Performance Climate Changer Air Handlers Sizes 3-120

2y ago
8 Views
3 Downloads
3.64 MB
232 Pages
Last View : 2m ago
Last Download : 3m ago
Upload by : Tripp Mcmullen
Transcription

CatalogPerformance Climate Changer Air HandlersSizes 3-120Indoor and Outdoor UnitsApplication and Performance InformationSeptember 2015CLCH-PRC022B-EN

IntroductionPerformance Climate Changer air handlers combine the Trane tradition of engineeringexcellence with the latest in manufacturing technology to give you an energy efficient air handlerwith superior performance, the highest quality and reliability, and the lowest installed cost in theindustry. This air handler was designed to incorporate such features as component flexibility,integrated control options, and proven performance to give you the optimal system to clean, filter,dehumidify, heat, and cool your building.Superior Performance ASHRAE 111 Class 6 low-leak casing design achieving less than 1.0 percent leakage rate at /- 8 inches w.g. Less than L/240 @ /- 8 inches w.g. panel and door deflection 2-inch R13 foam-insulated, mid-span thermal break panels and thermal break doors Casing thermal resistance ratio TR-value of 0.6 New filter technology that exceeds LEED requirements and reduces filter pressure drops up to50 percent versus previous designsIndustry-Leading Energy Efficiency AMCA 611-certified Traq airflow monitoring station Economizer section meets or exceeds all mandatory requirements prescribed by CaliforniaBuilding Energy Efficiency Standard Title 24. Total energy-recovery wheels Cool Dry Quiet (CDQ ) desiccant dehumidification wheels Discharge plenums and plenum fan sections available with variable size, type, and location ofopenings to reduce static pressure loss and lower energy consumption 50,000 hour LED service lights Low-leak, high thermal performance casing design All airfoil-bladed and Traq dampers meet ASHRAE 90.1 lowest specified leakage requirements High-efficiency coil fins deliver superior heat transfer while allowing face velocities in excessof 625 fpm without moisture carryoverSystem Optimization Optimal design to meet the Trane EarthWise design philosophy incorporating high-efficiencyair handlers and water chillers with low flow rates and low temperatures. Factory-engineered, -mounted, and -tested control packages with properly sealed casingopenings. Variety of coil types with high-efficiency coil fins allow lower coil approach temperature andreduce chance of moisture carryover Ability to choose the exact number of fins per foot of coil surface to enhance heat transfer andair pressure performance Wide array of fan options including motorized impellers, direct-drive plenum fans, belt-driveplenum fans, and housed fans Control options to easily incorporate fan pressurization and demand control ventilationstrategies. Design and analysis tools provide whole building analysis, acoustical design guidance,equipment performance data, and suggested control strategies to help achieve optimumsystem design with tailored energy, IAQ, and project budget solutions. 2015 Trane All rights reservedCLCH-PRC022B-EN

IntroductionHighest Quality UL/CUL listed AHRI Standard 430-certified air-handling unit AHRI Standard 410-certified coils are all factory tested AHRI Standard 1060-certified energy wheels All fans are dynamically balanced in the horizontal and vertical planes All fans with VFDs undergo inverter balancing Formulated panels and integral base frame minimize seams that could introduce air leak paths Integrated raceway for wiring protection Integrated, fully-enclosed control panel for starters, VFDs, and unit-mounted controllers Pre-engineered, factory-mounted controls, including end devices, motor controllers, VFDs,unit-mounted DDC controllers, Traq damper ventilation control section, UL-listed turnkeycontrol packagesLowest Installed Cost Lifting lugs included on the integral base frame Indoor units ship with skid designed for forklift transport Variable height, size, type, and location of openings on discharge plenums minimize ducttransitions Factory-installed interoperable controls shorten construction cycles, simplify job-sitecoordination, reduce installation time and expense, and provide single-source responsibilityfor warranty and service issues Single-point power is available with high-voltage distribution block and external main unitdisconnect with lockout/tagout capabilities. External service module with 15 amp GFCI receptacle, light switch Controller display and communications port Quick-connect wiring minimizes installation costs and provides wiring integrity betweensections Factory-installed conduit connectors eliminate penetrations in the wrong location Motor leads can be run through flexible metal conduits to external motor junction box. Building Information Modeling (BIM) drawings to minimize jobsite ductwork, electrical, pipingand structural interference Duct supports designed into factory roof curbs for pre-connection of ductworkCopyrightThis document and the information in it are the property of Trane, and may not be used orreproduced in whole or in part without written permission. Trane reserves the right to revise thispublication at any time, and to make changes to its content without obligation to notify any personof such revision or change.TrademarksAll trademarks referenced in this document are the trademarks of their respective owners.Revision HistoryAdded new information including motorized impellers.CLCH-PRC022B-EN3

Table of ContentsIntroduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Superior Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Industry-Leading Energy Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .System Optimization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Highest Quality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Lowest Installed Cost . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22233Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Form, Function and Flexibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Reduces Footprint when Stacked . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Eases Retrofit, Renovation, and Replacement . . . . . . . . . . . . . . . . . . . . . 11Airside Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Construction and Integrity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Engineered for Good IAQ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Sound-Sensitive Solutions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Provide Accurate, Tested Sound Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Minimize Sound Source . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Increase Operating Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Turnkey Control Solutions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Single-Source Responsibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Single-Point Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Reduced Installation Costs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Reliable Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Open Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Service Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .151616161717Proven Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18AHRI Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Miami/Dade County Notice of Compliance (NOA) . . . . . . . . . . . . . . . . . .UL Listing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .IBC Seismic Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .AMCA Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Canadian Registration Number (CRN) . . . . . . . . . . . . . . . . . . . . . . . . . . . .ISO Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18181818191919HVAC Design Fundamentals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Provide Proper Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Maintain Building Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Protect Coils from Freezing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Filter Contaminants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Particulate Filter Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Gases and Vapors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Minimize Microbial Growth . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Water Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Dehumidification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 254CLCH-PRC022B-EN

Humidification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26Provide Quiet Comfort . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26Application Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28Air Handler Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28Single-Path Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28Dual-Path Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29Standard AHU Arrangements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30Draw-Thru Arrangements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30Blow-Thru Arrangements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30Stacked Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31Arrangements for Specific Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31Building Pressurization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Building Pressurization with Return Fan and Economizer . . . . . . . . . . . .Building Pressurization with Exhaust Fan and Economizer . . . . . . . . . . .Building Pressurization with Barometric Relief Economizer . . . . . . . . . .Dehumidification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Dehumidification with CDQ (Cool, Dry, Quiet) Desiccant Wheels . . . .Dehumidification with Coil Runaround Loops . . . . . . . . . . . . . . . . . . . . .Dehumidification with a Split Dehumidification Unit (SDU) . . . . . . . . . .Dehumidification with Hot-Water Heat-Recovery Coils . . . . . . . . . . . . . .313132333334343538Energy Recovery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38Energy Recovery with a Total Energy Wheel . . . . . . . . . . . . . . . . . . . . . . 38Energy Recovery with Coil Runaround Loops . . . . . . . . . . . . . . . . . . . . . 40Energy Recovery with Air-to-Air Plate Frame Heat Exchangers . . . . . . . 41Acoustics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42Components and Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43Access/Blank/Turning Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43Blender . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43CDQ Desiccant Dehumidification Wheel . . . . . . . . . . . . . . . . . . . . . . . . . . 44Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45Coil Optimization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Drain Pans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Integral Face-and-Bypass Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45464646Dampers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47Face-and-Bypass Dampers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47Traq Dampers and Low Flow Traq Dampers . . . . . . . . . . . . . . . . . . . . . . 50Diffuser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50Discharge Plenum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51Economizer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51Energy Recovery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51Energy Wheels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52CLCH-PRC022B-EN5

Coil Runaround Loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52Air-to-Air Plate Frame Heat Exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . 53Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53Fan Choices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53Constant Volume vs. VAV Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54Airflow Measuring Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55Filtration and Air Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55Filtration Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55Air Cleaning Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56Gas Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57Humidifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57Inlet Hood . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58Mixing Box and Economizer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58Multizone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59Silencers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59General Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60Unit Size 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60Unit Size 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64Unit Size 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68Unit Size 8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73Unit Size 10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78Unit Size 12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83Unit Size 14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88Unit Size 17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93Unit Size 21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98Unit Size 22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103Unit Size 25 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106Unit Size 26 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111Unit Size 30 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115Unit Size 31 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120Unit Size 35 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123Unit Size 36 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128Unit Size 40 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131Unit Size 41 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136Unit Size 50 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139Unit Size 51 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144Unit Size 57 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147Unit Size 66 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1526CLCH-PRC022B-EN

Unit Size 80 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157Unit Size 100 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161Unit Size 120 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169Drain Pans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169Coil Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169Hydronic and Steam Coil Connections . . . . . . . . . . . . . . . . . . . . . . . . . . 169Refrigerant Coil Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170Coil Circuiting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174Distributor Arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174Distributor Circuiting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174Face-Velocity Limits for Moisture Carryover . . . . . . . . . . . . . . . . . . . . . . . 179Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184Air-to-Air Plate Heat Exchangers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184Blenders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185Dampers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 186Energy Wheel Dampers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Mixing Box Dampers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .AMCA 610 Test Performance for Traq Damper . . . . . . . . . . . . . . . . . . .Multizone Dampers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .186188192192Diffuser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193Discharge Plenums . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193Horizontal or Vertical Discharge Plenum with Factory Openings . . . . . 193Economizer for Outdoor Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198Gas Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201Hoods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201Humidifiers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203Multizone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204Silencers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204Trane Catalytic Air Cleaning Systems (TCACS) . . . . . . . . . . . . . . . . . . . . . 205Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206Mechanical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 207Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 207Seismic Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 207Unit Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208Casing Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208Unit Flooring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208CLCH-PRC022B-EN7

Casing Leakage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208Drain Pans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208Access Doors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209View Windows . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209Marine Lights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209FC Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .BC Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .AF Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Belt-Drive Plenum Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Direct-Drive Plenum Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Vertical Motorized Impeller Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .210210210210210210Fan Isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2111-Inch, Seismic Spring Isolators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2112-Inch, Seismic Spring Isolators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211Fan Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211Fan Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211Motor Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211Grease Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211Fan Section Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212Multiple Belt Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .External Motor Junction Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Motor Wiring Conduit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Flow Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Belt Guard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Door Guard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .212212212212212212Fan Modulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212Variable-Frequency Drives (VFDs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212Inverter Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212Horizontal and Vertical Coil Sections . . . . . . . . . . . . . . . . . . . . . . . . . . . .Inspection Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Water Coils (UW, UU, UA, W, 5W, 5A, WD, 5D, D1, D2, P, or TT) . . . .Refrigerant Cooling Coils (UF, FD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Steam Heating Coil (NS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Coil Coating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Electric Heat Coil Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Integral Face-and-Bypass Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .213213213213214214214215Dampers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215Barometric Relief Dampers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215Energy Recovery Wheel Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 216Performance and Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2168CLCH-PRC022B-EN

Wheel Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Wheel Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Maintenance and Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Wheel Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Frost Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Wheel Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .216216216216216217Cool Dry Quiet (CDQ ) Desiccant Wheel . . . . . . . . . . . . . . . . . . . . . . . . . . 217Wheel Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217CDQ Wheel Drive System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217Maintenance and Access Doors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217Humidifiers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217Direct Steam . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217Atmospheric Steam . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217Filters and Air Cleaners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218Permanent Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Throwaway Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Pleated Media Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bag Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Cartridge Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-Inch High-Efficiency Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .HEPA Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Air Cleaning Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .218218218218218219219219Filter Section Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220Differential Pressure Gauge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220Mixing Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220Dampers . . . . . . . . . . . . .

Performance Climate Changer air handlers combine the Trane tradition of engineering excellence with the latest in manufacturing technology to give you an energy efficient air handler with superior performance, the highest qual

Related Documents:

Climate Changer air handler. Carefully review the procedures discussed in this ma nual to minimize installation and startup difficulties. Product Information Trane M-Series Climate Changer air handlers are central-station air handlers designed for a variety of controlled-air applications. The basic unit consists of a fan, heating and/or

The T-Series Climate Changer air handler is an outdoor air handler designed for a variety of controlled-air applications. The basic unit consists of a fan, heating and/or cooling coils, filters, and dampers. T-Series air handlers ship as complete assemb l

changer. To prevent accidents or damage to the tire changer, use only Hunter recommended procedures and accessories. Wear OSHA approved eye protection while operating the tire changer. Wear non-slip safety footwear when operating the tire changer. Do not wear jewelry or loose clothing when operating the tire changer.

area where the EPT sealer will attach. 4503030T 4 x 8 mm WASHER-SCREW CD CHANGER LEFT CHANGER BRACKET 4 x 8 mm WASHER-SCREW SIDE BRACKET RIGHT CHANGER BRACKET 32. Measure and cut the EPT sealer as shown. Attach the EPT sealer to the left changer bracket. 33. Bundle up the CD changer bus cable using one wire tie with clip in the area shown. 35.

Trane is responsible for introducing two new air-handling units to the market: the CLCF Climate Changer for comfort applications, and the CLCF Climate Changer for hospital, laboratory and pharmaceutical applications. Designed by Trane to address the performance needs of an entire bui

air handlers are compact and combine versatility with economical, dependable performance. The 39S Series air handlers offer: Horizontal and vertical draw-thru arrangements for heating, cooling, ventilation, and VAV (variable air volume) applications Small footprint, w

Heat in the gym, stage and kindergarten classroom is provided by (2) Trane Climate Changer air handlers with steam coils. One of the air handlers serves the gym only. The second air handler

It WAS a powerful good adventure, and Tom Sawyer had to work his bullet-wound mighty lively to hold his own against it. Well, by and by Tom's glory got to paling down gradu'ly, on account of other things turning up for the people to talk about--first a horse-race, and on top of that a house afire, and on top of that the circus, and on top of that the eclipse; and that started a revival, same .