GRUNDFOS DATA BOOKLET UPZC Single- and multiple-zone controls for zone pumps and zone valves 60 Hz

UPZC Table of contents 1. General description 3 2. Special features 3 Additional features, UPZCP-3, -4, -6 Additional features, UPZCV-3, -4, -6 3 4 Applications 4 3. 4. 5. 6. 7. Identification 4 Nameplate Production code 4 4 Product range 4 Operation 5 LED diagnostics DIP-switch settings 5 6 Installation 7 Mechanical installation Electrical installation Wiring guidelines Wiring diagrams, pump controllers Wiring diagrams, zone valve controllers 7 7 7 9 18 8. Technical data 30 9. Approvals 31 10. Service Service parts 11. Further product documentation 2 31 31 32

1 1. General description 2. Special features The Grundfos UPZC series of zone controls is the ideal choice for single- and multiple-zone hydronic heating systems using either zone pumps or low-voltage zone valves. Grundfos UPZC zone controls offer these features: Compatibility with 2-, 3-, and 4-wire, low-voltage controllers or thermostats. Wiring ease with 120 VAC, ground and low-voltage screw terminal inputs. Front-facing LEDs on the front. Side-mounted terminal connections for ease of wiring and installation. General description UPZC TM06 6569 1816 Additional features, UPZCP-3, -4, -6 Fig. 1 UPZC zone controls All Grundfos UPZC multiple-zone controls are expandable to handle any size of job. UPZC zone controls can control boiler pumps, domestic hot-water pumps, and system pumps and assign priority. The side-mounted terminals provide easy access and ease in wiring. The front-facing, easy-to-read LEDs on the front panel provide essential operating status. Grundfos UPZCP-3, -4, -6 zone controls offer these additional features: Pump exercise, selectable for 72 hours or 14 days – The pumps are turned on for 30 seconds every 72 hours or 14 days in order to prevent the pumps from seizing up. This feature only works if there is a jumper connecting the ZR-ZC terminals on the pump controller. Post-purge for pump controllers. After the priority zone calls for heat, the priority pump will be allowed to run for an additional two minutes after the thermostat contacts open. This allows some of the residual heat in the boiler to be transferred to the water. Boiler demand terminals – The two terminals, labeled "XX MAIN", are wired to the boiler. When the contacts close, the boiler starts and reaches a preset temperature for hydronic heating. DHW terminal – The two terminals, labeled "XX PRIORITY", are wired to the boiler. When the contacts close, the boiler starts and reaches a preset temperature for domestic hot-water heating. ZR-ZC terminals – The terminals are available on the pump controllers only. These terminals are connected by a jumper at the factory. The ZR terminal is always powered with 120 VAC. When you remove the jumper, all 120 V power is removed from the pumps. 3

3 UPZC Applications Additional features, UPZCV-3, -4, -6 Grundfos UPZCV-3, -4, -6 zone controls offer these additional features: Low-voltage, end-switch output terminals for the zone valves Replaceable, snap-fit 40 VA transformer for the zone valve controllers only Zone priority with selectable time-out feature Pump exercise, selectable for 72 hours or 14 days – The pumps are turned on for 30 seconds every 72 hours or 14 days in order to prevent the pumps from seizing up. Boiler demand terminals – The two terminals, labeled "XX MAIN", are wired to the boiler. When the contacts close, the boiler starts and reaches a preset temperature for hydronic heating. DHW terminal – The two terminals, labeled "XX PRIORITY", are wired to the boiler. When the contacts close, the boiler starts and reaches a preset temperature for domestic hot-water heating. 3. Applications Grundfos UPZC zone controls are for single- and multiple-zone, domestic, hydronic heating systems: UPZCP-1 For single-zone pump control. UPZCP-3, -4, -6 For multiple-zone pump control. UPZCV-3, -4, -6 For multiple-zone valve control. 4 4. Identification Nameplate The nameplate on the front of the product shows the model, part number, and required electrical input. The power indicator light and LEDs are located on the nameplate. See figures 2, 3, and 4. Production code The production code represents the date of manufacture. You can find the production code on the circuit board and the carton label. Example: PC 1542 year 2015, week 42. Production code YYWW PC1542 Circuit board 1542 Carton label Fig. 1 Locating the production code 5. Product range Model Description UPZCP-1 Single-pump zone control UPZCP-3 UPZCP-4 UPZCP-6 Three-pump zone control Four-pump zone control Six-pump zone control UPZCV-3 UPZCV-4 UPZCV-6 Three-valve zone control Four-valve zone control Six-valve zone control

6 UPZC Operation 6. Operation LED diagnostics The power indicator light "Grundfos" is lit when you power on the unit. The red LED is lit when there is a call for heat. ZONE 1 UPZCP-1 1 Pump Zone Relay Part Number: XXXXXXXX Input: 120VAC 50/60Hz 10A MAX Certified to CSA C22.2 No 24 Conforms to UL Standard 873 DISCONNECT POWER PRIOR TO SERVICING ATTENTION, RISQUE DE CHOC ÉLÉCTRIQUE DÉCONNECTEZ LA PUISSANCE AVANT D’ENTRETENIR Fig. 2 TM06 5554 5015 CAUTION, RISK OF ELECTRICAL SHOCK - Listed UPZCP single-zone pump-relay LED The power indicator light "Grundfos" is lit when you power on the unit. ZONE 1 ZONE 2 ZONE 3 UPZCP-6 6 Pump Zone Relay Part Number: XXXXXXXX Input: 120VAC 50/60Hz 20A MAX Listed Certified to CSA C22.2 No 24 Conforms to UL Standard 873 ZONE 5 CAUTION, RISK OF ELECTRICAL SHOCK - ZONE 6 DISCONNECT POWER PRIOR TO SERVICING ATTENTION, RISQUE DE CHOC ÉLÉCTRIQUE DÉCONNECTEZ LA PUISSANCE AVANT D’ENTRETENIR The red LED is lit when there is a call for heat. Fig. 3 TM06 5584 4915 ZONE 4 UPZCP multiple-zone pump-relay LEDs The power indicator light "Grundfos" is lit when you power on the unit. ZONE 1 ZONE 2 ZONE 3 UPZCV-6 6 Valve Zone Relay Part Number: XXXXXXXX Input: 120VAC 50/60Hz 20A MAX Listed Certified to CSA C22.2 No 24 Conforms to UL Standard 873 ZONE 5 CAUTION, RISK OF ELECTRICAL SHOCK - ZONE 6 DISCONNECT POWER PRIOR TO SERVICING ATTENTION, RISQUE DE CHOC ÉLÉCTRIQUE DÉCONNECTEZ LA PUISSANCE AVANT D’ENTRETENIR The LEDs are green when there is a call for heat. The LEDs turn amber when the zone-valve end switch is closed. Fig. 4 TM06 5587 5015 ZONE 4 UPZCV multiple-zone valve-relay LEDs 5

6 UPZC Operation DIP-switch settings UPZCP-3, -4, -6 Master/Slave Allows expansion to additional Grundfos UPZC units. Post Purge ON The boiler pump continues to run for two minutes after priority ends to remove residual heat from the boiler. Pump Exercise ON The pumps operate for 30 seconds every 72 hours or every 14 days. Primary ON During the priority demand, select whether the primary pump is ON or OFF. Slave Master Priority ON Priority 30 min. OFF 60 minutes Post Purge ON OFF Pump Exercise ON Exercise 30 sec./72 hrs. Primary ON OFF 30 sec./14 days OFF TM06 5585 0516 Priority ON Zone 1 operates as priority and the other zones are switched off for a selectable 30- or 60-minute time-out. UPZCV-3, -4, -6 Priority ON Zone 1 operates as priority and the other zones are switched off for a selectable 30- or 60-minute time-out. Pump Exercise ON The pumps operate for 30 seconds every 72 hours or every 14 days. Slave Priority ON Priority 30 min. Pump Exercise ON Exercise 30 sec./72 hrs. Boiler Pump ON Secondary Pump ON Boiler Pump ON/Secondary Pump ON You can control the boiler pump and secondary pump to ON or OFF during priority demand. 6 Master OFF 60 minutes OFF 30 sec./14 days OFF OFF During priority demand TM06 5589 5115 Master/Slave Allows expansion to additional Grundfos UPZC units.

7 UPZC Mechanical installation Wiring guidelines Installing the base plate Also see sections Wiring diagrams, pump controllers on page 9 and Wiring diagrams, zone valve controllers on page 18. The base plate must be firmly attached to the wall surface with four screws and anchors using the key holes provided. Wiring for thermostats Aquastat TM06 5597 5015 2-wire thermostat 3-wire thermostat Base plate UPZCP-3, -4, -6 and UPZCV-3, -4, -6 C W R 4-wire thermostat C TM06 5607 5015 W R C R C W R Fig. 5 Jumper Attach the base plate to the wall with screws and anchors Electrical installation All electrical connections must be made using copper wire only. We recommend that you use these AWG wire sizes: 12-16 AWG wire for 120 VAC connections. 12-22 AWG wire for thermostat connections. 12-22 AWG wire for 24 VAC connections. Use approved UL conduit fittings. Additional wiring schematics, specs, and troubleshooting help is available online at www.grundfos.us/controls. C W R Fig. 6 TM06 5338 5115 W R Rh W C Example of thermostat wiring Wiring for valves, UPZCV-3, -4, -6 Jumper 4 3 2 1 Jumper 4 3 2-wire zone valve 2 1 4 3 2 1 3 1 2 TACO 570 3-wire zone valve 4 3 2 1 4 3 2 4-wire zone valve 1 4 3 1 and 2: Motor terminals 3 and 4: End-switch terminals 2 1 Fig. 7 TM06 5338 5115 Base plate UPZCP-1 Installation 7. Installation Example of wiring for zone valves 7

7 UPZC Installation Wiring for pumps, UPZCP-3, -4, -6 Wiring for two or more controllers N L N L N L N L N L L TM06 5605 5015 Ground screws on base plate N N L Fig. 8 Example of wiring for pumps Wiring for two or more boards, expansion Master board Slave C B A Master E X P A N S I O N C B A Master E X P A N S I O N Slave board Fig. 9 8 Example of wiring for expansion controllers TM06 5606 5015 Slave See fig. 9 for example. When connecting two or more controllers: You can only use the master controller with priority. When priority calls, the master board will produce 5 VDC between terminals B and C. This tells the slave board to turn off any zones that are calling for heat. This will also close the contacts "XX PRIORITY". When there is a demand for heat, the slave board will produce 5 VDC between terminals A and C. This tells the master board to activate any boiler or secondary pumps and close the contacts "XX MAIN". You can connect the pump and valve boards. When the slave board calls for heat, the secondary pump will be powered. If a boiler pump and secondary pump are to be used, they must be connected to the same terminals. You can use the low voltage wire to connect ABC terminals. The 120 VAC power supply must be connected to each board. The L and N terminals must be connected the same way on each board. If switched, a differential of 240 VAC can occur resulting in damage to the equipment.

7 UPZC Installation Wiring diagrams, pump controllers UPZCP-1 single-zone pump control Setup with one thermostat N/C N/O C Optional for 3-wire thermostat C C O M W T R T N/C Boiler N/O C 24 VAC 40 VA transformer L N I N P U T 1 2 0 V A C TM06 5593 5015 Factory jumper Fig. 10 UPZCP-1 single-zone with one thermostat 9

7 UPZC Installation UPZCP-1 single-zone pump control Setup with multiple zones End-switch wires 4-wire zone valves N/C N/O RW RW C C C O M W T R T 24 VAC N/C Boiler N/O C 24 VAC 40 VA transformer L N Fig. 11 UPZCP-1 with multiple zones 10 I N P U T 1 2 0 V A C TM06 5592 5015 Factory jumper

7 UPZC Installation UPZCP-3, -4, -6 multiple-zone pump control Setup with modcon boiler, primary and secondary loops 2-wire thermostat 2-wire thermostat 2-wire thermostat C N W R L C W 2-wire thermostat 5 A fuses R C N DIP switches L W SW1 R Slave Master N C 2-wire thermostat W R C Priority ON Priority 30 min. OFF 60 minutes Post Purge ON OFF W Pump Exercise ON Exercise 30 sec./72 hrs. R Primary ON L OFF 30 sec./14 days N OFF L C W N R C L B A N X X L X N X Ground screws on base plate L ZR N ZC L Jumper Mod-con boiler N L 250 mA fuse L N TM06 6637 1916 24 VAC 40 VA transformer Fig. 12 Wiring diagram, P1 11

7 UPZC Installation UPZCP-3, -4, -6 multiple-zone pump control Setup with conventional boiler, two-pipe direct return, and indirect DHW Aquastat for DHW 2-wire thermostat 2-wire thermostat 2-wire thermostat C N W R L C W 2-wire thermostat 5 A fuses R C N DIP switches L W SW1 R Slave Master N C 2-wire thermostat W R C Priority ON Priority 30 min. OFF 60 minutes Post Purge ON OFF W Pump Exercise ON Exercise 30 sec./72 hrs. R Primary ON L OFF 30 sec./14 days N OFF L C W N R C L B A N X X L X N X Ground screws on base plate L ZR N ZC L Jumper Conventional boiler N L 250 mA fuse L Fig. 13 Wiring diagram, P2 12 N TM06 6638 1916 24 VAC 40 VA transformer

7 UPZC Installation UPZCP-3, -4, -6 multiple-zone pump control Setup with mod-con boiler, primary loop 2-wire thermostat 2-wire thermostat 2-wire thermostat Boiler loop pump C N W Primary loop pump R L C W 5 A fuses R C N DIP switches L W SW1 R Slave Master N C W R C Priority ON Priority 30 min. OFF 60 minutes Post Purge ON OFF W Pump Exercise ON Exercise 30 sec./72 hrs. R Primary ON L OFF 30 sec./14 days N OFF L C W N R C L B A N X X L X N X Ground screws on base plate L ZR N ZC L Jumper Mod-con boiler N L 250 mA fuse L N TM06 6639 1916 24 VAC 40 VA transformer Fig. 14 Wiring diagram, P3 13

7 UPZC Installation UPZCP-3, -4, -6 multiple-zone pump control Setup with modified wiring: Boiler activates zone pumps using ZR/ZC control; primary and DHW pumps connect directly to boiler. 2-wire thermostat 2-wire thermostat C N W R L C W 5 A fuses N R C DIP switches L W SW1 R Slave Master N C W R C Priority ON Priority 30 min. OFF 60 minutes Post Purge ON OFF W Pump Exercise ON Exercise 30 sec./72 hrs. R Primary ON L OFF 30 sec./14 days N OFF L C W N R C L B A N X X L X N X Ground screws on base plate L Connect to the "Heating T-stat" terminals on the boiler 24 VAC 40 VA transformer ZR N ZC L N Remove the factory jumper. Connect ZC to the "system circulator" or ZC terminal on the boiler. 250 mA fuse L Fig. 15 Wiring diagram, P4 14 N TM06 6640 1916 L

7 UPZC Installation This page intentionally left blank. 15

7 UPZC Installation UPZCP-3, -4, -6 multiple-zone pump control Setup with mod-con boiler, two-pipe direct return, indirect DHW, two controllers connected, master controller 2-wire thermostat 2-wire thermostat Connect to the corresponding A, B, C terminals on the slave controller. See fig. 17. 2-wire thermostat 2-wire thermostat C N W R L C W 2-wire thermostat 5 A fuses R C N DIP switches L W SW1 R 2-wire thermostat Slave Master N C W R C Priority ON Priority 30 min. OFF 60 minutes Post Purge ON OFF W Pump Exercise ON Exercise 30 sec./72 hrs. R Primary ON L OFF 30 sec./14 days N OFF L C W N R C L B A N X X L X N X L ZR N ZC L Jumper Conventional boiler N L 250 mA fuse L Fig. 16 Wiring diagram, P5, master. See fig. 17 for corresponding diagram for slave controller. 16 N TM06 6641 1916 24 VAC 40 VA transformer Ground screws on base plate

7 UPZC Installation UPZCP-3, 4, 6 multiple-zone pump control Setup with mod-con boiler, two-pipe direct return, indirect DHW, two controllers connected, slave controller Connect to the corresponding A, B, C terminals on master controller. See fig. 16. 2-wire thermostat C N W R L C W 5 A fuses N R C DIP switches L W SW1 R Slave Master N C W R C Priority ON Priority 30 min. OFF 60 minutes Post Purge ON OFF W Pump Exercise ON Exercise 30 sec./72 hrs. R Primary ON L OFF 30 sec./14 days N OFF L C W N R C L B A N X X L X Ground screws on base plate N X L ZR N ZC L Jumper 24 VAC 40 VA transformer N 250 mA fuse L N TM06 6642 1916 L Fig. 17 Wiring diagram, P5, slave controller. See fig. 16 for corresponding diagram for master controller. 17

7 UPZC Installation Wiring diagrams, zone valve controllers UPZCV-3, -4, -6 multiple-zone valve control Setup with mod-con boiler, primary and secondary loops 2-wire thermostat 2-wire thermostat 2-wire thermostat 2-wire thermostat 2-wire thermostat C 4 W 3 R 2 C 1 W 4 R 3 C Dip switches W Slave Master C W OFF 60 minutes 4-wire zone valve 2 1 Pump Exercise ON Exercise 30 sec./72 hrs. OFF 30 sec./14 days W R 4 3 Priority ON Priority 30 min. R C 4-wire zone valve 2 1 SW1 R 2-wire thermostat 4-wire zone valve 4 3 Boiler Pump ON Secondary Pump ON C OFF OFF During priority demand 4-wire zone valve 2 1 W 4 R 3 C 2 B 1 A 4 X 3 4-wire zone valve 4-wire zone valve 2 X 1 X N X L N L N L 500 mA fuse 500 mA fuse N Mod-con boiler 24 VAC 40 VA transformer Fig. 18 Wiring diagram, V1 18 24 VAC 40 VA transformer L N TM06 6624 1916 Ground screws on frame L

7 UPZC Installation UPZCV-3, -4, -6 multiple-zone valve control Setup with mod-con boiler, primary and secondary loops, priority, indirect DHW Aquastat 2-wire thermostat 2-wire thermostat 2-wire thermostat 2-wire thermostat C 4 W 3 R 2 C 1 W 4 R 3 C Dip switches W Slave Master C W OFF 60 minutes 4-wire zone valve 2 1 Pump Exercise ON Exercise 30 sec./72 hrs. OFF 30 sec./14 days W R 4 3 Priority ON Priority 30 min. R C 4-wire zone valve 2 1 SW1 R 2-wire thermostat Jumper 4 3 Boiler Pump ON Secondary Pump ON C OFF OFF During priority demand 4-wire zone valve 2 1 W 4 R 3 C 2 B 1 A 4 X 3 4-wire zone valve 4-wire zone valve 2 X 1 X N X DHW priority pump L N L N L 500 mA fuse 500 mA fuse N Mod-con boiler Mod/con boiler 24 VAC 40 VA transformer 24 VAC 40 VA transformer L N TM06 6625 1916 Ground screws on frame L Fig. 19 Wiring diagram, V2 19

7 UPZC Installation UPZCV-3, -4, -6 multiple-zone valve control Setup with mod-con boiler, primary and secondary loops, indirect DHW on secondary loop Aquastat 2-wire thermostat 2-wire thermostat 2-wire thermostat 2-wire thermostat C 4 W 3 R 2 C 1 W 4 R 3 C Dip switches W Slave Master C W OFF 60 minutes 4-wire zone valve 2 1 Pump Exercise ON Exercise 30 sec./72 hrs. OFF 30 sec./14 days W R 4 3 Priority ON Priority 30 min. R C 4-wire zone valve 2 1 SW1 R 2-wire thermostat Jumper 4 3 Boiler Pump ON Secondary Pump ON C OFF OFF During priority demand 4-wire zone valve 2 1 W 4 R 3 C 2 B 1 A 4 X 3 4-wire zone valve 4-wire zone valve 2 X 1 X N X DHW priority pump L N L N L 500 mA fuse 500 mA fuse N Mod-con boiler 24 VAC 40 VA transformer Fig. 20 Wiring diagram, V3 20 24 VAC 40 VA transformer L N TM06 6626 1916 Ground screws on frame L

7 UPZC Installation This page intentionally left blank. 21

7 UPZC Installation UPZCV-3, -4, -6 multiple-zone valve control Setup with mod-con boiler, primary and secondary loops, indirect DHW on primary loop, two controllers connected, master controller Aquastat 2-wire thermostat Connect to the corresponding A, B, C terminals on the slave controller. See fig. 22. 2-wire thermostat 2-wire thermostat 2-wire thermostat C 4 W 3 R 2 C 1 W 4 R 3 C Dip switches W Slave 4-wire zone valve 2 1 SW1 R Master C 2-wire thermostat Jumper 4 3 Priority ON Priority 30 min. W OFF 60 minutes 4-wire zone valve 2 1 R Pump Exercise ON Exercise 30 sec./72 hrs. C OFF 30 sec./14 days W 4 3 Boiler Pump ON Secondary Pump ON R C OFF OFF During priority demand 4-wire zone valve 2 1 W 4 R 3 C 2 B 1 A 4 X 3 4-wire zone valve 4-wire zone valve 2 X 1 X N X DHW priority pump L N L N L 500 mA fuse 500 mA fuse N Mod-con boiler 24 VAC 40 VA transformer Fig. 21 Wiring diagram, V4, master controller. See fig. 22 for corresponding diagram for slave controller. 22 24 VAC 40 VA transformer L N TM06 6627 1916 Ground screws on frame L

7 UPZC Installation UPZCV-3, -4, -6 multiple-zone valve control Setup with mod-con boiler, primary and secondary loops, indirect DHW on primary loop, two controllers connected, slave controller Connect to the corresponding A, B, C terminals on the master controller. See fig. 21. 2-wire thermostat 2-wire thermostat C 4 W 3 R 2 C 1 W 4 R Jumper 3 C Dip switches W 1 SW1 R Slave 4-wire zone valve 2 Master C 4 3 OFF 60 minutes Priority ON Priority 30 min. W 4-wire zone valve 2 1 R OFF 30 sec./14 days Pump Exercise ON Exercise 30 sec./72 hrs. C W 4 3 Boiler Pump ON Secondary Pump ON R C OFF OFF During priority demand 2 1 W 4 R 3 C 2 B 1 A 4 X 3 2 X 1 X N X L N L N L 500 mA fuse 500 mA fuse N Mod-con boiler 24 VAC 40 VA transformer 24 VAC 40 VA transformer L N TM06 6628 1916 Ground screws on frame L Fig. 22 Wiring diagram, V4, slave controller. See fig. 21 for corresponding diagram for master controller. 23

7 UPZC Installation UPZCV-3, -4, -6 multiple-zone valve control Setup with conventional boiler, two-pipe direct return with indirect DHW* Aquastat 2-wire thermostat 2-wire thermostat Zone valve feeds indirect DHW tank. 2-wire thermostat 2-wire thermostat C 4 W 3 R 2 C 1 W 4 R 3 C Dip switches W Slave Master C W OFF 60 minutes 4-wire zone valve 2 1 Pump Exercise ON Exercise 30 sec./72 hrs. OFF 30 sec./14 days W R 4 3 Priority ON Priority 30 min. R C 4-wire zone valve 2 1 SW1 R 2-wire thermostat 4-wire zone valve 4 3 Boiler Pump ON Secondary Pump ON C OFF OFF During priority demand 2 1 W 4 R 3 C 2 B 1 A 4 X 3 2 X 1 X N X L N L N L 500 mA fuse 500 mA fuse N Conventional boiler 24 VAC 40 VA transformer 24 VAC 40 VA transformer L N Fig. 23 Wiring diagram, V5 * 24 This setup can also be used with priority. Set the priority DIP switch to ON, and connect the "XX PRIORITY" contacts to the boiler. TM06 6632 1916 Ground screws on frame L

7 UPZC Installation This page intentionally left blank. 25

7 UPZC Installation UPZCV-3, -4, -6 multiple-zone valve control Setup with mod-con boiler, primary and secondary loops, two secondary pumps, two controllers connected, master controller Aquastat 2-wire thermostat Connect to the corresponding A, B, C terminals on the slave controller. See fig. 25. 2-wire thermostat 2-wire thermostat 2-wire thermostat C 4 W 3 R 2 C 1 W 4 R 3 C Dip switches W Slave Master C W OFF 60 minutes 4-wire zone valve 2 1 Pump Exercise ON Exercise 30 sec./72 hrs. OFF 30 sec./14 days W R 4 3 Priority ON Priority 30 min. R C 4-wire zone valve 2 1 SW1 R 2-wire thermostat 4-wire zone valve 4 4-wire zone valve 3 Boiler Pump ON Secondary Pump ON C OFF OFF During priority demand 2 1 W 4 R 3 C 2 B 1 A 4 X 3 4-wire zone valve 4-wire zone valve 2 X 1 X N X L Secondary pump 1 N L N L 500 mA fuse 500 mA fuse N Mod-con boiler 24 VAC 40 VA transformer Fig. 24 Wiring diagram, V6, master controller. See fig. 25 for corresponding diagram for slave controller. 26 24 VAC 40 VA transformer L N TM06 6633 1916 Ground screws on frame L

7 UPZC Installation UPZCV-3, -4, -6 multiple-zone valve control Setup with mod-con boiler, primary and secondary loops, two secondary pumps, two controllers connected, slave controller Connect to the corresponding A, B, C terminals on the master controller. See fig. 24. 2-wire thermostat 2-wire thermostat C 4 W 3 R 2 C 1 W 4 R 3 C Dip switches W 1 SW1 R Slave Master C OFF 60 minutes 4-wire zone valve 2 1 R Pump Exercise ON Exercise 30 sec./72 hrs. OFF 30 sec./14 days W R 4 3 Priority ON Priority 30 min. W C 4-wire zone valve 2 4 3 Boiler Pump ON Secondary Pump ON C OFF OFF During priority demand 2 1 W 4 R 3 C 2 B 1 A 4 X 3 2 X 1 X N X L Secondary pump 2 N L N L 500 mA fuse 500 mA fuse N Mod-con boiler 24 VAC 40 VA transformer 24 VAC 40 VA transformer L N TM06 6634 1916 Ground screws on frame L Fig. 25 Wiring diagram, V6, slave controller. See fig. 24 for corresponding diagram for master controller. 27

7 UPZC Installation UPZCV-3, -4, -6 multiple-zone valve control Setup with conventional boiler, two-pipe direct return, indirect DHW Aquastat 2-wire thermostat 2-wire thermostat 2-wire thermostat 2-wire thermostat C 4 W 3 R 2 C 1 W 4 R 3 C Dip switches W Slave Master C W OFF 60 minutes 4-wire zone valve 2 1 Pump Exercise ON Exercise 30 sec./72 hrs. OFF 30 sec./14 days W R 4 3 Priority ON Priority 30 min. R C 4-wire zone valve 2 1 SW1 R 2-wire thermostat Jumper 4 3 Boiler Pump ON Secondary Pump ON C OFF OFF During priority demand 4-wire zone valve 2 1 W 4 R 3 C 2 B 1 A 4 X 3 4-wire zone valve 4-wire zone valve 2 X 1 X N X L N L N L 500 mA fuse 500 mA fuse N Conventional boiler 24 VAC 40 VA transformer Fig. 26 Wiring diagram, V7 28 24 VAC 40 VA transformer L N TM06 6635 1916 Ground screws on frame L

7 UPZC Installation UPZCV-3, -4, -6 multiple-zone valve control Setup with conventional boiler, primary and secondary loops, indirect DHW Aquastat for indirect DHW tank 2-wire thermostat 2-wire thermostat 2-wire thermostat 2-wire thermostat C 4 W 3 R 2 C 1 W 4 R 3 C Dip switches W Slave Master C W OFF 60 minutes 4-wire zone valve 2 1 Pump Exercise ON Exercise 30 sec./72 hrs. OFF 30 sec./14 days W R 4 3 Priority ON Priority 30 min. R C 4-wire zone valve 2 1 SW1 R 2-wire thermostat Jumper 4 3 Boiler Pump ON Secondary Pump ON C OFF OFF During priority demand 4-wire zone valve 2 1 W 4 R 3 C 2 B 1 A 4 X 3 4-wire zone valve 4-wire zone valve 2 X 1 X N X DHW priority pump L N L N L 500 mA fuse 500 mA fuse N Conventional boiler 24 VAC 40 VA transformer 24 VAC 40 VA transformer L N TM06 6636 1916 Ground screws on frame L Fig. 27 Wiring diagram, V8 29

8 UPZC Technical data 8. Technical data UPZCP-1 single-zone pump control relay UPZCP-1 Single-zone pump control relay Input power, 60 Hz Transformer voltage Thermostat output [A] Maximum single-phase motor rating, per zone [A] Maximum combined load rating: output @120 VAC [A] Temperature range, storage [ F ( C)] Temperature range, maximum operation [ F ( C)] Maximum operating humidity range [%] RH Number of knockouts Size of knockouts [in. (mm)] Dimensions, W x H x D [in. (mm)] Approvals Relay type Cover panel Base plate material Terminal block, side-mounted Front indicator lights 120 VAC 24 VAC, 40 VA, Class 2 0.125 5 10 50-100 (10-38) 0-100 (-18 to 38) 90 6 0.875 (22) 5.93 x 4.80 x 2.36 (151 x 122 x 60) CSA 22.2 No. 24/UL Standard 873 Sealed ABS - fire rated Galvanized steel PA66 LED UPZCP- 3, 4, 6 multiple zone pump control relay Model Input power, 60 Hz Transformer voltage Thermostat output [A] Maximum single-phase motor rating, per zone [A] Maximum combined load rating: output @ 120 VAC [A] Temperature range, storage [ F ( C)] Temperature range, maximum operation [ F ( C)] Maximum operating humidity range [%] RH Number of knockouts Size of knockouts [in. (mm)] Dimensions, W x H x D [in. (mm)] Approvals Relay type Cover panel Base plate material Terminal block, side- mounted Front indicator lights 30 UPZCP-3 Three-zone pump control relay UPZCP-4 Four-zone pump control relay UPZCP-6 Six-zone pump control relay 0.375 120 VAC 24 VAC, 40 VA, Class 2 0.5 0.75 5 20 50-100 (10-38) 0-100 (-18 to 38) 90 12 0.875 (22) 8.15 x 10.67 x 2.72 (208 x 272 x 70) CSA 22.2 No. 24/UL Standard 873 Sealed ABS - fire rated Galvanized steel PA66 LED

9 UPZC Approvals UPZCV- 3, 4, 6 multiple-zone valve control relay Model UPZCV-3 Three-zone valve control relay UPZCV-4 Four-zone valve control relay Input power, 60 Hz UPZCV-6 Six-zone valve control relay 120 VAC Transformer voltage 24 VAC 40 VA, Class 2 24 VAC 40 VA, Class 2 0.375 0.5 Thermostat output [A] Maximum single-phase motor rating, per zone [A] Maximum combined load rating: output @ 120 VAC [A] Temperature range, storage [ F ( C)] Temperature range, maximum operation [ F ( C)] Maximum operating humidity range [%] RH Number of knockouts Size of knockouts [in. (mm)] Dimensions, W x H x D [in. (mm)] Approvals Relay type Cover panel Base plate material Terminal block, side-fitted Front indicator lights 24 VAC 80 VA (40 VA x 2), Class 2 0.75 5 20 50-100 (10-38) 0-100 (-18 to 38) 90 12 0.875 (22) 8.15 x 10.67 x 2.72 (208 x 272 x 70) CSA 22.2 No. 24/UL Standard 873 Sealed ABS - fire rated Galvanized steel PA66 LED 9. Approvals The product conforms to UL Standard 873. The product is certified to CSA C22.2 No 24. 10. Service Service parts Part Description 5 A fuse 250 mA fuse 500 mA fuse 24 VAC transformer Kit, Kit, Kit, Kit, UPZC UPZC UPZC UPZC pump fuse, 5-pack transformer fuse, pump board 250 mA, 5-pack transformer fuse, pump board 500 mA, 5-pack transformer, 24 VAC, 40 VA 31

11 UPZC Further product documentation 11. Further product documentation Grundfos Product Center is an online search and sizing tool to help you make the right choice. http://product-selection.grundfos.com SIZING enables you to size a pump based on entered data and selection choices. REPLACEMENT enables you to find a replacement product. Search results will include information on the lowest purchase price the lowest energy consumption the lowest total life cycle cost. CATALOG gives you access to the Grundfos product catalog. LIQUIDS enables you to find pumps designed for aggressive, flammable or other special liquids. All the information you need in one place Downloads Performance curves, technical specifications, pictures, dimensional drawings, motor curves, wiring diagrams, spare parts, service kits, 3D drawings, documents, system parts. The Product Center displays any recent and saved items - including complete projects right on the main page. On the product pages, you can download installation and Operating Instructions, data booklets, service instructions, etc. in PDF format. Subject to alterations. 32

33

Copyright Grundfos Holding A/S ECM: 1185372 Grundfos Kansas City 17100 West 118th Terrace Olathe, Kansas 66061 Phone: 913-227-3400 Fax: 913-227-3500 www.grundfos.us Grundfos Canada 2941 Brighton Road Oakville, Ontario L6H 6C9 Canada Phone: 1-905-829-9533 Fax: 1-905-829-9512 www.grundfos.ca Grundfos México Boulevard TLC No. 15 Parque Industrial Stiva Aeropuerto C.P. 66600 Apodaca, N.L. Mexico Phone: 011-52-81-8144 4000 Fax: 011-52-81-8144 4010 www.grundfos.mx The name Grundfos, the Grundfos logo, and be think innovate are registered trademarks owned by Grundfos Holding A/S or Grundfos A/S, Denmark. All rights reserved worldwide. 99093908 0716

The Grundfos UPZC series of zone controls is the ideal choice for single- and multiple-zone hydronic heating systems using either zone pumps or low-voltage zone valves. Fig. 1 UPZC zone controls All Grundfos UPZC multiple-zone controls are expandable to handle any size of job. UPZC zone controls can control boiler pumps, domestic hot-water

Related Documents:

GRUNDFOS Sarajevo Phone: 387 33 592 480 Telefax: 387 33 590 465 www.ba.grundfos.com email: grundfos@bih.net.ba Brazil BOMBAS GRUNDFOS DO BRASIL Phone: 55-11 4393 5533 Telefax: 55-11 4343 5015 Bulgaria Grundfos Bulgaria EOOD Tel. 359 2 49 22 200 Fax. 359 2 49 22 201 Canada GRUNDFOS Canada Inc. Phone: 1-905 829 9533 Telefax: 1-905 829 .

Grundfos UPS 15-35, from 36 to 165 F (2 to 73 C). Grundfos UP(S) 15 pump with timer, maximum water temperature 150 F (65 C). 4. Operating conditions Grundfos UP(S) Series 15 pumps are designed for indoor use only. Grundfos UP(S)15 series pumps with stainless steel or bronze volutes can be used in both open and closed systems.

GRUNDFOS Un negocio global Con más de 18.000 empleados y una producción anual de . Para mantener su posición de líder, Grundfos constante- . GRUNDFOS ALPHA2, UPS, UP Serie 100 . . . . . .8 GRUNDFOS COMFORT

GRUNDFOS Pumps Corporation 17100 West 118th Terrace Olathe, Kansas 66061 Phone: (913) 227-3400 Telefax: (913) 227-3500 www.grundfos.com Canada GRUNDFOS Canada Inc. 2941 Brighton Road Oakville, Ontario L6H 6C9 Phone: (905) 829-9533 Telefax: (905) 829-9512 Mexico Bombas GRUNDFOS de Mexico S.A. de C.V.

Tel: ( 48-61) 650 13 00 Fax: ( 48-61) 650 13 50 Portugal Bombas GRUNDFOS Por-tugal, S.A. Tel.: 351-21-440 76 00 Telefax: 351-21-440 76 90 Romania GRUNDFOS Pompe România SRL Phone: 40 21 200 4100 E-mail: romania@grundfos.ro Russia ООО Грундфос Россия Тел. ( 7) 495 737 30 00, 564 88 00 E-mail grundfos.moscow@grundfo s.com .

Implementing Grundfos Direct Sensors in New Products 4 Operational Principles This chapter explains the basic operating principles of the Grundfos Direct Sensors Vortex Flow Sensor (VFS) and Relative Pressure Sensor (RPS). 4.1 Vortex Flow Sensor The Grundfos Direct Sens

Supplier eServices @ Grundfos Grundfos EDIFACT D.96.A INVOIC -Title Documentation 01-03-2003 31.10.2014, version 2.07 Grundfos

Inter-Calibration Activities of NSMC/CMA Peng Zhang Key Laboratory of Radiometric Calibration and Validation for Environmental Satellites (LRCVES/CMA) National Satellite Meteorological Center (NSMC/CMA) Email: zhangp@nsmc.cma.gov.cn Tel: 86-10-68409671