-RTUMODBUS TCP/IP Ethernet port (on request)BACnet-IP over Ethernet port (on request)BACnet MS/TP over RS485, BTL approved (on request)Ethernet/IP port, ODVA approved (on request)Profibus DP V0 port (on request)Up to 6 digital inputs for tariff selection, “dmd” synch,gas/water (hot-cold) and remote heating metering (onrequest)Up to 8 static outputs (pulse, alarm, remote control)(on request)Up to 6 relay outputs (pulse, alarm, remote control)(on request)Up to 16 freely configurable alarms with OR/AND logiclinkable with up to either 4 relay outputs or up to 6static outputs (on request)Up to 4 analogue outputs ( 20mA, 10VDC) (onrequest) Class 0.5S (kWh) according to EN62053-22Class C (kWh) according to EN50470-3Class 2 (kvarh) according to EN62053-23Accuracy 0.2% RDG (current/voltage)Instantaneous variables readout: 4x4 DGTEnergies readout: 9 1 DGTSystem variables: VLL, VLN, A, VA, W, var, PF, Hz,phase-sequence, phase-asymmetry and phaseloss.Single phase variables: VLL, VLN, AL, An (calculatedor real depending on the option), VA, W, var, PFBoth system and singles phase variables withaverage, max and min calculationDirect neutral current measurement (on request)Harmonic analysis (FFT) up to the 32nd harmonic(current and voltage) with harmonics source detection(imported/exported, only via serial port)Energy measurements (imported/exported): total andpartial kWh and kvarh (inductive and capacitive) orbased on 6 different tariffs (on request)Energy measurements according to ANSI C12.20,CA 0.5, ANSI C12.1 (revenue grade)Gas, cold water, hot water, remote heatingmeasurements (on request)Run hours counter (8 2 DGT)Real time clock functionData stamping of up to 10,000 events: alarm, min,max, digital input status, digital output status, resets,programming changing (on request)Application adaptable display and programmingprocedure (Easyprog function)Universal power supply:24-48 VDC/AC, 100-240 VDC/ACFront dimensions: 96x96 mmProduct DescriptionThree-phase smart power analyzer with built-in applicationconfiguration system and LCD data displaying. Particularlyrecommended for the measurement of the main electricalvariables.WM40 is based on a modular housing for panel mountingwith IP65 (front) protection degree. Moreover the analyzercan be provided with digital outputs that can be either forpulse proportional to the active and reactive total, partialand tariff energy being measured or/and for alarm outputs.Specifications are subject to change without noticeThe instrument is equipped with optical communication port,further I/O’s such as: RS485/RS232, Ethernet, BACnet-IP,BACnet MS/TP or Profibus DP V0 communication ports,pulse and alarm outputs and 6 digital inputs or analogueoutputs are available on request. Parameters programmingand data reading can be easily performed by means ofWM3040Soft.WM40 96 DS 3101171

WM40 96How to orderWM40-96 AV5 3 H R4 CT S1 XXModelRange codeSystemPower SupplyA Inputs/OutputsB Inputs/OutputsCommunication and data stampingOptionType SelectionRange codesSystemPower supplyA Inputs/OutputsAV4: 400/690VLL AC1(2)AVLN: 160V to 480VLNVLL: 277V to 830VLLAV5: 400/690VLL AC5(6)AVLN: 160V to 480VLNVLL: 277V to 830VLLAV6: 100/208VLL AC5(6)AVLN: 40V to 144VLNVLL: 70V to 250VLLAV7: 100/208VLL AC1(2)AVLN: 40V to 144VLNVLL: 70V to 250VLL3:H:XX:R2:B Inputs/OutputsXX:A2:V2:TP:CT:noneDual channel20mADC outputDual channel 10VDCoutputOne temperatureand one process signal inputDirect neutral currentmeasurement Onetemperature and oneprocess signal inputL:100-240 /-10%(90 to 255) VDC/AC(50/60 Hz)24-48 /-15%(20 to 55) VDC/AC(50/60 Hz)O2:A2:V2:R4:Communication and data S.XX:S1:S3:E2:E3:B1:B2:B3:B4:E6:E7:P1:P2:2balanced andunbalanced load:3-phase, 4-wire;3-phase, 3-wire;2-phase, 3-wire;1-phase, 2-wirenoneRS485/RS232 portRS485/RS232 portwith data stampingEthernet / InternetportEthernet / Internetport with data stampingBACnet (IP) overEthernetBACnet (IP) overEthernet with datastampingBACnet (MS/TP)over RS485BACnet (MS/TP)over RS485 withdata stampingEthernet/IP portEthernet/IP port withdata stampingProfibus DP/V0 portProfibus DP/V0 portwith data stampingO6:OptionsXX:noneDual channel relayoutputDual channel staticoutputDual channel20mADC outputDual channel 10VDCoutputAdvanced six channel digital inputs four channel relayoutputs OR/ANDalarm logic managementAdvanced six channel digital inputs six channel staticoutputs OR/ANDalarm logic managementnoneSpecifications are subject to change without noticeWM40 96 DS 310117

WM40 96Position of modules and combinationRefDescriptionMain features9Dual relay output (SPDT)10Dual static output (AC/DC Opto-Mos)1112131415Dual analogue output ( 20mADC)Dual analogue output ( 10VDC)RS485 / RS232 port moduleEthernet/TCP IP port moduleBACnet-IP port module Inputs/system: AV5.3 Power supply: H Inputs/system: AV6.3 Power supply: H Inputs/system: AV4.3 Power supply: H Inputs/system: AV7.3 Power supply: H Inputs/system: AV5.3 Power supply: L Inputs/system: AV6.3 Power supply: L Inputs/system: AV4.3 Power supply: L Inputs/system: AV7.3 Power supply: L 2-channel Alarm or/and pulse output 2-channel Alarm or/and pulse output 2-channel 2-channel Max. 115.2 Kbps RJ45 10/100 BaseT Based on Ethernet bus16BACnet MS/TP port module Over RS48512345WM40 base provided with display, power supply,measuring inputs, optical front communication port.67817BACnet MS/TP port module18Combined digital inputs and Relay outputs (SPDT)19Combined digital inputs and Static outputs (AC/DCOpto-Mos)20RS485 / RS232 port module withintegrated Memory21Ethernet port module with integrated Memory2223BACnet over IP port module withintegrated MemoryTemperature Process signal measurements( C/ F) Over RS485 Data Stamping 6-input channels 4-output channels Complex tariff management OR/AND logic management 6-input channels 6-output channels Complex tariff management. OR/AND logic management Max. 115.2 Kbps Data stamping RJ45 10/100 BaseT Data Stamping Based on Ethernet bus Data Stamping “Pt” type input 20mA inputPart numberPos. A Pos. B Pos. CWM40 AV5 3 HWM40 AV6 3 HWM40 AV4 3 HWM40 AV7 3 HWM40 AV5 3 LWM40 AV6 3 LWM40 AV4 3 LWM40 AV7 3 LM O R2XM O O2XM O A2M O V2M C 485 232M C ETHM C BAC IPXXXXXXXM C BAC MSXM C BAC MS MXM F I6 R4XM F I6 O6XM C 485 232 MXM C ETH MXM C BAC IP MXMATPXX24Direct neutral current measurement Temperature As above signal input like a common currentProcess signal measurements ( C/ F)input (CT ratio etc.)MATPN2526Ethernet/IP portEthernet/IP port with integrated MemoryMCEIMCEIMXX27Profibus moduleMCPBX28Profibus module with integrated memoryMCPBMX Based on Ethernet Based on Ethernet Profibus DP V0 Over RS485 Profibus DP V0 Over RS485 Data stampingNOTE: The position of the modules shall respect the sequence A-B-C. Possiblearrangements are M, M-A, M-B, M-C, M-A-B, M-A-C, M-B-C and M-A-B-C where“M” is the basic module.It is possible to use the WM40-96 without any additional module as a simpleindicator.Specifications are subject to change without noticeWM40 96 DS 3101173

WM40 96Input specificationsRated inputsCurrent typeCurrent range (by CT)System type: 1, 2 or3-phaseGalvanic insulation bymeans of built-in CT’sAV5 and AV6: 5(6)AAV4 and AV7: 1(2)AStart up current AV4, AV7Energy additional errorsInfluence quantitiesVoltage(by direct connection or VT/PT) AV4, AV5: 400/690VLL;AV6, AV7: 100/208VLLAccuracy (Display RS485)(@25 C 5 C,R.H. 60%, 48 to 62 Hz)In: see below, Un: seebelowAV4 modelIn: 1A, Imax: 2A; Un: 160to 480VLN (277 to 830VLL)AV5 modelIn: 5A, Imax: 6A; Un: 160to 480VLN (277 to 830VLL)AV6 modelIn: 5A, Imax: 6A; Un:40 to 144VLN (70 to250VLL)AV7 modelIn: 1A, Imax: 2A; Un: 40 to144VLN (70 to 250VLL)Current AV4, AV5, AV6, AV7modelsFrom 0.01In to 0.05In: (0.5% RDG 2DGT)From 0.05In to Imax: (0.2% RDG 2DGT)Phase-neutral voltageIn the range Un: (0,2%RDG 1DGT)Phase-phase voltageIn the range Un: (0.5%RDG 1DGT)Frequency 0.01Hz (45 to 65Hz)Active and Apparent powerFrom 0.01In to 0.05In, PF1: (1%RDG 1DGT)From 0.05In to ImaxPF 0.5L, PF1, PF0.8C: (0.5%RDG 1DGT)Power Factor [0.001 0.5% (1.000 - “PFRDG”)]Reactive powerFrom 0.02In to0.05In, senφ 1: (1.5%RDG 1DGT)From 0.05In to Imax, senφ1: (1%RDG 1DGT)From 0.05In to0.1In, senφ 0.5L/C: (1.5%RDG 1DGT)From 0.1In to Imax, senφ0.5L/C: (1%RDG 1DGT)Active energyClass 0.5S according toEN62053-22, ANSI C12.20Class C according toEN50470-3.Reactive energyClass 2 according toEN62053-23, ANSI C12.1.Start up current AV5, AV65mA41mAAccording to EN62053-22,ANSI C12.20,Class B or C according toEN50470-3, EN62053-23,ANSI C12.1Total Harmonic Distortion (THD) 1% FS (FS: 100%)AV4: Imin: 5mARMS;Imax: 3A; Umin: 30VRMS;Umax: 679VpAV5: Imin: 5mARMS; Imax:15Ap; Umin: 30VRMS;Umax: 679VpAV6: Imin: 5mARMS; Imax:15Ap; Umin: 30VRMS;Umax: 204VpAV7: Imin: 5mARMS; Imax:3A; Umin: 30VRMS; Umax:204VpTotal Demand Distortion (TDD) 1% FS (FS: 100%)Imin: 5mA RMS; Imax:15ApK-Factor and factor K (0.5%RDG 1DGT)Temperature drift 200ppm/ CSampling rate3200 samples/s @ 50Hz,3840 samples/s @ 60HzMeasurementsSee “List of the variablesthat can be connected to:”TRMS measurements ofdistorted wave forms.By means of CT’sMethodCoupling typeCrest factorAV5, AV6: 3(15A max. peak)AV4, AV7: 3(3A max. peak)Current OverloadsContinuous (AV5 and AV6)Continuous (AV4 and AV7)For 500ms (AV5 and AV6)For 500ms (AV4 and AV7)6A, @ 50Hz/60Hz2A, @ 50Hz/60Hz120A, @ 50Hz/60Hz40A, @ 50Hz/60HzVoltage OverloadsContinuousFor 500ms1.2 Un2 UnInput impedance400VL-L (AV4 and AV5)208VL-L (AV6 and AV7)5(6)A (AV5 and AV6)1(2)A (AV4 and AV7) Frequency40 to 440 Hz1.6MΩ1.6MΩ0.2VA0.2VASpecifications are subject to change without noticeWM40 96 DS 310117

WM40 96Output specificationsRelay outputs (M O R2)Physical outputsPurposeTypeConfigurationFunctionAlarmsMin. response timePulseSignal retransmissionPulse typePulse durationRemote controlledoutputsInsulationStatic outputs (M O O2)Physical . response time2 (max. 1 module perinstrument)For either alarm output orpulse outputRelay, SPDT typeAC 1-5A @ 250VAC; AC15-1A @ 250VACBy means of the front keypadThe outputs can work asalarm outputs but alsoas pulse outputs, remotecontrolled outputs, or inany other combination.Up alarm and down alarmand windows alarm (in andout) linked to the virtualalarms, other details seeVirtual alarms 200ms, filters excluded.Set-point on-time delay: “0 s”.Total: kWh, -kWh, kvarh,-kvarh.Partial: kWh, -kWh, kvarh, -kvarh.Programmable from 0.001to 10.00 kWh/kvarh perpulse. The above listedvariables can be connectedto any output. 100ms 120msec (ON), 120ms (OFF), accordingto EN62052-31The activation of theoutputs is managedthrough the serialcommunication portSee “Insulation betweeninputs and outputs” tableOpto-Mos type2 (max. 1 module perinstrument)For either pulse output oralarm outputVON:2.5VAC/DC/max.100mAVOFF: 42VDC max.By means of the front keypadThe outputs can work asalarm outputs but alsoas pulse outputs, remotecontrolled outputs, or inany other combination.Up alarm and down alarmlinked to the virtual alarms,other details see Virtualalarms 200ms, filters excluded. Setpoint on-time delay: “0 s”.Specifications are subject to change without noticePulseSignal retransmissionPulse typePulse durationRemote controlled outputsInsulation20mA analogue outputs(M O A2)Number of outputsAccuracy(@ 25 C 5 C, R.H. 60%)RangeConfigurationSignal retransmissionScaling factorResponse timeRippleTotal temperature driftLoadInsulation10VDC analogue outputs(M O V2)Number of outputsAccuracy(@ 25 C 5 C, R.H. 60%)RangeConfigurationSignal retransmissionWM40 96 DS 310117Total: kWh, -kWh, kvarh,-kvarh.Partial: kWh, -kWh, kvarh, -kvarh.Programmable from 0.001to 10.00 kWh/kvarh perpulse. The above listedvariables can be connectedto any output. 100ms 120msec (ON), 120ms (OFF), accordingto EN62052-31The activation of theoutputs is managedthrough the serialcommunication portSee “Insulation betweeninputs and outputs” table2 per module (max. 2modules per instrument) 0.2%FS0 to 20mABy means of the front keypadThe signal output canbe connected to anyinstantaneous variableavailable in the table “Listof the variables that can beconnected to”.Programmable withinthe whole range ofretransmission. 400 ms typical (filterexcluded) 1% (according to IEC60688, EN 60688) 500 ppm/ C 600ΩSee “Insulation betweeninputs and outputs” table2 per module (max. 2modules per instrument) 0.2%FS0 to 10 VDCBy means of the front keypadThe signal output canbe connected to anyinstantaneous variableavailable in the table “Listof the variables that can beconnected to”.5

WM40 96Output specifications (cont.)Scaling factorResponse timeRippleTotal temperature driftLoadInsulationRS485 serial port(M C 485 232 on request)RS485TypeConnectionsAddressesProtocolData (bidirectional)Dynamic (reading only)Programmable withinthe whole range ofretransmission. 400 ms typical (filterexcluded) 1% (according to IEC60688, EN 60688) 350 ppm/ C 10kΩSee “Insulation betweeninputs and outputs” tableBaud-rateNoteInsulationMultidrop, bidirectional(static and dynamicvariables)2-wireMax. distance 1000m,termination directly on themodule247, selectable by meansof the front key-padMODBUS/JBUS (RTU)Module with data stampingand event recording memory(M C 485 232 M)Event stampingType of dataSystem and phasevariables: see table “List ofvariables.”Static (reading and writing only) All the configurationparameters.Data format1 start bit, 8 data bit, no/even/odd parity,1 stop bitBaud-rateSelectable: 9.6k, 19.2k,38.4k, 115.2k bit/sDriver input capability1/5 unit load. Maximum160 transceivers on thesame bus.NoteWith the rotary switch(on the back of the basicunit) in lock positionthe modification of theprogramming parametersand the reset commandby means of the serialcommunication is notallowed. In this case justthe data reading is allowed.InsulationSee “Insulation betweeninputs and outputs” tableRS232 port (on request)TypeBidirectional (static anddynamic variables)Connections3 wires. Max. distance 15mProtocolMODBUS RTU /JBUSData (bidirectional)Dynamic (reading only)System and phasevariables: see table “List ofvariables.”Static (reading and writing only) All the configurationparametersData format1 start bit, 8 data bit, no/even/odd parity,1 stop bit6Selectable: 9.6k, 19.2k,38.4k, 115.2k bit/sWith the rotary switch(on the back of the basicunit) in lock positionthe modification of theprogramming parametersand the reset commandby means of the serialcommunication is notallowed. In this case justthe data reading is allowed.See “Insulation betweeninputs and outputs” tableStamping formatNumber of eventsData management typeData stampingType of dataStamping formatNumber of variablesTime intervalData management typeMemory typeEthernet/Internet port(M C ETH on request)ProtocolsIP configurationPortClient connectionsConnectionsData (bidirectional)Dynamic (reading only)Static(reading and writing only)NoteAlarm, min, max, digitalinput status, digital outputstatus as remote control,resets.Date (dd:MM:yy) and hour(hh:mm:ss) reference.Up to 10,000FIFOAny measured variable canbe stored in the memory.Date (dd:MM:yy) and hour(hh:mm:ss) reference.Up to 19 different type ofvariables can be stored.From 1 minute up to 60minutes.FIFOData flashModbus TCP/IPStatic IP / Netmask /Default gatewaySelectable (default 502)Max 5 simultaneouslyRJ45 10/100 BaseTXMax. distance 100mSystem and phasevariables: see table “List ofvariables.”All the configurationparameters.With the rotary switch(on the back of the basicunit) in lock positionthe modification of theprogramming parametersand the reset commandby means of the serialcommunication is notSpecifications are subject to change without noticeWM40 96 DS 310117

WM40 96Output specifications (cont.)Insulationallowed. In this case justthe data reading is allowed.See “Insulation betweeninputs and outputs” tableModule with data stampingand event recording memory(M C ETH M)Event stampingType of dataStamping formatNumber of eventsData management typeData stampingType of dataStamping formatNumber of variablesTime intervalData management typeMemory typeBACnet-IP(on request)ProtocolsBACnet-IPIP configurationPortDevice object instanceSupported servicesSupported objectsIP configurationModbus TCP/IPClient connectionsConnectionsDataDynamic (reading only)Static(reading and writing only)NoteAlarm, min, max, digitalinput status, digital outputstatus as remote control,resets.Date (dd:MM:yy) and hour(hh:mm:ss) reference.Up to 10,000FIFOAny measured variable canbe stored in the memory.Date (dd:MM:yy) and hour(hh:mm:ss) reference.Up to 19 different type ofvariables can be stored.From 1 minute up to 60minutes.FIFOData flashInsulationStatic IP / Netmask /Default gatewayFixed: BAC0h0 to 9999 selectable bykey-pad 0 to 2 22-2 4.194.302, selectable byprogramming software orby BACnet.“I have”, “I am”, “Who has”,“Who is”, “Read (multiple)Property”Type 2 (analogue value,including COV property),Type 5 (binary-value forup to 16 virtual alarmre-transmission) Type 8(device)Static IP / Netmask /Default gatewaySee “Ethernet/Internet port”aboveModbus only: max 5simultaneouslyRJ45 10/100 BaseTX Max.distance 100mSpecifications are subject to change without noticeAll the configurationparameters (Modbus only)With the rotary switch(on the back of the basicunit) in lock positionthe modification of theprogramming parametersand the reset commandby means of the serialcommunication is notallowed anymore. In thiscase just the data readingis allowed.See “Insulation betweeninputs and outputs” tableModule with data stampingand event recording memory(M C BAC IP M)Event stampingType of dataBACnet-IP (formeasurement readingpurpose and to write objectdescription) and ModbusTCP/IP (for measurementreading purpose and forprogramming parameterpurpose)System and phasevariables (BACnet-IP andModbus): see table “List ofvariables”Stamping formatNumber of eventsData management typeData stampingType of dataStamping formatNumber of variablesTime intervalData management typeMemory typeBACnet MS/TP (on request)Available portsRS485 portTypeConnectionsDevice object instanceProtocolSupported servicesWM40 96 DS 310117Alarm, min, max, digitalinput status, digital outputstatus as remote control,resets.Date (dd:MM:yy) and hour(hh:mm:ss) reference.Up to 10,000FIFOAny measured variable canbe stored in the memory.Date (dd:MM:yy) and hour(hh:mm:ss) reference.Up to 19 different type ofvariables can be stored.From 1 minute up to 60minutes.FIFOData flash2: RS485 and EthernetMultidrop, mono-directional(dynamic variables)2-wire Max. distance1000m, termination directlyon the module0 to 9999 selectable bykey-pad0 to 2 22-2 4.194.302,selectable by means ofprogramming software orby BACnet.BACnet MS/TP (formeasurement readingpurpose and to write objectdescription)“I have”, “I am”, “Who has”,7

WM40 96Output specifications (cont.)Supported objectsData (mono-directional)DynamicStaticData formatBaud-rateDriver input capabilityMAC addressesEthernet portProtocolIP configurationModbus PortClient connectionsConnectionsDataDynamic (reading only)“Who is”, “Read (multiple)Property”Type 2 (analogue value,including COV property),Type 5 (binary-value forup to 16 virtual alarmre-transmission)Type 8 (device)System and phasevariables: see table “List ofvariables.”Not available1 start bit, 8 data bit, noparity,1 stop bitSelectable: 9.6k, 19.2k,38.4k kbit/s1/5 unit load. Maximum160 transceivers on thesame bus.Selectable: 0 to 127Modbus TCP/IP (forprogramming parameterpurpose)Static IP / Netmask /Default gatewaySelectable (default 502)Modbus only: max 5simultaneouslyRJ45 10/100 BaseTX Max.distance 100mSystem and phasevariables: see table “List ofvariables.”NoteInsulationApprovalEthernet/IP (on request)ProtocolsIP configurationModbus PortEthernet/IP portTopologyLevelConnectionMessagingSupported featuresStatic(reading and writing only) All the configurationparameters (Modbus only).Bacnet MS/TP event recording memoryEvent stampingType of dataStamping formatNumber of eventsData management typeData stampingType of dataStamping formatNumber of variablesTime intervalData management typeMemory type8Alarm, min, max, digitalinput status, digital outputstatus as remote control,resets.Date (dd:MM:yy) and hour(hh:mm:ss) reference.Up to 10,000FIFODataDynamic (reading only)Any measured variable canbe stored in the memory.Date (dd:MM:yy) and hour(hh:mm:ss) reference.Up to 19 different type ofvariables can be stored.From 1 minute up to 60minutes.FIFOData flashEthernet/IP event recording memoryStatic(reading and writing only)Event stampingType of dataWith the rotary switch(on the back of the basicunit) in lock positionthe modification of theprogramming parametersand the reset commandby means of the serialcommunication is notallowed. In this case justthe data reading is allowed.See “Insulation betweeninputs and outputs” tableBTLEthernet/IP (formeasurement readingpurpose) and ModbusTCP/IP (for programmingparameter purpose)Static IP / Netmask /Default gatewaySelectable (default 502)Modbus only: max 5simultaneously RJ4510/100 Base TXMax distance 100mStarRJ45 standardMax distance 100mCommercial levelConnection establishment:targetClass 1 and class 3messangingACD (Address ConflictDetection)UCMMList service 0x0004List identity 0x0063Register session 0x0065Unregister session 0x0066Send RR data 0x006FSend Unit Data 0x0070System and phasevariables (Ethernet/IP):see Ethernet/IP protocoldocumentAll the configurationparameters (Modbus TCPonly)Alarm, min, max, digitalinput status, digital outputstatus as remote control,resets.Specifications are subject to change without noticeWM40 96 DS 310117

WM40 96Output specifications (cont.)Stamping formatNumber of eventsData management typeData stampingType of dataStamping formatNumber of variablesTime intervalData management typeMemory typeInsulationApprovalProfibus (MCPB)Available portsUSBPurposeConnectorProtocolData formatBaudrateAddressProfibusPurposeModules Selectable:Data formatConnectorProtocolBaudrateAddressNoteDate (dd:MM:yy) and hour(hh:mm:ss) reference.Up to 10,000FIFOAny measured variable canbe stored in the memory.Date (dd:MM:yy) and hour(hh:mm:ss) reference.Up to 19 different type ofvariables can be stored.From 1 minute up to 60minutes.FIFOData flashSee “Insulation betweeninputs and outputs” tableEthernet/IP conformancetested (ODVA)2: USB and Profibus DPV0Programmable parameterssettingUSB micro BModbus RTU1 start bit, 8 data bit,no parity,1 stop bitautorange depending onthe master (max 115200bps)1Data reading (12programmable profilesrealtime selectable) ;remote output control ;remote tariff control ;output up to 4 bytes, inputup to 62 wordstotalizers : FLOAT orINT32; electrical variables: FLOAT or INT16 ; statusvariables : UINT16RS485 DB9Profibus DP V0 slave9.6 k to 12 Mbps (9.6,19.2, 45.45, 93.75, 187.5,or 500 kbps; 1.5, 3, 6, or12 Mbps)2-125 (default 126)With the rotary switch(on the back of the basicunit) in lock positionthe modification of theprogramming parametersand the reset commandby means of the serialcommunication is notallowed. In this case justthe data reading is allowed.Specifications are subject to change without noticeInsulationModule with data stampingand event recording memory(MCPBM)Event stampingType of dataStamping formatNumber of eventsData management typeData stampingType of dataStamping formatNumber of variablesTime intervalData management typeMemory typeRelay Output and DigitalInput (M F I6 R4 on request)Relay OutputsPhysical outputsPurposeTypeConfigurationFunctionStandard alarm modesAdvanced alarm modesWM40 96 DS 310117See “Insulation betweeninputs and outputs” tableAlarm, min, max, digitalinput status, digital outputstatus as remote control,resets.Date (dd:MM:yy) and hour(hh:mm:ss) reference.Up to 10,000FIFOAny measured variable canbe stored in the memory.Date (dd:MM:yy) and hour(hh:mm:ss) reference.Up to 19 different type ofvariables can be stored.From 1 minute up to 60minutes.FIFOData flash4 (max. 1 module perinstrument)For either pulse output oralarm outputRelay, SPST typeAC 1-5A @ 250VAC; AC15-1A @ 250VACOnly by means of theprogramming softwareWM3040Soft. In this lattercase using either the serialcommunication port or thefront optical port.The outputs can work asadvanced alarm outputsand as remote controlledoutputs, or in any othercombination.Up alarm, down andwindow alarm. Thereis also the possibility toremote the control of theoutputs: the activation ofthe outputs is managedthrough the serialcommunication port (in thiscase the local alarms aredisabled).“OR” or “AND” or“OR AND” functions(see “Alarm parameterand logic” page). Freelyprogrammable on up to 16alarms.9

WM40 96Output specifications (cont.)Controlled variablesSet-point adjustmentHysteresisOn-time delay 0 to 255sOutput statusMin. response timeDigital inputsNumber of inputsPurposeInput frequencyPrescaler adjustmentOpen Contact voltageClosed Contact currentContact resistanceInput voltageWorking mode10The alarms can beconnected to any variableavailable in the table “Listof the variables that can beconnected to”From 0 to 100% of thedisplay scaleFrom 0 to full scaleSelectable: normallyde-energized or normallyenergized 200ms, filters excluded.Set-point on-time delay: “0 s”.6 (voltage-free contacts)Contact status reading.“dmd” measurementssynchronisation and clocksynchronisation. Energytariff selection. Utility metercounters. Trip counter.Interfacing with externalenergy meters ( kWh, kvarh, -kWh, -kvarh).20Hz max, duty cycle 50%From 0.1 to 999.9 m3 orkWh/pulse 3.3VDC 1mADC 300Ω closed contact 50kΩ open contact0 to 0.5VDC: LOW2.4 to 25VDC: HIG Total and partial energymeters (kWh and kvarh)without digital inputs; Total and partial energymeters (kWh and kvarh)managed by time periods(t1-t2-t3-t4-t5-t6), Wdmd synchronisation(the synchronisation ismade every time the tariffchanges) and GAS (m3)or WATER (hot/cold/m3)or remote heating (kWh)meters; Total and partialenergy meters (kWhand kvarh) managed bytime periods (t1-t2), Wdmd synchronisation (thesynchronisation is madeindependently of the tariffselection) and GAS (m3)or WATER (hot/cold/m3)or remote heating (kWh)meters; Total energy (kWh,kvarh) and GAS, WATER(hot-cold m3) and remoteInsulationOpto-mos Output andDigital Input(M F I6 O6 on request)Static OutputsPhysical outputsPurposeType of outputsSignalFunctionSignal retransmissionPulse typePulse durationheating meters (3 choicesonly). Remote alarm reset. Trip counter of installationprotection. Direct measurements forthe power quality analysis(LV or MV/HV connection); Indirect energy and powermeasurements by meansof external energy meters(LV or MV/HV connection); Direct measurements forthe instantaneous variables(LV connection) andindirect measurements forthe energy variables (LV orMV/HV).By means of opto-mos See“Insulation between inputsand outputs” table.6 (max. 1 module perinstrument)For either pulse output oralarm outputOpto-MosVON: 2.5VDC/max.100mAVOFF: 42VDCThe outputs can work aspulse outputs, but alsoas alarm outputs, remotecontrolled outputs, or inany other combination.Total: kWh, -kWh, kvarh,-kvarh.Partial: kWh, -kWh, kvarh, -kvarhTariff: kWh, -kWh, kvarh,-kvarh.Programmable from 0.001to 10.00 kWh/kvarh perpulse. Outputs connectableto the energy meters (kWh/kvarh) 100ms 120ms (ON), 120ms (OFF), accordingto EN62052-31Advanced tariff managementNo. of tariffsNo. of total energiesData formatDigital inputsNumber of inputsPurposeUp to 6Up to 4 ( kWh, -kWh, kvarh, -kvarh)9-DGT for Total andpartial/tariff, gas and watermetering.6 (voltage-free contacts)Contact status reading.Specifications are subject to change without noticeWM40 96 DS 310117

WM40 96Output specifications (cont.)Input frequencyPrescaler adjustmentOpen Contact voltageClosed Contact currentContact resistanceInput voltageWorking mode“dmd” measurementssynchronisation and clocksynchronisation. Energytariff selection. Utility metercounters. Trip counter.Remote input. Interfacingwith external energymeters ( kWh, kvarh,-kWh, -kvarh).20Hz max, duty cycle 50%From 0.1 to 999.9 m3 orkWh/pulse 3.3VDC 1mADC 300Ω closed contact 50kΩ open contact0 to 0.5VDC LOW2.4 to 25VDC HIG Total and partial energymeters (kWh and kvarh)without digital inputs; Total and partial energymeters (kWh and kvarh)managed by time periods(t1-t2-t3-t4-t5-t6), Wdmd synchronisation(the synchronisation ismade every time the tariffchanges) and GAS (m3)or WATER (hot/cold/m3)or remote heating (kWh)meters; Total and partialenergy meters (kWhand kvarh) managed bytime periods (t1-t2), Wdmd synchronisation (thesynchronisation is madeindependently of the tariffselection) and GAS (m3)or WATER (hot/cold/m3)or remote heating (kWh)meters; Total energy (kWh,kvarh) and GAS, WATER(hot-cold m3) and remoteheating meters (3 choicesonly). Remote alarm reset. Remote input channelstatus. Trip counter of installationprotection. Direct measurements forthe power quality analysis(LV or MV/HV connection); Indirect energy and powermeasurements by meansof watt-hour meters (LV orMV/HV connection); Direct measurements forthe instantaneous variables(LV connection) andSpecifications are subject to change without noticeInsulationindirect measurements byexternal energy meters (LVor MV/HV).By means of opto-mos See“Insulation between inputsand outputs” table.Temperature andProcess signal inputs(M A T P on request)Temperature signalNumber of inputs1Accuracy (Display RS485) See table “Temperatureinput characteristics”Temperature drift 150ppm/ CTemperature probePt100, Pt1000Number of wires2 or 3-wire connectionWire compensationUp to 10ΩEngineering unitSelectable C o FProcess signalNumber of inputs1Accuracy (Display RS485) (0,2%RDG 2DGT) da 0%a 25% FS;

EN62053-22, ANSI C12.20 Class C according to EN50470-3. Reactive energy Class 2 according to EN62053-23, ANSI C12.1. Start up current AV5, AV6 5mA Start up current AV4, AV7 1mA Energy additional errors According to EN62053-22, ANSI C12.20, Influence quantities Class B or C accord

Related Documents:

Modular: 18" x 36" (45.7 cm x 91.4 cm) Stratatec Patterned Loop Dynex SD Nylon 100% Solution Dyed 0.187" (4.7mm) N/A ER3 Modular, Flex-Aire Cushion Modular, Conserv Modular, ethos Modular 24" x 24": 18" x 36": Coordinate Group: Size: Surface Texture: Yarn Content: Dye Method: Pile Height Average: Pattern Match: Modular

modular cnc router plans 2009v1 copyright modular cnc @2009 for personal use only item no. part number description vendor material cost qty. 1 mc-z-001 drive end plate modular cnc hdpe 10.00 1 2 mc-z-002 end plate modular cnc hdpe 8.00 1 3 mc-z-003 top plate modular cnc hdpe 12.50 1 4 mc-z-005 linear rod speedy metals 1018 crs 3.00 2

smart grids for smart cities Strategic Options for Smart Grid Communication Networks To meet the goals of a smart city in supporting a sustainable high-quality lifestyle for citizens, a smart city needs a smart grid. To build smart cities of the future, Information and Communications Techn

2019), the term "smart city" has not been officially defined (OECD, 2019; Johnson, et al., 2019). However, several key components of smart cities have already been well-established, such as smart living, smart governance, smart citizen (people), smart mobility, smart economy, and smart infrastructure (Mohanty, et al., 2016).

Agenda and Target Discussion -Smart City What Smart City Components SHARED LIFE Modular Data Centers City Dashboard GIS CONVENIENT LIFE Smart Transportation - ITMS, Smart Parking, Integrated Public Transit, VMS, Traffic enforcement Smart Power - Intelligent Inspection Management System, Intelligent O&M systems .

Smart Home/Business Smart Meters (AMI) Smart Distribution System S t Utilit . 9Smart Meter Plan Filing - August 14, 2009 9Anticipated Smart Meter PUC approval - Mid-April 2010 . Up to 600,000 Smart Meters and associated infrastructure, supporting PECO's Act 129 Smart Meter Initiative Multiple Smart Grid Investments

emissions reduction from smart grid deployment 28 14. Smart grid product providers 33 List of Tables 1. Characteristics of smart grids 7 2. Workshop contributions to the Smart Grids Roadmap 8 3. Smart grid technologies 19 4. Maturity levels and development trends of smart grid technologies 20 5. Select national smart grid deployment efforts 21 6.

Smart Grid and Cyber-Physical Systems Office National Institute of Standards and Technology U.S. Department of Commerce Smart Grid And CPS Testbed Update Smart Grid Federal Advisory Committee Meeting June 3, 2014. 2. Smart Grid and Cyber ‐ Physical Systems Testbeds Layout. Smart Microgrid Control Smart andRoom Intelligent Device Smart Storage .