Service Facts GAM5-SF-1D Convertible Air Handlers

3y ago
28 Views
2 Downloads
2.16 MB
28 Pages
Last View : 1m ago
Last Download : 3m ago
Upload by : Mollie Blount
Transcription

Service FactsGAM5-SF-1DConvertible Air HandlersModels: Series 5 Air Handlers 1-1/2 to 5 A*For use with BAYEA series heaters ONLYWARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICINGIMPORTANT --- This document contains a wiring diagram and service information. This is customer property and is to remain with thisunit. Please return to service information pack upon completion of work. ! WARNINGSAFETY HAZARD! This information is intended for useby individuals possessing adequate backgrounds of electrical andmechanical experience. Any attempt to repair a central air conditioning product may result in personal injury and/or property damage.The manufacture or seller cannot be responsible for the interpretation of this information, nor can it assume any liability in connectionwith its use. ! WARNINGLIVE ELECTRICAL COMPONENTS! During instal-lation, testing, servicing, and troubleshooting of this product, it maybe necessary to work with live electrical components. Failure to follow all electrical safety precautions when exposed to live electricalcomponents could result in death or serious injury.Table of Contents ! WARNINGPRESSURIZED REFRIGERANT! SYSTEM CONTAINSOIL AND REFRIGERANT UNDER HIGH PRESSURE. RECOVERREFRIGERANT TO RELIEVE PRESSURE BEFORE OPENING THESYSTEM.DO NOT USE NON-APPROVED REFRIGERANTS OR REFRIGERANTSUBSTITUTES OR REFRIGERANT ADDITIVES.Note: This unit is certified to UL 1995.The interior cabinet wall meets the following:- UL94-5VA Flame Class Listed- UL723 Steiner Tunnel Listed for 25/50 Flame/Smoke- UL746C Listed for Exposure to Ultraviolet Light,Water Exposure and ImmersionProduct Specifications. 2Airflow Performance. 3Heater Attribute Data. 10Wiring Diagram. 13Sequence of Operation. 14Configuration Dip Switch Settings. 16EVC Thermal Resistance and Voltage Table. 17EEV Test Procedures. 18Subcooling Adjustment. 19Troubleshooting. 20NOTICE: Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change design and specifications withoutnotice. 2012 Trane

PRODUCT SPECIFICATIONSGAM5A0A18M11SAMODEL208-230/1/60RATED VOLTS/PH/HZ.See O.D. SpecificationsRATINGS 1Plate FinINDOOR COIL — Type3 - 14Rows — F.P.I.3.67Face Area (sq. ft.)3/8Tube Size (in.)EEVRefrigerant Control3/4 NPTDrain Conn. Size (in.) 2See Outline DrawingDUCT CONNECTIONSCentrifugalINDOOR FAN — Type11 X 8Diameter-Width (In.)1No. UsedDirect - 5Drive - No. SpeedsSee Fan Performance TableCFM vs. in. w.g.1 - 1/3No. Motors — H.P.1050Motor Speed RPM208-230/1/60Volts/Ph/Hz2.8F.L. AmpsFILTERNoFilter Furnished?ThrowawayType Recommended1 - 16 X 20 - 1 in.No.-Size-ThicknessR-410AREFRIGERANTBrazedRef. Line Connections3/4Coupling or Conn. Size — in. Gas3/8Coupling or Conn. Size — in. Liq.HxWxDDIMENSIONS51-3/8 x 20-1/2 x 25-3/4Crated (In.)49-7/8 x 17-1/2 x 21-3/4UncratedWEIGHT126/120Shipping (Lbs.) / Net (Lbs.)GAM5A0A24M21SA208-230/1/60See O.D. SpecificationsPlate Fin3 - 143.673/8EEV3/4 NPTSee Outline DrawingCentrifugal11 X 81Direct - 5GAM5A0B30M21SA208-230/1/60See O.D. SpecificationsPlate Fin3 - 144.133/8EEV3/4 NPTSee Outline DrawingCentrifugal11 X 101Direct - 5GAM5A0B36M31SA208-230/1/60See O.D. SpecificationsPlate Fin3 - 145.043/8EEV3/4 NPTSee Outline DrawingCentrifugal11 X 101Direct - 5See Fan Performance TableSee Fan Performance TableSee Fan Performance Table1 - 1/31050208-230/1/602.81 - 1/31050208-230/1/602.81 - 1/21050208-230/1/604.1NoThrowaway1 - 16 X 20 - 1 in.R-410ABrazed3/43/8HxWxD51-3/8 x 20-1/2 x 25-3/449-7/8 x 17-1/2 x 21-3/4NoThrowaway1 - 20 X 20 - 1 in.R-410ABrazed3/43/8HxWxD53 x 24-1/4 x 25-3/451-1/2 x 21-1/4 x 21-3/4NoThrowaway1 - 20 X 20 - 1 in.R-410ABrazed7/83/8HxWxD57-1/4 x 24-1/4 x 25-3/455-3/4 x 21-1/4 x 21-3/4126/120140/132150/142PRODUCT SPECIFICATIONSGAM5A0C42M31SAMODEL208-230/1/60RATED VOLTS/PH/HZ.See O.D. SpecificationsRATINGS 1Plate FinINDOOR COIL — Type4 - 14Rows — F.P.I.5.04Face Area (sq. ft.)3/8Tube Size (in.)EEVRefrigerant Control3/4 NPTDrain Conn. Size (in.) 2See Outline DrawingDUCT CONNECTIONSCentrifugalINDOOR FAN — Type11 X 10Diameter-Width (In.)1No. UsedDirect - 5Drive - No. SpeedsSee Fan Performance TableCFM vs. in. w.g.1 - 1/2No. Motors — H.P.1050Motor Speed RPM208-230/1/60Volts/Ph/Hz4.1F.L. AmpsFILTERNoFilter Furnished?ThrowawayType Recommended1 - 22 X 20 - 1 in.No.-Size-ThicknessR-410AREFRIGERANTBrazedRef. Line Connections7/8Coupling or Conn. Size — in. Gas3/8Coupling or Conn. Size — in. Liq.HxWxDDIMENSIONS58-1/2 x 27-1/2 x 25-3/4Crated (In.)56-7/8 x 23-1/2 x 21-3/4UncratedWEIGHT163/153Shipping (Lbs.) / Net (Lbs.)GAM5A0C48M41SA208-230/1/60See O.D. SpecificationsPlate Fin4 - 145.963/8EEV3/4 NPTSee Outline DrawingCentrifugal11 X 101Direct - 5GAM5A0C60M51SA208-230/1/60See O.D. SpecificationsPlate Fin4 - 145.963/8EEV3/4 NPTSee Outline DrawingCentrifugal11 X 101Direct - 5See Fan Performance TableSee Fan Performance Table1 - waway1 - 22 X 20 - 1 in.R-410ABrazed7/83/8HxWxD63-1/4 x 27-1/2 x 25-3/461-3/4 x 23-1/2 x 21-3/4NoThrowaway1 - 22 X 20 - 1 in.R-410ABrazed7/83/8HxWxD63-1/4 x 27-1/2 x 25-3/461-3/4 x 23-1/2 x 21-3/4176/166180/1701 These Air Handlers are A.R.I. certified with various Split System Air Conditionersand Heat Pumps (ARI STANDARD 210/240). Refer to the Split System OutdoorUnit Product Data Guides for performance data.2 3/4" Male Plastic Pipe (Ref.: ASTM 1785-76)GAM5-SF-1D2

AIRFLOW PERFORMANCEGAM5A0A18M11SAEXTERNAL STATIC(in w.g)AIRFLOW (CFM)Speed Taps - 230 VOLTSSpeed Taps - 208 08539420--680512392--NOTES:1. Values are with wet coil and without filters.2. Contact your particular filter manufacturer for pressure drop data.3. Electric heater pressure drop is negligible and is included within the airflow data.4. Tap 1 is an continuous fan speed tap.5. † Factory SettingGAM5A0A18M11SA MINIMUM HEATER AIRFLOW CFMHeaterMinimum Air Speed TapWithout Heat PumpWith Heat PumpBAYEAAC05BK1AABAYEAAC05LG1AATap 3Tap 4BAYEAAC08BK1AABAYEAAC08LG1AATap 3Tap 4BAYEAAC10BK1AABAYEAAC10LG1AATap 3 1Tap 5 1BAYEAAC10LG3AATap 5Tap 5 2BAYEABC15BK1AA--BAYEABC20BK1AA--1 Heater not qualified for downflow installations2 Approved for 240 V onlyNote: Heating and cooling speeds are the same, factoryset at Speed Tap #4.Note: A “G” only signal from the comfort control will runthe blower at a lower speed, factory set at Speed Tap #1.See the Sequence of Operation for additional information.3GAM5-SF-1D

AIRFLOW PERFORMANCEGAM5A0A24M21SAEXTERNAL STATIC(in w.g)AIRFLOW (CFM)Speed Taps - 230 VOLTSSpeed Taps - 208 08539460407-680512432--NOTES:1. Values are with wet coil and without filters.2. Contact your particular filter manufacturer for pressure drop data.3. Electric heater pressure drop is negligible and is included within the airflow data.4. Tap 1 is an continuous fan speed tap.5. † Factory SettingGAM5A0A24M21SA MINIMUM HEATER AIRFLOW CFMHeaterMinimum Air Speed TapWithout HPWith HPBAYEAAC05BK1AABAYEAAC05LG1AATap 3Tap 4BAYEAAC08BK1AABAYEAAC08LG1AATap 3Tap 4BAYEAAC10BK1AABAYEAAC10LG1AATap 3 1Tap 5 1BAYEAAC10LG3AATap 5Tap 5 2BAYEABC15BK1AA--BAYEABC20BK1AA--1 Heater not qualified for downflow installations2 Approved for 240 V onlyNote: Heating and cooling speeds are the same, factoryset at Speed Tap #4.Note: A “G” only signal from the comfort control will run theblower at a lower speed, factory set at Speed Tap #1. Seethe Sequence of Operation for additional information.GAM5-SF-1D4

AIRFLOW PERFORMANCEGAM5A0B30M21SAEXTERNAL STATIC(in w.g)AIRFLOW (CFM)Speed Taps - 230 VOLTSSpeed Taps - 208 621404--0.9771587376--743560348--NOTES:1. Values are with wet coil and without filters.2. Contact your particular filter manufacturer for pressure drop data.3. Electric heater pressure drop is negligible and is included within the airflow data.4. Tap 1 is an continuous fan speed tap.5. † Factory SettingGAM5A0B30M21SA MINIMUM HEATER AIRFLOW CFMHeaterMinimum Air Speed TapWithout HPWith HPBAYEAAC05BK1AABAYEAAC05LG1AATap 2Tap 3BAYEAAC08BK1AABAYEAAC08LG1AATap 3Tap 4BAYEAAC10BK1AABAYEAAC10LG1AATap 3Tap 4BAYEAAC10LG3AATap 3 1Tap 4 1BAYEABC15BK1AATap 4Tap 5BAYEABC15LG3AATap 4Tap 5BAYEABC20BK1AA--BAYEACC25BK1AA--1 208 V not approved for upflow installationsNote: Heating and cooling speeds are the same, factoryset at Speed Tap #4.Note: A “G” only signal from the comfort control will runthe blower at a lower speed, factory set at Speed Tap #1.See the Sequence of Operation for additional information.5GAM5-SF-1D

AIRFLOW PERFORMANCEGAM5A0B36M31SAEXTERNAL STATIC(in w.g)AIRFLOW (CFM)Speed Taps - 230 VOLTSSpeed Taps - 208 9633409-936861605--NOTES:1. Values are with wet coil and without filters.2. Contact your particular filter manufacturer for pressure drop data.3. Electric heater pressure drop is negligible and is included within the airflow data.4. Tap 1 is an continuous fan speed tap.5. † Factory SettingGAM5A0B36M31SA MINIMUM HEATER AIRFLOW CFMHeaterMinimum Air Speed TapWithout HPWith HPBAYEAAC05BK1AABAYEAAC05LG1AATap 2Tap 3BAYEAAC08BK1AABAYEAAC08LG1AATap 3Tap 4BAYEAAC10BK1AABAYEAAC10LG1AATap 4Tap 5BAYEAAC10LG3AATap 4Tap 5BAYEABC15BK1AATap 4Tap 5BAYEABC15LG3AATap 4Tap 5BAYEABC20BK1AA--BAYEACC25BK1AA--Note: Heating and cooling speeds are the same, factoryset at Speed Tap #4.Note: A “G” only signal from the comfort control will runthe blower at a lower speed, factory set at Speed Tap #1.See the Sequence of Operation for additional information.GAM5-SF-1D6

AIRFLOW PERFORMANCEGAM5A0C42M31SAEXTERNAL STATIC(in w.g)AIRFLOW (CFM)Speed Taps - 230 VOLTSSpeed Taps - 208 9-NOTES:1. Values are with wet coil and without filters.2. Contact your particular filter manufacturer for pressure drop data.3. Electric heater pressure drop is negligible and is included within the airflow data.4. Tap 1 is an continuous fan speed tap.5. † Factory SettingGAM5A0C42M31SA MINIMUM HEATER AIRFLOW CFMHeaterMinimum Air Speed TapWithout HPWith HPBAYEAAC05BK1AABAYEAAC05LG1AATap 2Tap 3BAYEAAC08BK1AABAYEAAC08LG1AATap 2Tap 3BAYEAAC10BK1AABAYEAAC10LG1AATap 2Tap 3BAYEAAC10LG3AATap 2Tap 3BAYEABC15BK1AATap 3Tap 4BAYEABC15LG3AATap 3Tap 4BAYEABC20BK1AA--BAYEACC25BK1AA--Note: Heating and cooling speeds are the same, factoryset at Speed Tap #4.Note: A “G” only signal from the comfort control will runthe blower at a lower speed, factory set at Speed Tap #1.See the Sequence of Operation for additional information.7GAM5-SF-1D

AIRFLOW PERFORMANCEGAM5A0C48M41SAEXTERNAL STATIC(in w.g)AIRFLOW (CFM)Speed Taps - 230 VOLTSSpeed Taps - 208 1513136212761156-NOTES:1. Values are with wet coil and without filters.2. Contact your particular filter manufacturer for pressure drop data.3. Electric heater pressure drop is negligible and is included within the airflow data.4. Tap 1 is an continuous fan speed tap.5. † Factory SettingGAM5A0C48M41SA MINIMUM HEATER AIRFLOW CFMHeaterMinimum Air Speed TapWithout HPWith HPBAYEAAC05BK1AABAYEAAC05LG1AATap 2Tap 3BAYEAAC08BK1AABAYEAAC08LG1AATap 2Tap 3BAYEAAC10BK1AA

1 These Air Handlers are A.R.I. certified with various Split System Air Conditioners and Heat Pumps (ARI STANDARD 210/240). Refer to the Split System Outdoor Unit Product Data Guides for performance data. 2 3/4" Male Plastic Pipe (Ref.: ASTM 1785-76) PRODUCT SPECIFICATIONS MODEL RATED VOLTS/PH/HZ. RATINGS 1 INDOOR COIL — Type Rows — F.P.I .

Related Documents:

The following Fact Fluency Card labels are included in this pack: 1. Plus One Facts 2. Plus Two Facts 3. Plus Three Facts 4. Minus One Facts 5. Minus Two Facts 6. Minus Three Facts 7. Facts of Five 8. Doubles Facts (Addition) 9. Doubles Facts (Subtraction) 10. Near Doubles Facts (e.g. 6 7 6 6 1 12 1 13) 11. Facts of Ten: Addition 12.

doubles-plus-one facts, doubles-plus-two facts, plus-ten facts, plus-nine facts, and then any remaining facts. For multiplication, the suggested sequence is the times-zero principle, times-one principle, times-two and two-times facts, times-five and five-times facts, times-nine and nine-times facts, perfect squares, and then any remaining facts .

Math Bee Practice . 1st Round Mixed Multiplication and Division Facts 2 seconds. Multiplication Facts 6 x 6 _ Multiplication Facts 6 x 6 36. Multiplication Facts 32 8 _ Multiplication Facts 32 8 4. Multiplication Facts 7 x 6 _ Multiplication Facts 7 x 6 42. Multiplication Facts 56 7 _

Practice basic subtraction facts. 11. Multiplication Memory Practice basic multiplication facts. 12. Division Memory Practice basic division facts. 13. Make Your Own Memory Game 14. Addition Bingo Practice basic addition facts to 10. 15. Subtraction Bingo Practice basic subtraction facts. 16.

The levels view: Political and moral theories are concerned with different normative facts, which belong to different ontological levels. The normative facts of political theory belong to a higher—more coarse-grained—ontological level than those of moral theory. Normative political facts are “multiply realizable” by moral facts, so

multiplication facts. Third graders are required to know their multiplication facts up to the 12. Once you’ve learned these, or if you already know them, you should use this time to learn, practice, and review multiplication facts up to 20. You will be logging the time spent practicing your math facts on a math facts

Long-Chain Fatty Acid Oxidation Disorders 41 Genetic counseling, newborn screening and patient support 9 Fatty acid metabolism 18 Epidemiology and genetics 24 Clinical presentation 32 Diagnosis Fill the gap in your knowledge, fast! with Fast Facts - the ultimate medical handbook series FAST FACTS Long-Chain Fatty Acid Oxidation Disorders

Siklus akuntansi pendidikan merupakan sistematika pencatatan transaksi keuangan, peringkasan dan pelaporan keuangan. Menurut Bastian (2007) siklus akuntansi pendidikan dapat dikelompokkan menjadi 3 tahap, yaitu: 1. Tahap Pencatatan a. Mengidentifikasi dan mengukur bukti transaksi serta bukti pencatatan. b. Mengelola dan mencatat bukti transaksi seperti kwitansi, cek, bilyet giro, nota kontan .