HUBBELL SPIKESHIELD Wired-In Branch Panels Surge .

2y ago
12 Views
2 Downloads
1.22 MB
16 Pages
Last View : 1m ago
Last Download : 3m ago
Upload by : Dani Mulvey
Transcription

HUBBELL SPIKESHIELD Wired-In Branch PanelsSurge Protective Device (SPD)Instruction Bulletin8222-0513BRetain for future use.

SPIKESHIELD Wired-In Branch PanelsElectricalLocation of Surge ProtectiveDevice (SPD)8222-0513B05/2012Install SPDs on the load side of the main overcurrent protection to complywith NEC Article 285 for Type 2 SPD.Locate the SPD as close as possible to the circuit being surge-limited tominimize the wire length and optimize SPD performance. Avoid long wireruns so that the device will perform as intended. To reduce the impedancethat the wire displays to surge currents, the phase, neutral, and groundconductors (wye and high-leg delta configurations), or phase and groundconductors (delta configurations), must be routed within the same conduitand tightly bundled or twisted together to optimize device performance.Avoid sharp bends in the conductors. See Figures 2 and 3.Figure 2:SPD Wiring for Wye and High-Leg Delta ConfigurationsTo load(s)Phase APhase BPhasesPhase CNeutralNeutralNeutral busGroundGroundGround busSPDPanelFigure 3:10Interconnect wiring– Minimize length– Avoid sharp bendsSPD Wiring for Delta Configurations 2010–2012 Hubbell Wiring Devices All Rights Reserved

SPIKESHIELD Wired-In Branch PanelsSystem Grounding8222-0513B05/2012System GroundingCAUTIONLOSS OF SURGE SUPPRESSION Must be installed on solidly grounded power systems. Do not use onungrounded systems. Verify that the service entrance equipment is bonded to ground inaccordance with all applicable codes. Verify that the neutral terminals are grounded to system ground inaccordance with all applicable codes.Failure to follow these instructions can result in equipment damage.An equipment grounding conductor must be used on all electrical circuitsconnected to the SPD. For the best performance, use a single-point groundsystem where the service entrance grounding electrode system isconnected to and bonded to all other available electrodes, building steel,metal water pipes, driven rods, etc. (for reference, see IEEE 142-2007). Theground impedance measurement of the electrical system should be as lowas possible, and in compliance with all applicable codes, for sensitiveelectronics and computer systems.When a metallic raceway is used as an additional grounding conductor, aninsulated grounding conductor should be run inside the raceway and sizedin accordance with all applicable codes.WARNINGINADEQUATE RACEWAY ELECTRICAL CONTINUITY Ground impedance must be as low as possible and in compliance withall applicable codes for sensitive electronic and computer systems. Install an insulated grounding conductor inside a metallic raceway whenthe raceway is used as an additional grounding conductor. Size theconductor in accordance with all applicable codes. Maintain adequate electrical continuity at all raceway connections. Do not use isolating bushings to interrupt a metallic raceway run. Do not use a separate isolated ground for the SPD. Verify proper equipment connections to the grounding system. Verify ground grid continuity by inspections and testing as part of acomprehensive electrical maintenance program.Failure to follow these instructions can result in death or serious injury. 2010–2012 Hubbell Wiring Devices All Rights Reserved11

SPIKESHIELD Wired-In Branch GERHAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Apply appropriate personal protective equipment (PPE) and follow safeelectrical work practices. See NFPA 70E. This equipment must only be installed and serviced by qualifiedelectrical personnel. Turn off all power supplying this equipment before working on or insideequipment. Always use a properly rated voltage sensing device to confirm power is off. Replace all devices, doors and covers before turning on power to thisequipment. This equipment must be effectively grounded per all applicable codes.Use an equipment-grounding conductor to connect this equipment tothe power system ground.Failure to follow these instructions will result in death or serious injury.Mounting Recommendations12The SPD should be nipple mounted directly to the equipment being surgelimited. The measured torque for tightening the lock nut is not to exceed 100lb-in. Always use the mounting brackets (provided) as primary support. 2010–2012 Hubbell Wiring Devices All Rights Reserved

SPIKESHIELD Wired-In Branch PanelsWiring8222-0513B05/2012WiringDANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Apply appropriate personal protective equipment (PPE) and follow safeelectrical work practices. See NFPA 70E. This equipment must only be installed and serviced by qualifiedelectrical personnel. Turn off all power supplying this equipment before working on or insideequipment. Always use a properly rated voltage sensing device to confirm power is off. Replace all devices, doors and covers before turning on power to thisequipment. This equipment must be effectively grounded per all applicable codes.Use an equipment-grounding conductor to connect this equipment tothe power system ground.Failure to follow these instructions will result in death or serious injury.DANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASHConfirm the SPD voltage rating on the module or nameplate label is thesame as the operating voltage.Failure to follow these instructions will result in death or serious injury.Table 4:Wiring Diagram Location1Wiring for:Figure and PageSingle-phase, 3-wire, groundedinstallationFigure 5 on page 14Three-phase, 3- or 4-wire,grounded WYE installationFigure 6 on page 14Three-phase, 3- or 4-wire, highleg delta installationFigure 7 on page 14Three-phase, 3-wire ground,delta installationFigure 8 on page 141See “Dry Contacts” on page 14 for dry contact wiring.Follow steps 1 through 7 to make wiring connections.1. Turn off all power supplying this equipment before working on or insideany enclosure containing this equipment.2. Confirm SPD is rated for your system by comparing voltagemeasurements to the Line Voltage (L-L, L-N) on the product label.3. Identify proper location for the SPD. Locate as close as possible to thepanel being surge-limited so the wires are as short as possible. Mountunit securely. See Figure 4 for mounting instructions.NOTE: The SPD must be installed in an accessible location (not withinwalls).4. Install in accordance with national and local electrical codes and match thebranch circuit Overcurrent Protection Device (OCPD) to the wire size.5. Twist conductors 1/2 turn or more for every twelve inches of length.6. Do not loop or coil wires. Be sure to maintain adequate wire bendingspace per NEC 2008 Article 408.7. Use on grounded systems only.NOTE: On a high-leg delta installation, the high-leg of the power systemmust be connected to the orange wire of the SPD.NOTE: Always install the SPD on the LOAD side of the main disconnect. 2010–2012 Hubbell Wiring Devices All Rights Reserved13

SPIKESHIELD Wired-In Branch PanelsWiring8222-0513B05/2012Wiring DiagramsFigure 4:Mounting UnitFigure 5:Single-Phase, 3-Wire, Grounded InstallationNOTE: The neutral conductor is not present on3-wire grounded neutral power systems. Forproper operation of the SPD diagnostics, theneutral (white) conductor of the SPD must beconnected to ground.Figure 6:Three-Phase, 3- or 4-Wire, Grounded Wye InstallationNOTE: The high-leg of the power system mustconnect to the orange wire of the SPD. Forproper operation of the SPD diagnostics on3-wire grounded neutral power systems, theneutral (white) conductor of the SPD must beconnected to ground.Figure 7:Three-Phase, 3- or 4-Wire, High-Leg Delta InstallationFigure 8:Three-Phase, 3 Wire, Delta InstallationLock Nut0.75 in. [19 mm] knockout (trade size)Actual hole size 1.0 in. [25 mm]G14 2010–2012 Hubbell Wiring Devices All Rights Reserved

SPIKESHIELD Wired-In Branch ARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Apply appropriate personal protective equipment (PPE) and follow safeelectrical work practices. See NFPA 70E. This equipment must only be installed and serviced by qualifiedelectrical personnel. Turn off all power supplying this equipment before working on or insideequipment. Always use a properly rated voltage sensing device to confirm power is off. Replace all devices, doors and covers before turning on power to thisequipment. This equipment must be effectively grounded per all applicable codes.Use an equipment-grounding conductor to connect this equipment tothe power system ground.Failure to follow these instructions will result in death or serious injury.LED Status IndicatorsDiagnostic LEDs are located on the front of the SPD. They operate asfollows: Verify that all phase voltages are present. If any of the LEDs are notilluminated, the device may not be installed correctly. Check the powersupply and service voltage. Upon energizing the SPD, check the LEDstatus. If all of the LEDs are illuminated, surge suppression is operating. If an inoperative condition occurs the device must be replaced byqualified electrical personnel.If one or more LEDs are not illuminated, there is a loss of surgesuppression on that phase.Figure 9:Diagnostic OperationLED ON OK8222-0012-07LED OFF Loss of surge suppression on that phaseand Audible AlarmON Loss of surge suppressionAudible Alarm 2010–2012 Hubbell Wiring Devices All Rights ReservedThe audible alarm does not have a silence switch. Silence the alarm byremoving power from the SPD (open the circuit breaker that it is connectedto). The alarm indicates that the device needs replacement by qualifiedelectrical personnel.15

SPIKESHIELD Wired-In Branch PanelsOperationDry Contacts8222-0513B05/2012The SPD is provided with dry contacts. The connection for the dry contactsis provided by 24-inch (61 cm) wire leads. The wire leads are 22 AWGstranded copper wire. See Table 5 for wire color and contact state. Theunpowered state shall be closed between the red wire (common) and theyellow wire (normally closed). This is also the alarm condition. The oppositestate, closed between the red wire (common) and the blue wire (normallyopen), indicates that power is on to the unit and that no alarm conditionexists (See Table 5). These dry contact leads can be used for remoteindication of the SPD operating status to a computer interface board oremergency management system. Also, these dry contact leads aredesigned to work with the SPD remote monitor option described in thefollowing section.The dry contacts are designed for a maximum voltage of 24 Vdc / 24 Vacand a maximum current of 2 A. Higher energy applications may requireadditional relay implementation outside the SPD. Damage to the SPD’srelay caused by use with energy levels in excess of those discussed in thisinstruction bulletin are not covered by warranty. For application questions,call the Surgelogic Technical Assistance Group at (800) 577-7353.Table 5:16Dry Contact ConfigurationDry ContactTerminalWire ColorPower off or Alarm Power on and noConditionAlarm ConditionN/O(Normally ally ClosedYellowClosedOpen 2010–2012 Hubbell Wiring Devices All Rights Reserved

SPIKESHIELD Wired-In Branch PanelsOperation8222-0513B05/2012Remote Monitor OptionThe remote monitor option has two LEDs, one red and one green, and anaudible alarm with an enable/disable switch. Normal status is a lit greenLED, and no audible alarm. To test the integrity of the remote monitor, pressthe push-to-test switch. The green LED will turn off, the red LED will turn on,and the alarm will sound, if the alarm is enabled. Releasing the switch willcomplete the test; the red LED will turn off, the green LED will turn on andthe alarm will shut off.If suppression on any phase is lost, the green LED will turn off, the red LEDwill illuminate and an alarm will sound. The audible alarm can be silenced bypushing the alarm enable/disable/test switch. The alarm will silence and thegreen alarm LED will not be lit. The red LED will continue to be illuminateduntil the inoperative condition has been cleared.The remote monitor includes a 120 Vac to 12 Vdc adapter with a six-footpower cord. Connections are made to the SPD diagnostic panel with the 24inch (61 cm) dry contact leads (provided). To extend the remote monitorfurther (up to 1,000 ft. [305 m]), use an additional length of solid or stranded22 to 14 AWG wire (not provided).Figure 10:Remote Monitor Option 0[88.9]0.460[5.86]1.25 2.500[31.8] [63.5]2x Ø 0.187[4.75] OK Fault / Falla / DéfautMonitor Remoto / Moniteur À DistanceBouton pousser pour vérifier0.130[3.3]Dry Contacts120 V power cord1.125[28.58] 2010–2012 Hubbell Wiring Devices All Rights Reserved17

SPIKESHIELD Wired-In Branch PanelsInstruction Bulletin8222-0513B05/2012Preventive MaintenanceDANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Apply appropriate personal protective equipment (PPE) and follow safeelectrical work practices. See NFPA 70E. This equipment must only be installed and serviced by qualifiedelectrical personnel. Turn off all power supplying this equipment before working on or insideequipment. Always use a properly rated voltage sensing device to confirm power is off. Replace all devices, doors and covers before turning on power to thisequipment. This equipment must be effectively grounded per all applicable codes.Use an equipment-grounding conductor to connect this equipment tothe power system ground.Failure to follow these instructions will result in death or serious injury.Inspect the SPD periodically to maintain reliable system performance andcontinued transient voltage surge suppression. During this inspection,check the state of the display LED status indicators.Electrical equipment should be installed, operated, serviced, and maintained only by qualifiedpersonnel. No responsibility is assumed by Hubbell Inc. for any consequences arising out of theuse of this material.Hubbell Wiring 13B 05/2012Replaces 8222-0513A 06/2010 2010–2012 Hubbell Inc. All Rights Reserved

Location of Surge Protective Device (SPD) Install SPDs on the load side of the main overcurrent protection to comply with NEC Article 285 for Type 2 SPD. Locate the SPD as close as possible to the circuit being surge-limited to minimize the wire length and optimize SPD performance. Avoid long wire runs so t

Related Documents:

1606 Auto Bhan Branch Hyderabad 1608 Citizen Colony Branch Hyderabad 1604 Gari Khata Branch Hyderabad 1601 Hyderabad Branch Hyderabad 1602 Latifabad Branch Hyderabad 1681 Market Road Branch Hyderabad 1605 New Cloth Market Branch Hyderabad 1603 Qasimabad Branch Hyderabad 0321 74-E Blue Area Branch Islamabad 0305 Aabpara Branch Islamabad

LIGHTING, EMERGENCY Atlite/Cooper Lighting Solutions Chloride/Philips ConTech Lighting/Leviton Dual-Lite/Hubbell Eaton Crouse-Hinds series Emergi-Lite/Thomas & Betts . Phoenix Lighting Prescolite/Hubbell Progress Lighting/Hubbell RAB Lighting Stonco/Philips LIGHTING, LED Alera

Pathway Lighting Prescolite/Hubbell Siltron Sure-Lites/Eaton Lighting solutions LIGHTING, FLOURESCENT Alera Lighting/Hubbell Apogee Translite Bartco Lighting Columbia Lighting/Hubbell Coronet Lighting Day-Brite/Philips Finelite Focal Point Lighting H.E. Williams Holophane/Acuity

the shore power connection". Note: A faulty electrical connection at the dock or on a boat could result in stray electrical current in the water. Such stray current in Electrical Shock Drowning (ESD). Hubbell’s family of ELCI adaptive Shore Power Inlet Kits provide a simple, flexible, low-cost solution. Kits Contain: Hubbell Shore Power Inlet

Please note the Ohio Brass Company is a subsidiary of Hubbell Power Systems, Inc. Hubbell Power Systems is a manufacturer of a wide variety of products for transmission and distribution needs of the electric utility industry. Ohio Brass manufactures insulators and arreste

8 9 Hilton Greenville 45 West Orchard Park Drive Greenville, South Carolina 29615 Direct Line: Hubbell Account Manager 864.298.6849 Hubbell Corporate Code: 0000391 *Be sure to identify yourself as a guest of Hubbell

situation, a patent owner cannot overcome ODP by filing a TD because common ownership and/or joint research agreement between assignees are prerequisites for filing a TD. In the Hubbell case, Hubbell's patent application was rejected for ODP over a patent that had a common inventor and Hubbell could not file a TD to overcome the ODP rejection.[12]

American Revolution Lapbook Cut out as one piece. You will first fold in the When Where side flap and then fold like an accordion. You will attach the back of the Turnaround square to the lapbook and the Valley Forge square will be the cover. Write in when the troops were at Valley Forge and where Valley Forge is located. Write in what hardships the Continental army faced and how things got .