Raychem IceStop Installation And Operation Manual For Roof .

2y ago
41 Views
2 Downloads
2.86 MB
76 Pages
Last View : 19d ago
Last Download : 3m ago
Upload by : Isobel Thacker
Transcription

IceStop SystemINSTALLATION AND OPERATION MANUAL FORROOF AND GUTTER DE-ICING SYSTEMSTHERMAL MANAGEMENT SOLUTIONSWWW.THERMAL.PENTAIR.COM

Important Safeguards and WarningsWARNING: FIRE AND SHOCK HAZARD.IceStop roof and gutter de-icing systems must beinstalled correctly to ensure proper operation and toprevent shock and fire. Read these important warningsand carefully follow all the installation instructions. To minimize the risk of fire from sustained electricalarcing if the heating cable is damaged or improperly installed and to comply with Pentair ThermalManagement requirements, agency certifications,and national electrical codes, ground-fault equipmentprotection must be used on each heating cable branchcircuit. Arcing may not be stopped by conventionalcircuit breakers. Approvals and performance are based on the use ofPentair Thermal Management parts only. Do not substitute parts or use vinyl electrical tape. Bus wires will short if they contact each other. Keepbus wires separated. Connection kits and cable ends must be kept drybefore and during installation. The black heating cable core and fibers are conductive and can short. They must be properly insulatedand kept dry. Damaged bus wires can overheat or short. Do notbreak bus wire strands when scoring the jacket orcore. Damaged heating cable or connection kits can causeelectrical shock, arcing or fire. Do not attempt torepair or energize damaged cable. Remove damagedsections at once and replace them with a new lengthusing the appropriate Pentair Thermal Managementsplice kit. Replace damaged connection 7 03/13

Table of Contents12General Information11.1 Use of the Manual11.2 IceStop Applications11.3 Safety Guidelines21.4 Typical Roof and Gutter System31.5 Approvals61.6 Warranty6Pre-Installation Checks72.1 Check Materials72.2 Connection Kits and Accessories3456782.3 Review the Design12Heating Cable Installation133.1 Heating Cable Handling133.2 Protecting the Heating Cable143.3 Visual Inspection143.4 Heating Cable Layout15Attachment Methods294.1 Overview294.2 Roof Attachment Methods304.3 Attachment Methods for Other Areas35Control, Monitoring and Power Distribution395.1 Control Systems395.2 Power Distribution44Commissioning and Preventive Maintenance486.1 System Start-up and Operation486.2 Insulation Resistance (Megohmmeter) Test486.3 Continuity Test51Test Procedures527.1 Tests527.2 Insulation Resistance Test – Test 1527.3 Insulation Resistance (Megohmmeter) Test537.4 Fault Location 7 03/13iii

89ivTroubleshooting Guide60Installation and Inspection 067 03/13

11.1General InformationUse of the ManualThis manual covers the installation of RaychemIceStop roof and gutter de-icing system. The manualcovers general heating cable installation proceduresand specific installation details and shows availableconnection kits. The manual also discusses controls,testing, and periodic maintenance.This manual assumes that the proper roof and gutterde-icing design has been completed according to theRoof and Gutter De-Icing: IceStop System DesignGuide (H56070).Only the applications described in Section 1.2 areapproved by Pentair Thermal Management forIceStop systems when used with approved PentairThermal Management connection kits. The instructions in this manual and the installation instructionsincluded with the connection kits must be followedfor the Pentair Thermal Management warranty toapply. Contact your Pentair Thermal Managementrepresentative for other applications and products.1.2IceStop ApplicationsRaychem IceStop is a roof and gutter de-icing systemthat provides drain paths for the followingapplications: Roofs made from standard roofing materials,including shake, shingle, rubber, tar, wood, metal,and plastic. Gutters made from standard materials, includingmetal, plastic, and wood. Downspouts made from standard materials,including metal and plastic.The guide does not provide information for using anIceStop system for the following applications: Preventing snow movement on roofs—IceStop willnot keep snow or ice from falling off the roof.IceStop is designed to remove melt water, notaccumulated snow. Snow fences or snow guardsshould be used to eliminate snow 067 03/131

1General InformationFor the names of manufacturers of snow guardsor snow fences, contact your Pentair ThermalManagement representative, or contact PentairThermal Management directly at (800) 545-6258. Melting snow on a roof and/or reduction of snowload—IceStop is designed to remove melt water,not accumulated snow.If your application conditions are different, or if youhave any questions, contact:Pentair Thermal Management7433 Harwin DriveHouston, TX 77036USATel: 1.800.545.6258Tel: 1.650.216.1526Fax: 1.800.527.5703Fax: pentair.com1.3Safety GuidelinesThe safety and reliability of any heat-tracing systemdepends on the quality of the products selected andthe manner in which they are installed and maintained. Incorrect design, handling, installation, ormaintenance of any of the system connection kitscould damage the de-icing system or the roof andmay result in inadequate de-icing, electric shock, orfire. To minimize these risks and to ensure that thesystem performs reliably, read and carefully followthe information, warnings, and instructions in thisguide. Important instructions are marked Warnings are DeIcing-IM-H58067 03/13

11.4General InformationTypical Roof and Gutter SystemIce dams can cause water ingress into buildings andgenerate dangerous icicles. An IceStop system canhelp prevent ice dams and icicles by maintaininga continuous path for melt water to drain from theroof. As long as a heated path from the roof to a safedischarge area is maintained, ice dams will not form.The IceStop system can be used on roofs and valleysand in downspouts and gutters made from all typesof standard roofing materials, including metal, plastic, wood, shake/shingle, rubber, and tar.The IceStop system is intended to provide drainpaths. A typical system is shown in Figure 1.EN-RaychemIceStopRoofGutterDeIcing-IM-H58067 03/133

1General InformationPower Connection KitsSplice KitsHeating CablePower Distribution PanelSnow ControllerGutter SensorAPSSnow/I -4ceMelting ControllerSUPHEA PLYUSE TER : 277ONL : 377 VACY COP VAC , 50/6SEE SUF PER , 40 AMP0HZINST FICI CON . Z, 35VALL ENT DUC MAX AATIO AMP TOR RESACIT S HAVISN INSTY.INGRUCTIONSSUPPLYSNOWHEDANLeth GERqual al voltaOFified gesELEC WARare TRIC NINGrequpersonnepres ALiredSHOto l only ent bene CKde-e . MorORnerg e athELCTize than thisthis one cove ROCUTIOcont disc r. Servrol onne iceeNforserv ct may byicing be.ATERGROUNDFAULTATERES R CYCETLET GROUNDHETESFAULTHOLDONTIME (HRS)Figure 1: IceStop Roof and Gutter De-Icing 7 03/13

1General InformationTee KitsAttachment KitsDownspout Hanger KitEnd Seal KitEN-RaychemIceStopRoofGutterDeIcing-IM-H58067 03/13Lighted End5

11.5General InformationApprovalsThe IceStop roof and gutter de-icing system is ULListed, CSA Certified, and FM Approved for use innonhazardous areas. GM-1XT and GM-2XT are alsoFM Approved for use in Class I, Division 2 hazardouslocations.1.6WarrantyPentair Thermal Management’s limited standardwarranty applies to all products. You can access thecomplete warranty at www.tycothermal.com. Toqualify for an extended 10-year warranty, registeronline within 30 days of installation tterDeIcing-IM-H58067 03/13

22.1Pre-Installation ChecksCheck MaterialsIf physical damage is found, the entire damaged section must be removed and a new section of heatingcable spliced in, using only approved Raychem splicekits. Do not attempt to repair the damaged heatingcable section. If the damage cannot be found, thecomplete circuit should be removed and replacedwith new IceStop heating cable.WARNING: Shock or Fire Hazard. Damagedheating cable or connection kits can cause electricalshock, arcing, and fire. Do no attempt to energizedamaged heating cable or connection kits. Replacethem immediately using a new length of heating cableand the appropriate IceStop accessories.Catalog number:GM — 1 or 2XT or XProduct familyVoltage1 120 V2 208-277 VJacket type: FluoropolymerorPolyolefinFigure 2: Catalog numberEN-RaychemIceStopRoofGutterDeIcing-IM-H58067 03/137

22.2Pre-Installation ChecksConnection Kits and AccessoriesTable 1: CONNECTION KITSCatalog numberDescriptionHeating cableallowance1Power connectionRayClic-PCRayClic-PSRayClic-PTQuick connect power con- 2 ft (0.6 m)nection kit to power 1 runof heating cable. Includes 1end seal.Standard pkg: 1Quick connect power con- 2 ft (0.6 m)nection kit to power 2 runsof heating cable. Includes 2end seals.Standard pkg: 1Quick connect power con- 3 ft (1 m)nection kit to power 3 runsof heating cable. Includes 3end seals.Standard pkg: 1Alternate lighted end seal 2 ft (0.6 m)Standard pkg: 1RayClic-LERCross connection to connect four heating cablesStandard pkg: 18 ft (2.4 m)Extra end sealStandard pkg: 10.3 ft (0.1 m)RayClic-XEnd M-H58067 03/13

2Pre-Installation ChecksTable 1: CONNECTION KITSCatalog numberDescriptionHeating cableallowance1Junction boxJunction box1 mounted2 ft (0.6 m)HSP power connection kits.Includes 1 end seal.Standard pkg: 1FTC-PSplice connectionQuick connect splice kitStandard pkg: 12 ft (0.6 m)RayClic-SHeat-shrinkable splice kit 2 ft (0.6 m)Standard pkg: 2FTC-HSTTee connectionQuick connect tee kit2 ft (0.6 m)Standard pkg: 1RayClic-THeat-shrinkable tee kitStandard pkg: 22 ft (0.6 m)FTC-HST212Junction box not included.One RayClic-E end seal is required for each FTC-HST used asa tee kit.EN-RaychemIceStopRoofGutterDeIcing-IM-H58067 03/139

2Pre-Installation ChecksTable 2: ATTACHMENT ACCESSORIESCatalog number DescriptionNo. of packages requiredMounting bracketRayClic wallmountingbracketStandard pkg: 11 mounting bracket/RayClic connection kit(except RayClic-E) installedon a wallMechanical(penetrating)roof clip1 box per 35' of roof edgewhen zig-zag layout isusedRayClic-SB-02Standard pkg: 50GMK-RCHanger bracketStandard pkg: 11 hanger per cable indownspout or as requiredfor mechanical protectionUV-resistantcable tieVaries depending oninstallationGM-RAKECT-CABLE-TIEStandard pkg: 10010EN-RaychemIceStopRoofGutterDeIcing-IM-H58067 03/13

2Pre-Installation ChecksAdhesives for Metal RoofsWith the adhesives that are available today, theattachment of clips to metal roofs can be as reliableas screws or nails into a wooden roof. The adhesivesthat perform the best allow some flexibility in theconnection between the clip and the roof surface.Adhesives such as epoxies, which cure to a hardnonflexible form, should not be used. Acid-curingsilicones, which are not as strong and could damagethe roof, also should not be used.The adhesives listed below have been evaluated byPentair Thermal Management.Table 3: ADHESIVES FOR METAL mentivePerformanceMaterials, ing gunSpeedBonderH4800Methacrylateadhesive20 minCure48 hrTwo-part mixing45–55 min dispenserToolingCure24 hrPlexus MA300MethacrylateadhesiveTooling15 minTwo-part mixingdispenserCure16 hrPlexus MA310MethacrylateadhesiveTooling30 minTwo-part mixingdispenserCure16 hrImportant: Adhesive is not supplied by PentairThermal Management. Contact the manufacturers listed for information on local distributors. Follow manufacturer’s instructions for surface preparation -IM-H58067 03/1311

2Pre-Installation ChecksTooling time is the time between when the adhesiveis mixed and becomes unusable for installing moreclips. Cure time is the time needed to wait before theheating cable can be installed.Momentive Performance Materials, Inc. RTV 167Silicone Adhesive is a neutral-cure silicone adhesive.Contact: (800) 332-3390.SpeedBonder H3300 and H4800 are general purpose,two-component, room-temperature curing, 1:1 mixratio, methacrylate adhesive systems. Contact: (800)767-8786.Plexus MA310 and MA300 are two part methacry-late adhesives designed for structural bonding ofthermoplastic, metal, and composite assemblies.Contact: (800) 851-6692.Please consult with a roofing contractor before purchasing and installing clips with the adhesives. It isextremely important to follow the adhesive manufacturer’s instructions carefully, especially with regardto surface preparation.2.3Review the DesignHold a project coordination meeting. Review thedesign at this meeting and ensure that the cablessupplied meet the design requirements.Plan the location of all junction boxes and supplypoints. Review the installation steps in Section 3 forthe particular application as several trades may beinvolved in the system installation. Review Section4 on attachment methods. During the meeting, discuss the role of each trade and the -H58067 03/13

33.1Heating Cable InstallationHeating Cable HandlingPaying Out the CableMount the reel on a holder and place it near eitherend of the pipe run to be traced. Use a reel holderthat pays out smoothly with little tension. Avoid jerking the cable while pulling.When paying out the heating cable, AVOID: Sharp edges Excessive pulling force or jerking Kinking or crushing Walking on or running over the heating cable withequipmentConnection Kits and Accessories InstallationStart by installing connection kits and accessoriesin locations indicated on project drawings or as indicated in “Heating Cable Layout” beginning on thefollowing page.Once all clips and downspout hangers are in place,and adhesives cured if applicable, the heating cablecan be installed.Start at the end seal and work back. Be sure toleave a drip loop at connection kits so that waterwill not track down the heating cable into the component. Install heating cable using the layout shownin "Heating Cable Layout" on page 15 for yourapplication. Be sure the heating cable provides a continuouspath for water to flow off the roof. Be sure to leave drip loops where appropriate. Do not exceed maximum circuit length determined during design process using the Roof andGutter De-Icing: IceStop System Design Guide(H56070). Be sure to loop and secure heating cable at thebottom of downspouts so that the heating cable isnot exposed to mechanical damage. Install a UV-resistant cable tie wherever two heating cables are intended to stay 067 03/1313

3Heating Cable Installation Test installed heating cable for insulationresistance and continuity (see "Procedure" onpage 54).3.2Protecting the Heating CableOn many projects, there is a delay between installation of the heating cables and installation of heatingsystem connection kits. If there is any delay at all,take the following precautions to protect the heatingcables. Keep covers on junction boxes to prevent moisture from entering them. Mechanically protect the heating cables so thatthey cannot be damaged by being walked on, runover, painted, sandblasted, burned, welded, orcut.3.3Visual InspectionA visual inspection of the IceStop system should bemade after installation is complete. This inspectionwill ensure: Proper installation of the system No mechanical damage (cuts, burns, scrapes,etc.) to cable sustained prior to pour Proper heating cable spacing and depth Proper heating cable fastening Proper treatment and location of expansion andcontrols jointsFurther visual inspection of the IceStop systemis recommended following any further work performed on building that may cause damage to thesystem. Further work may include, but is not limited to, roofing, gutter or downspout maintenanceor repair, manual snow removal, installation ofmechanical, electrical or communications equipment such as antennas, receivers, or air conditioning units. Also, if roof sustains damage of any kind,visual and functional inspection of IceStop system -IM-H58067 03/13

33.4Heating Cable InstallationHeating Cable LayoutHeating cable layout depends primarily on the rooftype and roof features. The following sections showtypical layouts on standard roof types: "Sloped Roof – Standard" on page 16 "Sloped Roof – Standing Seam" on page 17 "Flat Roof" on page 20 "Sloped Roof without Gutters" on page 21 "Roof Valleys" on page 23 "Roof/Wall Intersections" on page 24 "Gutters" on page 25 "Downspouts" on page 27Important: For optimum performance, the heatingcable should be in contact with snow or ice. Installingthe heating cable under the roofing or the roofingmaterials will reduce the efficiency of the heating system. Please contact Pentair Thermal Management forassistance.Figure 3 and Figure 4 following illustrate severalimportant hFigure 3: Front view of roof with IceStop systemEN-RaychemIceStopRoofGutterDeIcing-IM-H58067 03/1315

3Heating Cable InstallationRoof12" (30 cm)Area where ice dams aremost likely to formHeating cableGutterHeatedareaEave overhangExterior wallFigure 4: Side view of roof with IceStop systemSloped Roof – StandardFor sloped roofs, ice dams may form at the roofedge. To maintain a continuous path for melt waterrunoff, route the heating cable in a zig-zag pattern as shown in Figure 5 and follow the appropriate attachment recommendations in “AttachmentMethods‚” page 29. Additional heating cablemay be needed for other gutters, downspouts, andvalleys.2'(60)cmFigure 5: Layout in a zig-zag pattern Run heating cable up the roof until it is 12 inches(30 cm) past the exterior wall into the heated area(see Figure 4). Install the heating cable on the roof in a zig-zagpattern as shown in Figure 5. Be sure that the heating cable extends all the waydown to meet with the run of heating cable in the16EN-RaychemIceStopRoofGutterDeIcing-IM-H58067 03/13

3Heating Cable Installationgutter. This will ensure that you have a continuouspath where the melted water can flow. Attach theheating cables together with UV-resistant cableties. Table 4 was used in the design process of yourproject to determine the amount of heating cablerequired for a standard sloped roof.Table 4: ICESTOP HEATING CABLE LENGTH FOR SLOPEDROOF – STANDARDFeet ofheatingcable perfoot of roofedgeMeters ofheatingcable permeter ofroof 2' (60 cm)12" (30 cm)2.5 ft2.5 m12"(30 cm)2' (60 cm)24" (60 cm)3.1 ft3.1 m24"(60 cm)2' (60 cm)36" (90 cm)4.2 ft4.2 m36"(90 cm)2' (60 cm)48"(120 cm)5.2 ft5.2 mImportant: Attachment methods are not shownin Figure 5. For attachment methods, proceed to“Attachment Methods,” page 29.other considerations Use a snow fence or snow guards (not shown) toprevent snow from sliding. Extend heating cableabove the snow fence at least 6 inches (15 cm). If there are no gutters, refer to "Heated DripEdges" on page 37, for information on how toinstall heating cable for this application. It is not always necessary to run heating cables onthe roof. If you do not experience ice dams on theroof, installing heating cables only in the guttersand downspouts may be sufficient.Sloped Roof – Standing SeamFor sloped standing-seam metal roofs, ice damsmay form at the roof edge. To maintain a continuous path for melt water to run off, route the heating cable along the seams as shown in Figure 6EN-RaychemIceStopRoofGutterDeIcing-IM-H58067 03/1317

3Heating Cable Installationand follow the attachment recommendations in“Attachment Methods‚” page 29. Additional heating cable may be needed for gutters, downspouts,and valleys and is covered in Section 3.Figure 6: Layout on a standing seam room Run the heating cable up the seam until it is 12"(30 cm) past the exterior wall and into a heatedarea, Figure 4 on page 16. Run the heating cable up one side of the seam,loop it over to the other side, and return it to thebottom of the gutter. Continue along the bottomof the gutter to the third seam and repeat theprocess (Figure 5). If the seams are more than 24"(60 cm) apart, trace every 7 03/13

3Heating Cable InstallationTable 5: ICESTOP HEATING CABLE LENGTH FOR SLOPEDROOF – STANDING SEAMFeet ofheatingcable perfoot ofroof edgeMeters ofheatingcable permeter ofroof height12"(30 cm)18"(45 cm)24" (60 cm)2.8 ft2.8 m24"(60 cm)18"(45 cm)36" (90 cm)3.6 ft3.6 m36"(90 cm)18"(45 cm)48"(120 cm)4.3 ft4.3 m12"(30 cm)24"(60 cm)24" (60 cm)2.4 ft2.4 m24"(60 cm)24"(60 cm)36" (90 cm)2.9 ft2.9 m36"(90 cm)24"(60 cm)48"(120 cm)3.6 ft3.6 m On standard systems, the length of heating cableneeded for the roof and gutter can be determinedby the formula:Heating cable length [2 x no. of seams traced x(trace height distance from roof edge to gutter bottom)] distance along the gutter/roof edgeAdditional heating cable will be needed for connection kits and downspouts.Important: Attachment methods are not shownin Figure 5. For attachment methods, proceed to“Attachment Methods,” page 29.other considerations Use a snow fence or snow guards (not shown) toprevent snow from sliding. Extend heating cableabove the snow fence at least 6 inches (15 cm). If the roofing materials continue down the fascia,contact your local Pentair Thermal Managementrepresentative or Pentair Thermal Managementdirectly for design assistance. If there are no gutters, refer to "Heated DripEdges" on page 37, for information on how toinstall heating cable for this application. It is not always necessary to run heating cables onthe roof. If you do not experience ice dams on theroof or roof damage, installing heating cables onlyin the gutters and downspouts may be 58067 03/1319

3Heating Cable InstallationFlat RoofIce dams may occur on flat roofs at the edge flashingand at drains. Flat roofs are typically pitched towarddrains and these paths often become obstructedby snow and ice. To maintain a continuous path formelt water to run off, route the heating cable asshown in Figure 7 and follow the appropriate attachment recommendations in “Attachment Methods‚”page 29. Additional heating cable may be neededfor downspouts.SlopeDrainHeating cable should bepositioned around theperimeter and in the valleysof a flat roof. The heatingcable must extend into thedrain orscupper to allow themelt water to exit the roof.JunctionboxDrip loopScupperIce can form arounddrain and at roof edgeswhere adjacent snowthaws during the dayand refreezes at night.Heating cable provides acontinuous heated path toallow melt water to run offthe roof before it refreezes.Figure 7: Layout on a flat roof20EN-RaychemIceStopRoofGutterDeIcing-IM-H58067 03/13

3Heating Cable Installation Place heating cable around perimeter. Trace valleys from perimeter to drain. Extend heating cable into internal downspouts atleast 12 inches (30 cm) into heated space. External downspouts and scuppers must betreated carefully. A path must be provided for thevalley/perimeter heating cable to the point of discharge (see Figure 15 on page 27). To avoid damage, do not walk on the heatingcable.Sloped Roof without GuttersWhen gutters are not used on a building, ice damsmay form at the roof edge. To maintain a continuouspath for melt water to run off, a drip loop or heateddrip edge may be used. Drip loops and drip edgesallow water to drip free of the roof edge.Route the heating cable as shown in Figure 8 orFigure 9 below and follow the appropriate attachment recommendations in “Attachment Methods‚”page 29. Additional heating cable may be neededfor valleys.2"–3"(5–8 cm)Figure 8: Layout for heated drip loopsEN-RaychemIceStopRoofGutterDeIcing-IM-H58067 03/1321

3Heating Cable InstallationIceStopheatingcableFigure 9: Layout for heated drip edgeImportant: Attachment methods are not shown inthe above illustrations. For attachment methods, proceed to “Attachment Methods,” page 29.other considerations Use a snow fence or snow guards to prevent snowfrom sliding (not shown). Extend heating cableabove the snow fence a minimum of 6 inches(15 cm). Ice will build up on the surfaces below the driploop or drip edge if gutters are not used. Ice may also build up on the vertical surfaces ifthere isn’t a sufficient overhang or if there is astrong wind. Use of a gutter system will preventthis ice 8067 03/13

3Heating Cable InstallationRoof ValleysIce dams may form at the valley on a roof wheretwo different slopes meet. To maintain a continuouspath for melt water, run the heating cable up anddown the valley as shown in Figure 10 and followthe appropriate attachment recommendations in“Attachment Methods‚” page 29. Additional heating cable may be needed for the roof surface, gutters, and downspouts.1/32/3Figure 10: Layout for a roof valley Trace two-thirds of the way up each valley witha double run of heating cable (loop up and backonce). The heating cable must extend into the gutter. Ifyou don’t have gutters, the heating cable shouldextend over the edge 2 to 3 inches (5 to 8 cm) toform a drip loop. For attachment methods, proceed to “AttachmentMethods‚” page 29.EN-RaychemIceStopRoofGutterDeIcing-IM-H58067 03/1323

3Heating Cable InstallationRoof/Wall IntersectionsRoof/wall intersections can be treated in the samemanner as valleys. Snow has a tendency to collect atthis interface. Providing a loop of heating cable twothirds of the way up the slope will provide a path forthe extra melt water in this area to escape.1/32/32"–3"4"–6"Figure 11: Layout for a roof/wall intersection Extend a loop of heating cable two-thirds of theway up the slope adjacent to the wall. Position the closest heating cable approximately 2to 3 inches (5 to 8 cm) from the wall. Position thesecond heating cable 4 to 6 inches (10 to 16 cm)from the 67 03/13

3Heating Cable InstallationGuttersIce may accumulate in gutters and at the roof edge.To maintain a continuous path for melt water to runoff, route the heating cable as shown in Figure 12below. Additional heating cable may be needed forthe roof surface, downspouts, and valleys.Figure 12: Layout in standard gutters up to 6" (16 cm)wide Use one run of heating cable in the gutter. No attachment to gutter is normally required. Ifattachment is desired, use a roof clip such as aRaychem GMK‑RC clip. Continue heating cable down the inside of thedownspout. See "Downspouts" on page 27, formore H58067 03/1325

3Heating Cable InstallationIn wide gutters, snow and ice can bridge over thetunnel created by a single heating cable and preventmelt water from getting into the gutter and downspouts. To maintain a continuous path for melt waterto run off, run the heating cable in the gutter asshown in Figure 13 below and follow the appropriate attachment recommendations in “AttachmentMethods‚” page 29. Additional heating cable maybe needed for the roof surface, downspouts, andvalleys.GM-RAKE6" (15 cm) spacingmaximumGMK-RCFigure 13: Layout in wide gutters 6" to 12" wide26EN-RaychemIceStopRoofGutterDeIcing-IM-H58067 03/13

3Heating Cable InstallationDownspoutsIce may form in downspouts and prevent melt waterfrom escaping from the roof. To maintain a continuous path for melt water to run off, run the heatingcable inside the downspout to the end as shown inFigure 14 and Figure 15 below. Follow the appropriate attachment recommendations in “AttachmentMethods‚” page 29. Additional heating cable maybe needed for the roof surface, gutters, and valleys.Figure 14: Heating cable at top of downspout12"Drain removes melt waterbelow the frost line.Accumulated icecan be removed.Accumulated icemay block drains.Figure 15: Heating cable at bottom of downspout If the downspout ends underground, the heatingcable should extend into a heated area or belowthe frost line. For low-water-flow situations, teeing the heatingcable so that a single run goes down the downspout is usually sufficient. For high-water-flowsituations, where ambient temperatures often fallbelow –10 F (–23 C), or where it isn’t 8067 03/1327

3Heating Cable Installationto tee the heating cable, use two runs—by runningthe heating cable down to the bottom and thenback to the top. Leave drip loops below the downspout at bottom. If a single run of heating cable is used, the endseal should be looped back up at least 12 inches(30 cm) inside the downspout. If the downspout ends near the ground, water willrefreeze on the ground and build up around thedownspout, eventually blocking the opening.other considerationsTo prevent mechanical damage, do not leave the endseal exposed at the end of the H58067 03/13

44.1Attachment MethodsOverviewHeating cable attachment depends primarily uponthe roof type. The following table shows the recommended attachment methods for typical roof materials and roof areas.Table 6: ATTACHMENT METHODS FOR TYPICAL ROOFSRoof materialRecommendedattachment methodAlternateattachment methodShake/shingle"MechanicalAttachment" onpage 30Rubber/membrane"Belt Loop Approach" "Adhesiveon page 33Attachment" onpage 31Metal"AdhesiveAttachment" onpage 31Wood"MechanicalAttachment" onpage 30OtherContact Pentair Thermal Management forassistanceAreaAttachment methodGuttersRecommend using hanger clips gluedto gutter if possible for security (seepage 35)DownspoutsDownspout hangers (page 3

For the names of manufacturers of snow guards or snow fences, contact your Pentair Thermal Management representative, or contact Pentair Thermal Management directly at (800) 545-6258. Melting snow on a roof and/or reduction of snow load—IceStop is designed to remove melt water, not accumulated snow.

Related Documents:

2. APS-3C/APS-4C snow/icing melting controller OR Raychem SMPG1 control panel OR Raychem SMPG3 control panel OR Raychem ACS-30 with snow/ice melting controller [Select one] 3. Raychem ProtoNode multi-protocol device server 2.2 PRODUCTS, GENERAL A. Single Source Responsibility: Furnish heat tracing system for snow melting from a single .

PYROTENAX* PyroFLX Connector 2000 PETROTRACE** Downhole Heating RAYCHEM Power-Limit-ing Technology (VPL)) 1957 CHEMELEX Cut-to-Length Heater 1982 MONITRACE GF and Current Monitoring 1971 RAYCHEM Self-Regulating Heating Cable 1983 TRACER Turnkey Solutions 1986 Offshore De-Icing 2011 2014 RAYCHEM NGC-40 Control & Monitoring New RAYCHEM XTV/KTV .

order or contract is prohibited unless agreed to in writing as condition of sale by Raychem RPG Private Limited. Raychem RPG Private Limited reserves the right to alter any product or service. Disclaimer Offices Head Office: Raychem RPG (P) Ltd., RPG House, 463, Dr. Annie Besant Roa

Products from Tyco Thermal Controls LLC (Raychem) UL File KOBQ.E74811, De-icing and Snow-melting Equipment CSA Class 2872-01, File 021133_C_000 HEATERS-Cable and Cable Sets Raychem IceStop Roof & Gutter De-Icing Systems GM-1X Heating cables (120VAC, 10 watts per foot) GM-2X Heating cables (240VAC, 12 watts per foot and 277VAC, 12 watts per .

For the names of manufacturers of snow guards or snow fences, contact your Tyco Thermal Controls representative, or contact Tyco Thermal Controls directly at (800) 545-6258. Melting snow on a roof and/or reduction of snow load—IceStop is designed to remove melt water, not accumulated snow.

Raychem tubing bundles are available in a wide range of tubing and heater options (see bundle ordering options on page 4). Trace-heating components Raychem tubing bundles use the full range of standard XTV and BTV power connection and end seal kits. Bundle accessories Raychem bundle accessories includ

Stress control patch The Raychem TFT stress control patch is a recently formulated electrical stress control compound, which is based on long experience with Raychem ceramic semi-conductor technology (ZnO). The ZnO-based stress control patch is not integrated in the TF

commitment awards will be informed by this process. 7. 1.8 Where Consultants work for more than one NHS employer, a lead employer will be designated and an integrated single job plan agreed. 1.9 Where a Consultant disagrees with a job planning decision, there will be an initial referral to the Medical Director (or an appropriate other person if the Medical Director is one of the parties to the .