5000 SERIES POWER SUPPLY/CHARGERS INSTALLATION GUIDE

2y ago
30 Views
2 Downloads
774.28 KB
16 Pages
Last View : 3m ago
Last Download : 3m ago
Upload by : Joao Adcock
Transcription

5000 SERIESPOWER SUPPLY/CHARGERSINSTALLATION GUIDEMODEL# 5025 (1 AMP @ 12VDC OR 24VDC)MODEL# 5500 (3 AMP @ 12VDC OR 2 AMPS @ 24VDC)MODEL# 5600-12 (10 AMPS @ 12VDC)MODEL# 5600-24 (5 AMPS @ 24VDC)IMPORTANT SAFETY INSTRUCTIONSTHIS MANUAL CONTAINS IMPORTANT SAFETY INSTRUCTIONS FORPOWER SUPPLY/BATTERY CHARGER MODELS:5025, 5500, 5600-12, 5600-24BEFORE USING THE BATTERY CHARGER, READ ALL INSTRUCTIONS ANDCAUTIONARY MARKINGS ON THE BATTERY CHARGER,BATTERY/BATTERIES AND PRODUCTS USING BATTERIESWWW.DYNALOCK.COM705 EMMETT STREETBRISTOL, CT 06011-2728PHONE: (860) 582-4761 FAX: (860) 585-0338REV. 8/30/2010

OVERVIEWThese access control power supply/chargers are specifically designed for use with access controlsystems and accessories. These units convert a 115VAC/50-60Hz input into two outputs(see options). Outputs will route power to a variety of access control hardware devices includingMag Locks, Electric Strikes, Magnetic Door Holders, ect. These outputs will operate inboth Fail-Safe and Fail-Secure modes.5000 SERIES POWER SUPPLY CONFIGURATION REFERENCE CHARTUL LISTINGS12VDC24VDC115VAC/60HZ INPUT INPUT FUSEOUTPUTSAGENCY LISTINGS& FILE NUMBERSRATINGCURRENT OUTPUT CURRENT OUTPUTCURRENT DRAW3S845025 (12/24VDC FIELD SELECTABLE)RESETTABLE.45 AMPS1 AMP21 AMPFile# E1836655500 (12/24VDC FIELD SELECTABLE)2 AMPS3 AMPS1 AMP1 AMP2DYNALOCK MODEL NUMBERMEA5600 (12 OR 24VDC FIXED)10 AMPS5 AMPS22 AMPS4 AMPSApprovedNYCC Dept.Of Buildings# 23-92-EINSTALLATION INSTRUCTIONSWiring methods shall be in accordance with the National Electric Code/NFPA 72/ANSI,and with all local codes and authorities having jurisdiction. Product is intended for indoor use only.1) Mount unit in desired location. mark and pre-drill holes to line up with the top two keyholes in theenclosure. Install two upper fasteners and screws with screw heads protruding. Place the enclosuresupper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes.Remove the enclosure and drill the lower two holes. Place the enclosures upper key holes back overthe two upper screws. Install the two lower screws and make sure to tighten all screws(Enclosure Dimensions, pg 12). Secure the enclosure to earth ground.2) Set the output voltage: 5025, 5500 set the desired output voltage by setting the voltage selector tothe appropriate position on the power supply main board.Note: The 5600 is not field selectable and the output voltage must be specified when ordering.3) Secure green/yellow stripe lead to earth ground. Connect AC power (115VAC 60Hz) to terminalsmarked (H or L, G, N) on the power supply board. Use 18AWG wire or larger for all powerconnections (Battery, DC output, AC input).4) Measure output voltage before connecting any devices. This will help prevent damage fromoccurring. Keep power limited wiring separate from non-power limited wiring(115VAC/60Hz Input, Battery Wires). Minimum .25” spacing must be provided.5) Connect Fail-Safe or Fail-Secure type locking hardware (e.g. Door strikes, Mag Locks and ElectricDeadbolts) positive leads to the terminals marked ( ) DC OUTPUT and the negative leads to theterminals marked (-) DC OUTPUT.PAGE 2

INSTALLATION INSTRUCTIONS (CONT’D)6) For access control applications, batteries are optional. When batteries are not used, a loss ofAC voltage will result in the loss of output voltage. Batteries must be sealed lead acid rechargeabletypes if used. Connect one 12VDC battery to terminals marked (Battery) on the power supply boardfor 12VDC operations. Use two 12VDC batteries connected in series for 24VDC operations. Batteryleads are included when batteries are ordered with the power supply.7) Please insure enclosure cover is secured closed with the provided screw or the key lock option.( ) (-)-12VDC RECHARGEABLE BATTERY(OPTIONAL) -12VDC RECHARGEABLE BATTERY(OPTIONAL)Units should be tested at least once a year for proper operation as follows:Output Voltage Test: Under a normal load condition, the DC output voltage should be checked for aproper voltage level.Battery Test: Under normal load conditions, check that the battery is fully charged, check specifiedvoltage at the battery terminals and the board terminals to insure that there is no break in the batteryconnection wires.Expected battery life is 5 years, however, it is recommended to change the batteries within two yearsor less if necessary.PAGE 3

MODELS 5600-12 / 5600-24POWER SUPPLY/CHARGERSDynaLockMade in the USAMODEL 5600-12MODEL 5600-24INPUT POWER:115 VAC 50-60Hz, 2.0 Amp115 VAC 50-60Hz, 2.0 AmpOUTPUT POWER:12 VDC Nominal (13.8 VDC) @ 10 Amp24 VDC Nominal (27.6 VDC) @ 5 AmpPRIMARY FUSE:4A, 250V Slow-Blow4A, 250V Slow-BlowOUTPUT FUSE:(2) 12A, 250V Slow Blow(2) 6A, 250V Slow BlowNote: Refer to 5000 Series Power Supply Installation Manual115 VACEarth GroundCONTROLLER BONDING WIRE STRAPPower MainsNon-PowerLimitedLine/NeutralGreen/Yellow Stripe LeadLine/HotCHASSIS GROUND WIREGreen/Yellow Stripe LeadGreenGround BondScrewCOVERBONDINGWIRE STRAPGreen/Yellow StripeLeadAC OUT CONTROLLERGRNGND1GND2NEUT3LINEBLKLINEDC IN FROM CONTROLLERRED( )WHTNEUTRED( )BLK(-)BLK(-)POWER CTSUPPLY BEFORECHANGINGFUSES3 4 OUTPUTSTATUSCONTROLLERGROUND INPUTWIRECUT JUMPERWHEN RELAYIS INSTALLEDF3SEEMANUAL --BATTERY INPUTREMOTE CONTROL INPUTCAUTION: De-energize unit prior toservicing. For continued protectionagainst electric shock and fire hazard,replace fuses with same type and rating(See chart above). Do not expose to rainor moisture.Green/Yellow StripeLeadFAC REMOTECONTROL INPUTCAUTION: Risk of electric shock. Hazardouslive parts inside this power supply are energizedfrom the battery supply even when the input poweris disconnected.Battery Connections (Non-Power Limited)CAUTION: This cabinet (compartment) containsvented wet cell batteries. Ventilation of the room inaccordance with the rules of the Canadian ElectricalCode, Part I, is required.12 VDC Rechargeable Battery(Optional)CAUTION: Charge only sealed lead-acid typerechargeable batteries. Other types of batteriesmay burst causing personal injury and damage.12 VDC Rechargeable Battery(Optional)CAUTION: When power supply board is set for12 VDC use only (1) 12 VDC stand-by battery.KEEP POWER LIMITED WIRING SEPARATE FROM NON-POWER LIMITED.USE MINIMUM O.25” SPACING.NOTE: THIS PRODUCT IS INTENDED TO BE USED IN A GENERAL ENVIRONMENTDynaLock Corp. is not responsible for any typographical errors.DynaLock Corp.705 Emmett StreetBristol, CT 060101-877-DYNALOCKWebsite: www.dynalock.comE-mail: info@dynalock.comPAGE 4

MODEL 5500POWER SUPPLY/CHARGERDynaLockMade in the USAUL Listed General Purpose Power SupplyMODEL 5500INPUT POWER:115 VAC 50-60Hz, 1.0 AmpOUTPUT POWER:12 VDC Nominal (13.8 VDC) @ 3 Amp or 24 VDC Nominal (27.6 VDC) @ 2 AmpPRIMARY FUSE:1A, 250V Slow-BlowOUTPUT FUSE:(2) 5A, 250V Slow BlowNote: Refer to 5000 Series Power Supply Installation Manual115 VACEarth GroundCONTROLLER BONDING WIRE STRAPPower MainsNon-PowerLimitedLine/HotGreen/Yellow Stripe LeadLine/NeutralCHASSIS GROUND WIREGreen/Yellow Stripe LeadGreen Ground Bond ScrewCOVERBONDINGWIRE STRAPGreen/Yellow StripeLeadDYNALOCK CORP.PN500180PSIOBORDLINE FUSE24VPOWER OUTPUT12V131LINE2122NEUT3GNDLINE INPUT110 VAC 60 HZ34F2DC OUTPUTTO DEVICES(Power Limited)F3BATTERY INPUTCONTROLLERGROUND INPUTWIREGreen/Yellow StripeLeadCAUTION: Risk of electric shock. Hazardouslive parts inside this power supply are energizedfrom the battery supply even when the input poweris disconnected.CAUTION: De-energize unit prior toservicing. For continued protectionagainst electric shock and fire hazard,replace fuses with same type and rating(See chart above). Do not expose to rainor moisture.Battery Connections (Non-Power Limited)CAUTION: This cabinet (compartment) containsvented wet cell batteries. Ventilation of the room inaccordance with the rules of the Canadian ElectricalCode, Part I, is required.12 VDC Rechargeable Battery(Optional)CAUTION: Charge only sealed lead-acid typerechargeable batteries. Other types of batteriesmay burst causing personal injury and damage.12 VDC Rechargeable Battery(Optional)CAUTION: When power supply board is set for12 VDC use only (1) 12 VDC stand-by battery.KEEP POWER LIMITED WIRING SEPARATE FROM NON-POWER LIMITED.USE MINIMUM O.25” SPACING.NOTE: THIS PRODUCT IS INTENDED TO BE USED IN A GENERAL ENVIRONMENTDynaLock Corp. is not responsible for any typographical errors.PAGE 5

MODEL 5025POWER SUPPLY/CHARGERDynaLockMade in the USAUL Listed General Purpose Power SupplyMODEL 5025INPUT POWER:115 VAC 50-60Hz, 0.45 AmpOUTPUT POWER:12 VDC Nominal (13.8 VDC) @ 1 Amp or 24 VDC Nominal (27.6 VDC) @ 1 AmpPRIMARY FUSE:Resettable PTCCNote: Refer to 5000 Series Power Supply Installation Manual115 VACEarth GroundCONTROLLER BONDING WIRE STRAPPower MainsNon-PowerLimitedLine/HotGreen/Yellow Stripe LeadLine/NeutralCHASSIS GROUND WIREGreen/Yellow Stripe LeadDC OUTPUTSHUT DOWNTB4NJP1GDC OUTPUTTO DEVICES(Power Limited)H12 VOLTGreen/Yellow StripeLeadTB3F124 VOLTCOVERBONDINGWIRE STRAPTB2TB1CONTROLLERGROUND INPUTWIREGreen/Yellow StripeLeadCAUTION: De-energize unit prior toservicing. The primary fuse is resettable.Reset by correcting the overload conditionand de-energizing the unit for at least twominutes. Do not expose to rain or moisture.CAUTION: Risk of electric shock. Hazardouslive parts inside this power supply are energizedfrom the battery supply even when the input poweris disconnected.Battery Connections (Non-Power Limited)CAUTION: This cabinet (compartment) containsvented wet cell batteries. Ventilation of the room inaccordance with the rules of the Canadian ElectricalCode, Part I, is required.12 VDC Rechargeable Battery(Optional)CAUTION: Charge only sealed lead-acid typerechargeable batteries. Other types of batteriesmay burst causing personal injury and damage.12 VDC Rechargeable Battery(Optional)CAUTION: When power supply board is set for12 VDC use only (1) 12 VDC stand-by battery.KEEP POWER LIMITED WIRING SEPARATE FROM NON-POWER LIMITED.USE MINIMUM O.25” SPACING.NOTE: THIS PRODUCT IS INTENDED TO BE USED IN A GENERAL ENVIRONMENTDynaLock Corp. is not responsible for any typographical errors.PAGE 6

5500/5600 OPTIONSFAC Option (Remote Control)Kills all voltage outputs when interfacedwith remote dry contact.REMOTE CONTROL MODULEREMOTE CONTROL MODULENORMALNORMALMANUAL RESETMANUAL RESET1 2 31 2 31 2 31 2 356005500DB-5 & DB-10 Option (Distribution Board)Two size distribution (5 or 10 position)are available to provide individually fusedoutput terminals for each lock zone.DC INPUT FROMPOWER SUPPLY MAIN BOARDCONNECTOR FORCM/CMTD MODULEOUTPUT JUMPERSRESETTABLE FUSE(SEE NOTE BELOW)WITHOUT CONTROL MODULE OPTION(FACTORY SETTING)WITH CONTROL MODULEOPTIONNOTE: RESETTING IS DONE BY FIRST CORRECTING THEOVERLOAD THEN DISCONNECTING THE LOAD OR TURNINGOFF THE LINE VOLTAGE FOR TWO MINUTESPAGE 7

5500/5600 OPTIONSCM Option (Control Module)Accepts access/egress controldry contact input. ProvidesSPDT relay output.ABAACCESS CONTROL INPUT (DRY CONTACTS ONLY)BSPDT DRY CONTACTS RATED AT 2A @ 24VCMTD Option (Control Module with Time Delay)same as CM Option with Relock Time DelayADJUSTABLE FOR1-80 SECONDS DELAYON RE-LOCK TIMEATS Option (Anti-Tamper switch)CONTACT HELD OPENWITH ENCLOSURE COVER CLOSEDCONTACT CLOSEDWITH ENCLOSURE COVER OPENWHITEWHITEWHITEWHITENOTE: ATS switch contacts rated .25A @ 24VPAGE 8

5500/5600 OPTIONSILB Option (Interlock Logic Board)Provides Four DPDT Relay OutputsNote: Separate ILB User Manualshows typical wiring diagrams.COMMON NEGATIVE TERMINALPOSITIVE INPUTS TO ENERGIZE RELAY COILSPAGE 9

INSTALLATION INFORMATION5600 LOCK CAPACITYSINGLEDOUBLEVOLTAGE (FULL SIZE) (FULL SIZE) SINGLE DOUBLE12VDC24VDC181899181899SINGLEDEADBOLTDELAY EGRESS101189CURRENT DRAW UP TO ½ AMPVOLTAGE20 AWG18AWG16AWG 50FT12AWG10AWG400FT900FT625FT1375FT5500 LOCK CAPACITYSINGLEDOUBLEVOLTAGE (FULL SIZE) (FULL SIZE) SINGLE DOUBLE12VDC24VDC68346834SINGLEDEADBOLTDELAY EGRESS3334CURRENT DRAW UP TO ½ AMPVOLTAGE20 AWG18AWG16AWG 00FT400FT750FT750FT1500FT250FT500FTThese charts indicates the minimum recommended wire size, local codes prevail.PAGE 10

TYPICAL 5500/5600 APPLICATION120 VAC50/60 HZINPUTFAC Remote ControlCEADBANORMALLY CLOSED DRY CONTACT FROM THE FIRE ALARM CONTROL PANEL (FROM OTHERS)BFAIL SAFE LOCKING DEVICECFAIL SECURE LOCKING DEVICEDNORMALLY CLOSED ACCESS/EGRESS CONTROLSENORMALLY OPEN ACCESS/EGRESS CONTROLSPAGE 11

5600 TROUBLESHOOTINGAC OUT TO SWITCHERDC IN FROM SWITCHER(12V OR 24V)ACCESS CONTROLLEGAL RELEASENO OUTPUT POWER AT BNO OUTPUT POWER AT A1CHECK INPUT LINE FUSE6CHECK JUMPER SETTING AY CM/CMTD MODULE (IF APPLICABLE)2CHECK LINE FUSE7CHECK JUMPER SETTING AT DB-5/DB-10 CARD3CHECK FOR 12 OR 24VDC FROM SWITCHER8CHECK FOR PROPER ACCESS SWITCH CONTACT STATUS4CHECK FOR 12 OR 24VDC FROM SWITCHER9CHECK LOAD AND EXTERNAL WIRING FOR SHORT CONDITION5aCHECK F2 AND F3 OUTPUT FUSESCHECK THAT FAC MODULE IS SEATEDPROPERLY (IF APPLICABLE)TERMINALS 1 AND 2 MUST BE JUMPEDTOGETHER IF UNIT HAS FAC MODULE105b5cRESET POWER SUPPLY (WITH NO LOAD) BYDISCONNECTING INPUT POWER AT AC LINE IN FOR2 MINUTESPAGE 12

5500 TROUBLESHOOTINGACCESS CONTROLLEGAL RELEASEELECTROMAGNETICLOCKNO OUTPUT POWER AT A1 CHECK INPUT LINE POWER2 CHECK LINE FUSE3 CHECK F2 & F3 OUTPUT FUSES4 CHECK FAC (IF APPLICABLE) TERMINALS, 1 AND 2 MUST BE WIRED TO N/C CONTACT5025 TROUBLESHOOTINGAPRIMARY RESETTABLEFUSETB3DC OUTPUTF12HNG12 V OLTJP124 VOLTTB23TB1BATTERYLINE INPUT110 VAC 60 HZSHUT DOWNTB41CONNECT TO NORMALLY CLOSEDDRY CONTACTS TO SHUT DOWN POWERSUPPLY IN CASE OF EMERGENCYDYNALOCKPOWER SUPPLY SHUTDOWNNO OUTPUT POWER AT A1 CHECK INPUT LINE POWER2 RESET POWER SUPPLY (WITH NO LOAD)BY DISCONNECTING POWER AT LEAST FOR 2 MINUTES3 MAKE SURE YOU HAVE A CLOSURE BETWEEN THE 2 SHUT DOWN TERMINALSPAGE 13

POWER SUPPLY ENCLOSURE1.25SIDE VENT HOLE PATTERN0.265 DIA.THRU(30 PLACES)2.125TYPICAL(4 PLACES)0.375 TYP.0.750.751.0(4) #6-32 x 1/4” PEM Studs (For Chassis Grounding)0.187 X 0.5SLOT THRUTYP. (3 PLACES)0.375 TYP.2.03.00.7510-1/2”19GA(0.42)0.6250.75 TYP.15.375” REF.COVER HEIGHT0.31213-1/4”0.2515.0” CLEARINSIDE �� CLEARINSIDE WIDTH4.0” CLEARINSIDEDEPTH6.1250.312 TYP.0.870 DIA. KNOCK-OUT TYP. (8 LOCATIONS)CC1.125 TYP. (8 K.O. LOCATIONS)1.125 TYP.PAGE 14

5000 SERIES PART LISTGRNGNDBLKLINEWHTNEUTDC IN FROM CONTROLLERRED( )RED( )BLK(-)BLK(-)TB3POWER OUTPUTH1-TB4LINE INPUT110 VAC 60 HZ2-CAUTIONDISCONNECTSUPPLY BEFORECHANGINGFUSESJP1G3 4 OUTPUTSTATUSTB2TB1BATTE RY3NEUTN24 V OLT2LINE12 VOLTF2SEEMANUAL1GNDDC OUT PUTF1S HUTDOWNAC OUT CONTROLLERCUT JUMPERWHEN RELAYIS INSTALLEDF3SEEMANUAL --5025 P/N 500280BATTERY INPUTREMOTE CONTROL INPUT5600 12VDCP/N 5003335600 24VDCP/N 5003345500 P/N 500221PRIMARY CIRCUIT BOARD PART NUMBERSDB-5 DISTRIBUTION BOARDP/N 500228ILB BOARDP/N 50025912DB-10 DISTRIBUTION BOARDP/N 5002293FUSES5600 REMOTE FIRE MODULE(FAC) PLUG IN RELAY1AMP P/N 5001494AMP3AMP P/NP/N 5003325002105AMP P/N 5000566AMP P/N 50020312AMP P/N 50022724VDC P/N 50030312VDC P/N 5003025500 REMOTE FIRE MODULE(FAC) PLUG IN RELAYP/N 500232PAGE 15

PLEASE DELIVER THIS MANUALTO THE END USER UPON COMPLETION OFTHE POWER SUPPLY INSTALLATIONFOR PRODUCT SUPPORT AND PARTSORDERING INFORMATION CONTACT:DynaLock Corp.705 Emmett StreetBristol, CT 06010Bus: (877) 396-2562 Toll-Free USA(860) 582-4761Fax: (860) 585-0338DYNALOCK ON THE INTERNET:E-mail: info@dynalock.comWebsite: www.dynalock.comQQFU/QQFU7 Power Supplies, General Purpose

model# 5500 (3 amp @ 12vdc or 2 amps @ 24vdc) model# 5600-12 (10 amps @ 12vdc) model# 5600-24 (5 amps @ 24vdc) important safety instructions this manual contains important safety instructions for power supply/battery charger models: 5025, 5500, 5600-12, 5600-24 before using the battery cha

Related Documents:

Ricoh Aficio MP 4000/5000 series Refer to Table 1 about product names for "Ricoh imagio MP 4000/5000 series" and "Ricoh Aficio MP 4000/5000 series". TOE Version : "Ricoh imagio MP 4000/5000 series" and "Ricoh Aficio MP 4000/5000 series" are identified by following software and hardware. Software System/Copy 1.09 Network Support 7.23

measured at the battery terminals with a battery connected. SUPER FILTERING (OPTIONAL) 30mV on battery only for 130Vdc chargers. ELIMINATOR (OPTIONAL) 30mV without battery for 24Vdc and 48Vdc chargers. 100mV without battery for 130Vdc chargers. 200mV without battery for 260Vdc chargers. * 260Vdc chargers

element is the Studio 5000 Logix Designer application. The Logix Designer application is the rebranding of RSLogix 5000 software and will continue to be the product to program Logix 5000 controllers for discrete, process, batch, motion, safety, and drive-based solutions. The Studio 5000 environment is the foundation for the future ofFile Size: 1MBPage Count: 71Explore furtherEmulate a Studio 5000 Controller and Connect to a .www.dmcinfo.comStudio 5000 Logix Emulate (Virtual PLC) - PLC Programmin www.plctr.comDownload Center Rockwell Automation United Stateswww.rockwellautomation.comStudio 5000 Logix Emulate FactoryTalk United Stateswww.rockwellautomation.comStudio 5000 Design Software FactoryTalk United Stateswww.rockwellautomation.comRecommended to you based on what's popular Feedback

engine rpm chart johnson rpm . 100 hp 1989 thru 4750-5250 2.07 115 hp 1989-2005 4750-5250 2.07 125 hp 1994-2005 4750-5250 2.07 135 hp 1990-1996 5000-5600 2.00 150 hp efi 2004 5000-6000 1.87 150 hp efi 2005 5000-5600 1.87 175 hp 1990-1999 5000-5600 1.87 175 hp efi 2000-2002 5000-5600 1.87 200 hp 1991-2005 5000-5600 1.87 200 hp efi 1994-2002 5000-5800 1.87 225 hp 1996-1998 5000-5500 1.64 .

electric vehicles (EV), California is striving to deploy 250,000 public and shared private electric vehicle chargers by 2025 and forecasts the need for 1.2 million chargers by 2030 for light-duty vehicles and 157,000 chargers for medium- and heavy-duty vehicles. The light-duty target includes public chargers that are available at parks, shopping

Nov 29, 2010 · Roundup Original Max 5000 5000 Moderate Moderate Roundup Pro Concentrate 5000 5000 Moderate Slight Roundup ProMax 5000 5000 Moderate Slight Roundup UltraDry 3700 5000 Moderate Slight Roundup

M14 40.2 103.7 148.4 173.4 M16 62 161 230 269 M18 86 222 318 372 M20 122 314 449 525 M22 166 428 613 716 M24 211 543 777 908 M27 309 796 1139 1331 . 6 BILL OF MATERIALS PER KIT 5000-040A – 6R30 JD StalkMaster 606C/706C – 2) 5000-160 Roller Bearing Bolt Bag, 4) 5000-167 Torsion Pivot Assembly, 4) 5000- 168 Torsion Mount Bolt Bag, 2) 5000-272 .

TSI 147kW GTI DSG Engine Cylinders 4 3 3 3 3 3 4 Capacity (cm3) 1 598 999 999 999 999 999 1 998 Power output (kW @ r/min) 66 @ 5000 70 @ 5000 70 @ 5000 70 @ 5000 85 @ 5000 85 @ 5000 147 @ 4400 Torque output (Nm @ r/min) N/A 175 @ 2000 175 @ 2000 175 @ 2000 200 @ 200