Trafford, Pa. 15085 Page 1 October, 1977 - Electrical Part Manual S

6m ago
13 Views
1 Downloads
1.14 MB
20 Pages
Last View : 5d ago
Last Download : 3m ago
Upload by : Jayda Dunning
Transcription

.c om 33-356 8 Westinghouse Electric Corporation Descriptive Bulletin Oil Circuit Breaker Department Power Circuit Breaker Division Trafford, Pa. 15085 Page 1 October, 1977 Supersedes DB 33-356 dated September, 1956 E, D, C/1951 /DB For Outdoor Oil Circuit Breakers .E lec tri ca lP ar tM an ua ls Bushing-Type Current and Linear Coupler Transformers 14.4 kV breaker ww w For For For 230/196 kV breaker 69 kV breaker

.c om Page 2 Bushing-Type Current Transformers (Types for use with out door oil circuit breakers have a secondary winding completely insulated and perma nently assembled on a ring-type core, but have no primary winding or insulation for a primary winding. They are designed to fit over the circuit breaker bushing flanges, which are permanently grounded. Thus the circuit breaker bushing with its conductor or stud becomes the completely insulated single-turn primary winding of the bushing type current transformer. NEMA Standard Ratios and Taps (Type BLC) can be mounted in the same space as bushing-type current transformers when it is desired to provide high speed and sensitive bus differentia I protection through linear coupler bus differential protective relays. Bushing Type an Development of Wirn:ling Current Ratio Multi Single Single Single Relaying Metering Metering Metering 50 To 5 100 To 5 150 To 5 200 To 5 250 To 5 300 To 5 400 To 5 450 To 5 500 To 5 600 To 5 10 To 20 To 30 To 40 To 50 To 60 To 80 To 90 To 100 To 120 To ca Primary Application Secondary Taps Multi-Ratio tri Hipersil"' Hipersil Hipersil"' Hipersil"' Ratio Turn Ratio lP 600 Ampere Current Core Transformer Material BYM BHB BHS BY tM Bushing-Type Linear Coupler Transformers ar All breakers may be equipped with 2 trans formers per bushing, or 12 transformers per three-pole breaker, having the described ratings and accuracy characteristics in accordance with NEMA standard SG4-3.10, based on ANSI standards C57 .13. See tabu lation on Page 6. -600:5MR -1200:5MR -2000:5MR -3000:5MR -4000:5MR X5 X4 X3 X2 X1-5000:5MR 1 1 1 1 1 1 1 1 1 1 X2-X3 X1-X2 X1-X3 X4-X5 X3-X4 X2-X4 X1-X4 X3-X5 X2-X5 X1-X5 1200 Ampere Multi-Ratio .E lec 100 To 5 200 To 5 300 To 5 400 To 5 500 To 5 600 To 5 800 To 5 900 To 5 1000 To 5 1200 To 5 20 To 40 To 60 To 80 To 100 To 120 To 160 To 180 To 200 To 240 To 1 1 1 1 1 1 1 1 1 1 w 300 To 5 400 To 5 500 To 5 800 To 5 1 100 To 5 1200 To 5 1500 To 5 1600 To 5 2000 To 5 60 To 80 To 100 To 160 To 220 To 240 To 300 To 320 To 400 To 1 1 1 1 1 1 1 1 1 X5 X4 X3 X2 X1 Finish Primary Polarity Mark .S . econdary Polarity Mark Start Polarity mark adjacent to terminal X1 indicates that the end of the terminal bushing opposite the breaker contacts and terminal XI have like polarity. With any combination of taps, the tap numercially nearest X1 has the same relative polarity as XI. Current Ratio Turn Ratio Secondary Taps 3000 Ampere Multi-Ratio 300 To 5 500 To 5 800 To 5 1000 To 5 1200 To 5 1500 To 5 2000 To 5 2200 To 5 2500 To 5 3000 To 5 60 To 100 To 160 To 200 To 240 To 300 To 400 To 440 To 500 To 600 To 1 1 1 1 1 1 1 1 1 1 X3-X4 X4-X5 X3-X5 X1-X2 X2-X3 X2-X4 X2-X5 X1-X3 X1-X4 X1-X5 4000 Ampere Multi-Ratio X2-X3 X 1-X2 X 1-X3 X4-X5 X3-X4 X2-X4 X1-X4 X3-X5 X2-X5 X1-X5 2000 Ampere Multi-Ratio ww ua ls BVM, BHB, BHS and BY) 500 To 5 1000 To 5 1500 To 5 2000 To 5 2500 To 5 3000 To 5 3500 To 5 4000 To 5 5000 Ampere X3-X4 X1-X2 X4-X5 X2-X3 X2-X4 X 1-X3 X1-X4 X2-X5 X 1-X5 Figure 1-Connection chart for 600, 1200. 2000, 3000, 4000, and 5000 to 5 ampere multi-ratio bushing-type current transformers. 500 To 5 1000 To 5 1500 To 5 2000 To 5 2500 To 5 3000 To 5 3500 To 5 4000 To 5 5000 To 5 100 To 200 To 300 To 400 To 500 To 600 To 700 To 800 To 1 1 1 1 1 1 1 1 X 1-X2 X3-X4 X2-X3 X1-X3 X2-X4 X1-X4 X2-X5 X1-X5 Multi-Ratio 100 To 5 200 To 5 300 To 5 400 To 5 500 To 5 600 To 5 700 To 5 800 To 5 1000 To 5 X2-X3 X4-X5 X 1-X2 X3-X4 X2-X4 X3-X5 X2-X5 X 1-X4 X1-X5 , F,

33-356 Cl Page 3 .c om Descriptive Bulletin Features Application Low-cost,convenient means of relaying Since these transformers have but a single and metering on conventional outdoor turn primary,the total ampere-turns avail dead-tank oil circuit breakers. able for supplying the secondary burden and the excitation current is equal to the primary page 2 for available tap ratios and Special alloy cores-Hipersil for relaying; current flowing. Hence, on the lower ratios ity and method of marking the secondary Biased-Core or special Hipersil for of bushing-type current transformers more leads are shown in Figs. 3 to metering. care in application is required than is neces sary when applying wound-type current transformers,which usually have 1200 or secondary winding arrangements. The polar 7. For Metering Applications- On the lower ratio transformers considerable improve NEMA Standards-NEMA Standard accu racy classifications met or exceeded, all N EMA Standard ratios provided. more ampere-turns at normal rated primary ment in accuracy over the range of primary current irrespective of the current ratio. currents encountered in metering are ob Two standard-size transformers per bush ing 12 per breaker, available on all The continuous current rating factor (R.F.) is normally 1.0,which in some cases may and secondary winding compensation. For breakers. result in a derating of the breakers contin accuracy metering transformer is recom uous current rating, if the maximum current mended. When necessary,double ratio Linear Coupler Transformers-Immune to ratio of the current transformer specified is metering transformers may be furnished at ac or de saturation for dependable bus less than the breaker continuous current rat an increase in cost and at some reduction in differential relaying. ing. In many cases,bushing current trans formers with rating factors of up to 2.0 may the metering transformers is quite good, be turnished at an increase in cost. often approaching the accuracy of the stand For Relaying Applications. General appli cations involving indicating instruments, ard relaying transformer for the same ratio. standard multi-ratio bushing transformers Nominal primary current ratings are 300, tained by the use of special core materials 400,600,800,1000.1200,1500,1600, 2000.3000, 4000,and 5000 amperes,with mended. The wide choice of available a nominal secondary rating of 5 amperes. ratios permits utilization of the most desir The polarity and method of marking second ary leads are as shown in Figures 3 to except that there are only two secondary if system or load conditions should warrant. leads marked X1 and X2. lec tri Instantaneous Direction of Core Flux Instantaneous Direction/ of Secondary Current .E xs-------- ----' X4 -X3------ X2-------- X1-------- L------X1 L------X2 ' ------ X3 -r---X --- 4 L- 1------xs XI White Polarity Mark above Terminal indicates like Polarity ww w for the Marked Primary (the end of Breaker Figure 2--Arrangement of two transformers on one pole of an oil circuit breaker, showing relative directions of current and core flux. 7, able ratio when installed,and provides a convenient means of future change in ratio ca Circuit Breaker Pole Unit accuracy. The over-current performance of tributed,secondary windings are recom lP Arrangement of Transformers on such applications.the single-ratio high having uncompensated, tapped,fully dis ar ua ls 5000 amperes,with a nominal secondary current rating of 5 amperes. See Fig. 1 on an are 600, 1200,2000,3000,4000,and tM Nominal maximum primary current ratings Contacts the Breaker Terminal opposite the Breaker Contacts) and the Marked Secondary (Terminal XI.)

.c om Page 4 Identification of Transformers and Leads ) X2 X4 w X3 - X5 5X1 5X2 5X3; 5X4 () w X1 5X5 X2 5Y1 w X5 () - X2 () () 1X3 1X4 X2. ) 1Y2 1Y1 1 ) Pole 1 ) - ------ 1X 1 1X2 1X3 1X4 1X5 0 0 0 0 0 3X1 0 3X5 0 0 5X 1 5X2 5X3 5X4 5X5 0 0 6X1 6X2 6X3 6X4 6X5 ca § i ! § § .n tri lec .E w ww 0 0 O ,. 1Y 1 0 '-- 1Y2 0 0 0 '-- 0 0 0 0 '--- L 0 0 0 3Y1 3Y2 0 0 0 0 0 O . . , , Circuit Breaker -'-----!--- Short-Circuiting Terminal Blocks ----- Mechanism Housing 0 0 0 0 0 O ; 8. o . . . ;::::::: 0 0 0 0 0 0 . . transformers are located on bushings 1-3-5 unless otherwise specified. 0 2X2 2X3 2X4 2X5 4X 1 4X2 4X3 4X4 4X5 0 Figure 3-Standard method of identifying trans formers and leads on multi pole oil circuit breakers. Note: When one transformer per pole is used, 0 0 0 0 0 o o 2X1 lP L 1X5 () 2 ar ) LJ X1 Pole I 3Y2 LJ X5 3 w Q X1 3Y1 ;j Pole 5Y2 3X5 X3 j X4 () ua ls an X tM ,.5 . 0 0 0 o . , j

.c om 33-356 Descriptive Bulletin Page 5 1 X1 X3: X4 X2 ( r u X5 0 I ---- ) Instruments, Relay Coils, or Trip Coil u r X3 ) i X4 ) X5 LJ X4 X5 X4 ( X5 X5 ( LJ X4 I X3 () ( -----.J . .E lec ) X3 Q tri () -o lP ca LJ 0 X2 0 X1 ,- Instruments Figure 5-Two transformers per breaker pole, connected independently, It is recommended that instruments be operated on separate transformer. X1 ) X2 t f"' Relay Coils or Trip Coil - X3 ar X2 (\ tM Figure 4-0ne transformer per breaker pole. X1- .n an o ua ls Schematic Diagrams of Transformer Connections . Instruments, Relay Coils, or Trip Coil X2 X1 -D t Figure 6-Two transformers per breaker pole, connected in series, used when burdens are large. (). -.:::. -- X1 X1 X2 X3 X4 J ) () () XS I ww w L- L-- Instruments Figure 7-Four transformers per breaker pole, two per terminal connected independently and two per terminal connected in series. XS L L------- Relay Coils or Trip Coil ) .() X4 X3 I - - - n r -- - -r lnst ume ts, Relay Coils, or Trip Coil t

Accuracy Classifications Outdoor Oil Circuit Breakers-Bushing-Type Current Transformers Outdoor Oil Circuit Breaker Rating Type MVA or kA Relaying Amperes Accuracy (3) Multi-Ratio (2) C200 144G1500 1500 3000 3000:5 C400 144G1500 1500 4000 4000:5 1500 6000 6000:5 1200 1200:5 C200 1200 1200:5 ,C200 345GS1500 1500 1200 1200:5 345G1500 1500 1200:5 345G1500 1500 1200 2000 345G2500 2500 2000 2000:5 345G2500 2500 3000 3000:5 1200:5 1200:5 C200 300:5 0.6B-0.5 C400 400:5 0.3 B-0.5 C400 600:5 0.3 B-0.5 800:5 0.3B-0.5 1500 1200 1500 460GS2500 2500 1200 1200 1200:5 C200 460G2500 2500 1200 1200:5 C200 460G2500 2500 2000 2000:5 C400 1200:5 C400 1200:5 C400 2500 1200 2500 1200 3500 1200 3500 5000 1200 2000 121GM20 20 1200 121 GMS20 20 20 40 1600 2000:5 2000 2000:5 1600 2000:5 2000 2500 2000:5 3000 3000:5 2000 3000 2000:5 3000:5 121 GMB40 40 40 121 GMB40 40 121 GMB63 121GMB63 63 63 145GM20 145GMS20 145GMS20 20 1200 20 1600 2000 20 40 145GMB40 40 145GMB40 40 40 1600 2000 2500 3000 .E lec 145GMB40 145GMB40 145GMB63 145GMB63 63 63 2000 2500 2000:5 1200:5 3000:5 1200:5 2000:5 2000:5 2000:5 2000:5 3000:5 3000:5 3000:5 3000:5 145GMB63 63 3000 3000:5 169GM16 16 1200 1200:5 169GM31 31.5 1600 2000:5 169GM31 31.5 2000 2000:5 169GM50 50 2000 2000:5 169GM50 50 3000 3000:5 40 2000 2000:5 40 3000 3000:5 242GMA50 50 2000 2000:5 242GMA50 50 3000 3000:5 242GMA63 63 2000 2000:5 242GMA63 63 3000 3000:5 362GW50 50 2000 2000:5 362GW50 50 3000 3000:5 362GW63 63 2000 2000:5 362GW63 63 3000 3000:5 w 242GMA40 242GMA40 ww C200 1200:5 1200:5 690GS2500 690G2500 690GS3500 121GMB40 362 C400 C400 460GS1500 121 GMB40 242 C200 C200 C400 460G1500 121 GMS20 169 an 1500 1500 690GM5000 145 caoo caoo 230GS1500 690G3500 121 C200 230G1500 2000:5 Accuracy tM 69.0 1200:5 ar 46.0 1200:5 1200 lP 34.5 1200 1000 ca 23.0 1000 144G1000 144G1500 Metering Single Ratio (4) 144GS1000 tri 14.4 ua ls kV Transformer Accuracy Classifications (1) .c om Page 6 caoo caoo caoo caoo caoo caoo caoo caoo caoo caoo caoo caoo caoo caoo caoo caoo caoo caoo caoo caoo caoo caoo caoo caoo caoo caoo caoo caoo caoo caoo caoo caoo caoo caoo caoo 1000:5 0.3B-1.0 1200:5 0.3B-1.0 1500:5 0.3B-1.0 1600:5 0.3B-1.0 2000:5 0.3B-2.0 3000:5 0.3B-2.0 4000:5 0.3B-2.0 5000:5 0.3B-2.0 Note: These values apply only when current trans· formers are used on 60-Hertz Circuits. 12) The nominal primary current rating of the standard multi-ratio transformer corresponds to the listed continuous current ratings of the breakers. except that circuit breakers rated 1600 and 2500 amperes use current transformers rated 2000 and 3000 amperes respectively. Accuracies listed correspond to the require(3) ments of NEMA SG4 and apply to the full secondary winding. It is recommended that the minimum ratio selected shall not be less than 50 percent of the continuous current rating of the circuit breaker. (1) (4)

.c om 33-356 Descriptive Bulletin Page 7 Non-Standard Transformer Accuracy ondary current without exceeding 10 per Classification cent ratio error. Since the nominal rated sec The table of relaying and metering accura current is 100 amperes,and the ohms im ondary current is 5 amperes, 20 times rated pedance of the secondary burden is given by dividing the burden voltages of 200, 400 and 800 by 100 giving the standard relaying several limitations,such as the single-turn burdens of 2.0, 4.0 and 8.0 ohms, respec primary and space limitations in apparatus, tively,as listed in ANSI Standards C-57.13. ua ls cies available on standard transformers for oil circuit breakers is in accordance with N EMA SG4. Since bushing transformers have the table furnishes an excellent and needed guide as to the performance which may be expected and economically obtained in standard apparatus. It is impractical to cover 69-kv breaker is a 1200:5 MR type BYM transformer with a C400 accuracy classifica tion. This transformer is one which on the an all possible specific applications such as special accuracies, accuracies at other than For example, the standard relaying trans former for a type 690G2500,1200-ampere, 60 Hertz, ratios other than those listed, special rating factor (R.F.). etc. Any relaying 1200 to 5 ratio will not have a ratio error in excess of 10 per cent,under steady state or metering applications not suitably cov ered here should be referred to Power Circuit times rated secondary current when ener gizing secondary burdens equal to or less than the standard B-4 burden, 4 ohms 50 per tM Breaker Marketing Department,Trafford, Pennsylvania,for further information. Relaying Service Accuracy Classification ar The last figure in this classification also has added significance in that on an open C800. The letter " C " designates a trans former having low internal impedance,of circuit excitation test,approximately this classifications such as C200, C400 and voltage must be developed when the excit which bushing current transformers are an ing current transformers, see Fig. 8 for curves) . Although the classication is based lP ratio transformers and are indicated by the ing current in amperes is equal to the per cent ratio error (10 amperes for these bush having high internal impedance, of which only on the maximum ratio,it also gives the usua I wound primary current transform some information as to approximating the ers are an example. The numbers following performance on lower ratios, since the exci tation voltage varies directly with the ratio ca voltage the transformer will deliver to a and the excitation current varies inversely as standard burden at 20 times nominal sec- the ratio. This can be seen readily from the tri lec .E typical curves) . The various accuracies listed apply to the the letter such as 200,400 and 800,is the w cent lagging power factor (See Fig. 8 for maximum ratio of the corresponding multi example,as compared to a "T" transformer, ww conditions, over a range of one to twenty curves of Fig. 8.

.c om Page 8 Metering Service Accuracy Classification Likewise,in the case of bushing current Commercial Tests at Factory transformers,the accuracy is a function of the ratio,since the primary is limited to a service is based on limits of "Transformer single turn. Other things being the same, the Correction Factor" (TCF); see ANSI higher the current ratio the lower the ratio C-57.13. The TCF is that factor by which a and phase angle errors. 1. All transformers are checked for proper nameplate and polarity markings. ua ls The accuracy classification for metering 2. All transformers are checked electrically to insure proper direction of windings to wattmeter reading must be multiplied to correct for the ratio and phase angle errors For example,on the type 345G 1500,1200- of a current transformer,within specified ampere,34.5-kV breaker a 0.38-0.5 accuracy limits of power factor of the circuit being classification has been assigned to a 600:5 metered. The various accuracy classes have single ratio metering bushing current trans definite limiting values for the TCF's at both former. The TCF of this transformer will be 100 per cent and 10 per cent of rated pri mary current,and are designated by the between 0.997 and 1.003 at 100 per cent maximum per cent error permitted by the limiting value of the TCF at 100 per cent these same limits and the phase angle "f:J" will be between 15.6 minutes. The corres rated primary current. ponding limits at 10 per cent rated primary current are a TCF between 0.994 and 1.006, A definite relationship exists between the "Transformer Correction Factor" (TCFL the and RCF between 0.994 and 1.006 and f3 be tween 31.2 minutes. As indicated by the "Ratio Correction Factor" (RCF) and the second part of the accuracy classification, insure the correctness of winding for each "Phase Angle" {iJ) for power factors of the B-0.5,the foregoing accuracy limits will be tap section. In addition, two excitation metered circuit between 1.0 and 0.6 lagging met when the transformer is energizing the check points are taken on the secondary as given by the following expression: standard B-0.5 burden equa I to 12.5 volt with the primary open-circuited to insure amperes at 90 per cent power factor lagging based on 5 amperes, 60Hertz. See Fig. 9 for each transformer meets its specified of the Ratio Correction Factor for any given Since the secondary burden imposed on a given sufficient ratio tests to insure the proper number of turns; multi-ratio trans formers are given sufficient ratio tests to relaying accuracy classifications. 5. All transformers for metering service are checked for ratio and phase angle at 10 insure that they meet their metering accu racy requirements. 6. After installation in the oil circuit breaker each transformer is given a one-minute parallelogram. Application data consisting of typical RCF and phase angle data on iden potential test of 2500 volts between the ca errors are within the limits of the 0.3 tical units when energizing the standard request. metering budrens will be furnished upon Refer to the Power Circuit Breaker Market ing Department,Trafford, Pennsylvania for information concerning special tests using other ANSI Standard or special burdens lec and I or other current test points. .E 4. All transformers for relaying service are and 100 per cent rated primary current to tri metering classification denote the accuracy class and the second part denote one of the standard metering burdens. w circuited,for a period of 18 seconds. ly assigned only one accuracy classification, such as 0.38-0.5,and each unit with this assigned classification would be tested at 10 burden to insure its RCF and phase angle its ratio and phase angle errors,the sec ww ary winding,with the primary open and 100 percent rated current with the B-0.5 current transformer has a material effect on accomplished by having the first part of the of ANSI C-57.13,across the full second Each metering current transformer is normal lP Transformer Correction Factor. with the accuracy classification. This is induced potential test by applying a volt age,in accordance with the requirements typical metering performance curves. This results in a parallelogra describing the limits of the Phase Angle as a function ondary burden must be inherently tied in tM ar f:J 2600 (RCF-TCF) minutes: 3. All transformers are given a 400 Hertz an rated current. The RCF will be between give correct polarity. shorted secondary winding including leads and ground. Also ,each transformer is given polarity and ratio check tests to insure correct installation in the oil breaker. circuit

Descriptive Bulletin Cl Page 9 Relaying Transformers Typical Excitation Curves for all standard ratios showing secondary volts vs second 1000 1 ary exciting amperes will be furnished on request. The curves will be extended to the C!lrttnt ,'!Wio 'too: 2Qil,s 3(!!))5 . IQO: 00 :6 00:5 'furxL S. i R,!i ( '!0:1 40:1 (t10 «0:1 '().16· ' 0;1 M! 1QO:I 0.2& 12Q:l O S1 . 801l!S 160:1·· 0.41 1 1!11:1· o. ? t o.st '1200':a 2 o: 1 o. 2 . 4\'1 5' t equivalent of 25 amperes exciting current through the full secondary winding provided these values do not require an excitation QV:a Dash 'une Actu t Voftlt9e wilt not cbl!: l,eu: tban !1% of ttteCutvG'Vatue f!el wQash lfl'le Aetual Exciting Currf;I:M wfU,notbe mate thah 25% l he CvrveVatus voltage in excess of 1600 volts. 100 1 8 The approximate 75 C resistance of the secondary winding is provided on the curves ua ls Performance Data ----------- 200' :5 8. an of Figure .c om 33-356 1 001 6 8 1 .01 ar 1 0 1 tM 10 6 8 1 01 6 Sac Exciting Amp1. 8 1 10 - I8 6 6 8 1 10 8 1 100 ca lP Figure 8-Typical excitation for a curve 60-Hertz, 1200:5 MR. C400 Relaying Transformer. Metering Transformers E 30 tri Typical Ratio Correction Factor and Phase Angle Curves for the standard metering bur dens of B-0.1, B-0.2, B-0.5 and B-1 from 5 to 150 percent of rated primary current, pro . -30 lec vided the transformer errors to not exceed .E those of accuracy class 1.2 of ANSI C-57.13, will be furnished on request. Curve Secondary Power No. Burden Ohms Factor o/o 0.1 90 2 0.2 90 3 4 0.5 90 1.0 50 ww w 1 1.02 l' 0 8 01 1 00 99 20 40 60 80 Percent rate P primary current Figure 9-Typical ratio correction factor and phase angle curves for 400:5, single ratio, 60 Hertz, 0.38-0.5 Metering Transformer. 100 120 140 160

Ordering Information .c om Page 10 Bushing-Type Linear Coupler Transformers Type BLC The following information should be included on orders or inquiries for bushing-type current transformers: 1. Identification of type and rating of the circuit breaker on which the transformer is to be installed. ua ls Application The Type BLC linear coupler transformers are intended for use with linear coupler dif ferentia I protective relays to provide de a. If installation is on a new breaker, this information should be in the breaker order reading. pendable high speed,sensitive protection to station buses. These linear coupler trans formers are "Air-Core" reactors having in b. If installed is on a breaker previously installed,the following information snould be given to Power Circuit Breaker Marketing for a quotation: duced secondary voltages proportiona I to the primary current. Unlike current transformers, there is no saturation of magnetic circuit of the linear coupler transformer when it is subjected to heavy fault currents,even when the latter contains large d c transient cur an {1) Breaker type, original breaker shop order and serial number. {2) State whether the new bushing current transformers are to be added to the existing breaker or are to replace some of the existing bushing current transformers. rents. This eliminates an ever-present prob lem which must receive consideration when {3) Give the desired terminal location, i.e.,1-3-5 {left-hand side when facing the tM mechanism housing) or 2-4-6 {right-hand side) and whether in the upper or lower {closest to the breaker contacts) positions. 2. State circuit frequency. ar 3. State application. a. For relaying service. lP {1) Ratio desired. {2) Relaying accuracy classification {i.e. C400). {3 ) Rating factor {R.F.) if greater than 1.0. ca b. For metering service. {1) Ratio desired. tri {2) Metering accuracy classification {i.e.,0.38-0.5). using current transformers for bus differen tial protective relaying. The differential circuit for linear coupler differential protection is formed by connect ing the linear coupler transformer second aries and linear coupler relays in series as shown in the accompanying schematic dia gram {see Figure 10). The simplicity and ease of application of linear coupler transformers and relays pro vide an outstanding method of station bus protection. Ratings rated at 0.005 ohms 1% * mutua I react The standard linear coupler transformer is circuit, secondary induced voltage of 5 volts ance at 60 Hertz. This provides an open per thousand amperes primary current. ww w .E lec {3) Rating factor {R.F.) if greater than 1.0. The secondary self-impedances of linear coupler transformers vary with the size and specific design. Their values along with the number of circuits on the bus have a bearing on the sensitivity of the bus protection. The variations in sizes of linear coupler transformers are dictated by the rating and design of the breakers in which they are to be installed. When ordering linear coupler transformers for breakers already installed, the breaker identification {S.O. number) or limiting dimensions for the linear coupler must be furnished. * Prior to 1950 tolerance was 1.5%.

Cl Page ------- D p c --- ) -D c ri) u J Bkr. N r-D c fi --- c c """: . --- BLC Linear Coupler Transformers Polarity w .E Figure 10-Typical schematic d iagram of Linear Coupler Bus Diff erent ial Protection with Series Differential Loop using Phase Relays. Ph 1 - Py-:; ,. , , """ '"" '"" Ph 2 -:;Py ,. -o- o-H :o -4 , h 3 Ph PI Pos Bus Neg Bus ca lec tri , ",r NO lP Ground at "'" only one place Breaker Aux. sws and Trip Coils Linear Coupler Phase Relays LC-2 as shown LC-1 same except no "N" Connection N1 N2 N3 Circuit Breakers ar --- r- r-) D ua ls Bkr. 2 Protected 3 Phase Bus an 3---- . --- ----1-- 11 tM 2-------- --1-- ww .c om Descriptive Bulletin 33-356 Bell Bus .25 ohms 125v, .50 ohms 250v loading res. ) 5) N p TC I TN ---- T4 - T1 T3 T2 : . p !::: WL Auxiliary Tripping Relay N T

33-356 Page .c om Descriptive Bulletin 12 ww w .E lec tri ca lP ar tM an ua ls . Westinghouse Electric Corporation Oil Circuit Breaker Department Power Circuit Breaker Division Trafford, Pa. 15085

.c om 230/19& For 69 kv breaker ar tM For an ua ls - ca Q6 lP kv breaker . . . BUSHING-TYPE CURRENT TRANSFORMERS (TYPES BYM, BHB, BH ANO BY) for use with outdoor oil circuit breakers have a secondary .E lec tri winding completely insulated and permanently assembled on a ring-type core, but have no primary winding or insulation for a primary winding. They are designed to fit over the circuit breaker bushing flanges, which are permanently grounded. Thus the circuit breaker bushing with its conductor or stud becomes the completely insulated single-turn primary winding of the bushing-type current transformer. All breakers, except those with interrupting ratings of 250 mva or less, may be equipped with 2 transformers per bushing, or 12 transformers per three-pole breaker, having the described ratings and accuracy characteristics in accordance with NEMA standards SG4-3.09 and SG4-3.10, based on ASA standards C-57, Section 13. See tabulation on Page 4. Breakers rated 250 mva or less take a maximum of 6 transformers. BUSHING-TYPE LINEAR COUPLER TRANSFORMERS (TYPE BLC) can be mounted in the same space as bushing-type current trans formers when it is desired to provide high speed and sensitive bus differential protection through linear coupler bus differen· tial protective relays. BUSHING-TYPE CURRENT TRANSFORMER Type Type Type Type BYM BHB BH BY CORE MATERIAL Hipersil Hipersil Hipernik Hipersil RATIO Multi Single Single S ingle PRIMARY APPLICATION Relaying Metering Metering Metering * The classification of multi-ratio transformers for relaying service and single-ratio transformers for metering service is a very general segregation. Depending on the specific conditions, any of the above types of transformers may be suitable for either or both relaying and metering applications. ----------------------- . w WESTINGHOUSE SPECIAL FEATURES eLOW-COST, CONVENIENT MEANS OF RELAYING AND METERING on conventional outdoor dead-tank oil circuit breakers. ww eVACUUM-PRESSURE-IMPREGNATED to provide greater integrity of insulation. eSPECIAL ALLOY CORES--Hipersil for relaying; Hipernik or Biased-Core Hipersil for metering . eNEMA STANDARDS--NEMA Standard accuracy classifications met or exceeded, all NEMA Standard ratios provided. eTWO STANDARD-SIZE TRANSFORMERS PER BUSHING 12 per breaker, available on all breakers except those rated 250 mva and below. eLINEAR COUPLER TRANSFORMERS--Immune to a-c or d-e saturation for dependable bus differential relaying. Supersedes Descriptive Bulletin Mailed t o: E/279, 280/DB; C26-5Z 33-765 dated December, 1952 SEPTEMBER, 1956

NEMA STANDARD RATIOS AND TAPS STUD Since these transformers have but a single-turn primary, the total ampere turns available for supplying the secondary burden and the excitation current is equal to the primary current flowing. Hence, on the lower ratios of bushing-type current transformers more care in application is required than is necessary when applying wound-type c u r r e n t transformers, which usually have 1200 or more ampere-turns at normal rated primary current irrespective of the current ratio. Q I X3 X2 WINDING XI FINISH X4 tM DEVELOPMENT OF X2 START XI ar Fig ure 1-Connection chart for 600, 1200, 2000, 3000, 4000, and 5000 to 5 ampere multi-ratio bushing-type current transformers. IDENTIFICATION OF TRANSFORMERS AND LEAD S r-- ·-·------- ---------- 1 o--- - t -l-----ff'A' ''F 1---f-- --l I X2 XI lec X2 2XI 0 0 .E w MARK X3 Polarity mark adjacent to terminal Xl indicates that the end of the terminal bushing opposite the breaker contacts and terminal XI have like polarity. With any combination of taps, the tap numercially nearest Xl has the same rel

current irrespective of the current ratio. The continuous current rating factor (R.F.) is normally 1.0, which in some cases may result in a derating of the breakers contin uous current rating, if the maximum current ratio of the current transformer specified is less than the breaker continuous current rat ing. In many cases, bushing current .

Related Documents:

Key Benefit Claimants & Worklessness 20 Trafford: Business 23 Economy: Drivers of Productivity, Industrial Structure and Economic Forecasts 23 Centre for Enterprise 26 Productivity: Gross Value Added 27 Locations and Sizebands of Business in Trafford 28 Key Centres of Business in Trafford 31 Trafford: Place 35 Employment Land 36 Transport 37

Hilti (Gt. Britain) Limited, 1 Trafford Wharf Road, Trafford Park, Manchester M17 1BY Telephone: 0800 886 100 . HILTI CP 648 . Firestop Wrap. The enclosed pages are taken from the . Hilti Firestop Systems Manual . Edition April 2011 . Supported by additional standard details . For Material Safety data sheets . visit the technical library at

as soccer, basketball and Volleyball. It also provides a well-equipped fitness center with impressive facilities for those interested in maintaining their physical fitness. Old Trafford Multisport complex Ltd. is in its development stage and when fully developed would take on the Limited liab

ef-fec1we issued by sandy valley water district ,-eb ri 7 '. ovh :- vi) hjj\j (name by -@- index page 1. page 2. page 3. page 4. page 5. page 6. page 7. page 8. page 9. page 10. page 1 1. page 12. page 13. page 14. page 15. page 16. page 17. page 18. page 19. page 20. .

The Lenape / English Dictionary Table of Contents A page 2 B page 10 C page 10 D page 11 E page 11 F no Lenape words that begin with F G page 14 H page 19 I page 20 J page 20 K page 21 L page 24 M page 28 N page 36 O page 43 P page 43 Q page 51 R no Lenape words that begin with R S page 51 T

Cahier pédagogique À deux roues, la vie! DynamO Théâtre 2 page 3 page 3 page 3 page 4 page 4 page 5 page 5 page 5 page 6 page 7 page 8 page 9 page 10 page 11 page 12 page 12

ÌSprue Bushing MSB-A3530 Page 18 Page 18 Page 18 Page 19 Page 19 Page 19 Page 20 Page 20 Page 20 Page 21 Page 21 Page 21 Page 22 Page 22 Page 22 Page 23 MSB-B3030 MSB-C2520 MSB-D3030 MSB-E2520 MSB-F1530 MSB-G3520 MSB-H3530 . HOT CHAMBER S L GP GB GPO EP C SB SP CL ML MAIN PRODUCTS ITEM

The modern approach is fact based and lays emphasis on the factual study of political phenomenon to arrive at scientific and definite conclusions. The modern approaches include sociological approach, economic approach, psychological approach, quantitative approach, simulation approach, system approach, behavioural approach, Marxian approach etc. 2 Wasby, L Stephen (1972), “Political Science .